VL SERIES STEAMER - ELECTRICAL OPERATION

ELECTRICAL OPERATION

WATER LEVEL CONTROLS

Solid State - Low level Cut-Off & Differential Control

The steamer is equipped with three water level sensing probes (high, low and low level cut-off) and a single water level control board. The water level control board performs two functions:

1.Provide low level cut-off protection to shut off the heat source in case the water level drops below the low level cut-off (LLCO) probe.

2.Performs as a differential level control to maintain the water level between the low and high water level probes.

The water level control (WLC) has input voltage (120VAC) across terminals 11 and 12 which powers the transformer. On one side of the transformer secondary, power is provided to the control by a series path through chassis ground (terminal 10). The other side of the transformer secondary (12VAC) supplies power to one side of the internal relays LLCO, HL and ILR. As water enters the boiler, it becomes part of the water level control’s circuit. When the water level in the boiler reaches a probe, that circuit is completed.

The inverse latching relay of the board is de- energized, leaving the ILR-1 (N.O.) and ILR-2 (N.C.) contacts in their shelf state.

When the main power switch is turned ON, power is supplied to the WLC board which energizes the high level (HL) relay and illuminates the HL relay LED.

With the HL-3 contacts closed, the boiler fill solenoid is energized and water begins filling the boiler.

When the water level reaches the low level cut-off (LLCO) probe, the LLCO relay is energized and illuminates the LLCO LED. With the LLCO-2 contacts closed the heat source is then energized. The LLCO relay will remain energized and its LED will stay lit until the water level in the boiler drops below the LLCO probe.

When the water level reaches the low level (LL) probe, power to terminal 2 on the WLC board is present but no switching occurs.

After the water level reaches the high level (HL) probe, the inverse latching relay of the board is energized and locked through the low level probe

(LL)and ILR-1 contacts. With ILR-2 contacts open, this de-energizes the HL relay and the HL LED goes out. With the HL-3 contacts open, the boiler fill solenoid is de-energized, stopping the flow of water into the boiler.

When the water level drops below the low level (LL) probe, power is removed from the inverse latching relay, the HL relay energizes through ILR-2 and HL contacts change state. The fill solenoid is energized through HL-3 to refill the boiler and the HL LED is lit. The HL relay and LED will toggle ON and OFF during a cooking cycle as needed.

