Step 2.3 Connecting the Power and communication cables (assembly cable)

If using a multi system, install as described in the installation manual supplied with the outdoor unit.

 

 

 

Control box

Before

 

 

 

 

connecting

 

 

 

 

Correct

Upside down

Damaged

Non-circular

After

 

 

 

 

connecting

 

 

 

 

Correct

Correct

Upside down

Non-fitted

(Front view)

(Side view)

<Circular terminal>

 

1(L)2(N)

F1 F2

 

 

Fasten the screws for the wire holders.

 

**07*******

**18*******

Model

**09*******

**24*******

 

**12*******

 

 

Power cable

3G X 2.5 mm²,

3G X 2.5 mm²,

(Outdoor unit)

H07RN-F

H07RN-F

Outdoor-to-

3G X 1.0 mm²,

3G X 1.0 mm²,

indoor power

H07RN-F

H07RN-F

cable

 

 

Communication

2 X 0.75 mm²,

2 X 0.75 mm²,

cable

H05RN-F

H05RN-F

Type GL

20A

25A

When performing electrical and earthing works, be sure to comply with the 'technical standards of electrical installations' and the 'wiring regulations' in the local regulations.

Tighten the terminal block screw to 1.2-1.8 N•m (1.2-1.8 kgf•cm).

NOTE

Each wire is labelled with the corresponding terminal number.

Use shield cable (Category 5; less than 50pF/m) for noisy environmental site.

Power supply cords of parts of appliances for outdoor use shall not be lighter than polychloroprene sheathed flexible cord. (Code designation IEC: 60245 IEC66/CENELEC: H07RN-F, IEC: 60245 IEC57 CENELEC: H05RN-F, IEC: 60227 IEC53: H05VV