Page 38 of 88

Image 38
Contents VL Boiler Base Series Convection Steamers Table of Contents VL Series Steamers Introduction Water ConditioningSpecifications ToolsGas Steamers Electric SteamersRegenerated Steam Powered Boiler Gas Powered Steam BoilerElectrically Powered Steam Boiler Steamer OperationAutomatic blowdown Direct Steam Powered CookerBoiler Blowdown and Steamer Shut off Manual blowdownStandard Automatic Prevent High Limit Pressure Switch Water Level Gauge AssemblyCycling Pressure Switch Power SwitchBoiler Pressure Gauge Handhole Cover AssemblyDelime Port Assembly Check ValveThermal Switch Load Compensator Compartment Power SwitchCooking Timer Cooking Light RedRemoval and Replacement of Parts VL Series Steamers Removal and Replacement of Parts Cooking Compartment Controls Component Configurations Solid State Water Level Gauge AssemblyWater Level Controls LOW Level CUT OFF and Differential Electro MechanicalBoiler Assembly High Limit Thermostat GAS Combination Control Valve Boiler Fill and Cold Water Condenser Solenoid ValvesDoor Screw Nut Compartment Gasket and Door Screw NUT, Door and BushingsGasket Door and BushingHeating Elements Heater ContactorsSteam Coil Inspection Clean-Out All Boiler ModelsBoiler Deliming Only Models with Deliming Port Assembly Electro Mechanical Low level Cut-Off & Differential Control Water Level Controls TestSolid State Low level Cut-Off & Differential Control Water Level Probes Fill and Cold Water Solenoid Valves Compartment Pressure AdjustmentDisassembly Boiler not Filling with Water Boiler Blowdown Drain Solenoid ValveOlder Models Boiler Slow to PressurizeNewer Models All Models With BoilerDirect Steam Models Inlet Water StrainerElectric Models Regenerated Steam Coil SteamersVL Series Steamer Service Procedures and Adjustments Automatic Ignition Systems GAS Models Air Shutter AdjustmentGAS Burners Terminals Spark Ignition Control TestGAS Manifold Pressure Adjustment Direct Steam Models Regenerated Steam Older Models Heater ContactorsVL Series Steamer Service Procedures and Adjustments Thermal Switch Prevent Automatic Models Steam Gate Valves Electrical Operation Water Level ControlsSolid State Auxiliary Low Level Cut-Off Electro Mechanical Low level Cut-Off & Differential Control Electro Mechanical Auxiliary Low Level Cut-Off Sequence of Operation Initial Fill and PreheatVL Series Steamer Electrical Operation Cook Cycle Water Refill After Initial FillElectric Models Boiler Blowdown/drainCook Cycle Water Refill After Initial Fill Purposely Left Blank Manual Ignition, Standard Controls Electronic Ignition, Standard Controls Manual Ignition, CSD-1 Code Controls Electronic Ignition, CSD-1 Code Controls VL Series Steamer Electrical Operation Manual Ignition, Standard Controls VL Series Steamer Electrical Operation Electronic Ignition, Standard Controls VL Series Steamer Electrical Operation Manual Ignition, CSD-1 Code Controls VL Series Steamer Electrical Operation Electronic Ignition, CSD-1 Code Controls VL Series Steamer Electrical Operation Auto Blowdown, Standard Controls Auto Blowdown, Cal-Code Controls Auto Blowdown, Standard Controls contactor 1 std VL Series Steamer Electrical Operation Auto Blowdown, Standard Controls contactors 2 std VL Series Steamer Electrical Operation Manual Blowdown, Cal-Code Controls contactors 1 std aux VL Series Steamer Electrical Operation Auto Blowdown, Cal-Code Controls contactors 1 std aux VL Series Steamer Electrical Operation Auto Blowdown, Cal-Code Controls contactors 2 std aux VL Series Steamer Electrical Operation Manual Blowdown, Cal-Code Controls contactors 2 std aux VL Series Steamer Electrical Operation Standard and Cal-Code/CSD-1 Controls See Schematic and Wiring Diagrams Compartment Controls Manual Blowdown Older Models Auto Blowdown Older Models Schematic and Wiring Diagrams Compartment Controls Automatic Standard Manual Troubleshooting ALL ModelsContacts not closing to power boiler fill solenoid Schematic and Wiring Diagrams Symptom Possible Causes GAS Models onlyPilot not adjusted correctly. See Pilot

VL2GPS, VL3GPS, VL3GSS, VL2GSS, VL2GAS specifications

Vulcan-Hart is well-known in the commercial cooking equipment industry, providing durable and efficient products that cater to the needs of restaurants and foodservice operations. Their line of griddles, namely the VL3GAS, VL3GPS, VL3GMS, VL2GAS, and VL2GPS, showcases their commitment to high-quality performance and innovative cooking technologies.

The Vulcan-Hart VL3GAS is a gas griddle, featuring a robust stainless steel construction that ensures longevity and resilience in a bustling kitchen environment. It offers a smooth, hot cooking surface that allows for optimal heat retention and distribution, ensuring that food cooks evenly. With a 3/4-inch thick steel plate, it provides excellent thermal conductivity, making it ideal for high-volume cooking. This model is designed with easy-to-use controls, which makes it convenient for chefs to operate.

The VL3GPS model is a gas-powered griddle that comes equipped with a patented grease management system, which aids in maintaining a cleaner cooking environment. This system helps to separate grease from food and minimizes flare-ups, enhancing safety during cooking. Additionally, the griddle features a temperature control that allows chefs to set precise cooking temperatures, ensuring consistent results.

Moving to the VL3GMS, this model introduces increased versatility with its combination of gas and optional electric features. It’s tailored for establishments that require flexibility in their cooking strategies. The VL3GMS is also designed with a spacious cooking surface, making it suitable for preparing a wide array of dishes simultaneously.

The VL2GAS is a two-burner gas griddle that is specifically tailored for smaller kitchen operations or those with limited space. Its compact design does not compromise on performance, still providing a durable cooking surface and reliable temperature control. This model is ideal for smaller cafes or food trucks where space is at a premium.

Lastly, the VL2GPS complements the VL2GAS with its grease management system. This enhances hygiene and ensures that cooking remains efficient and safe. Both VL2 models offer easy startup and shutdown procedures, making them user-friendly for chefs working in fast-paced environments.

Overall, the Vulcan-Hart VL series griddles combine quality construction, innovative technology, and efficient design. Whether it’s the three-burner or two-burner options, these griddles meet the demands of commercial kitchens, providing reliable cooking solutions that serve the dynamic needs of the foodservice industry.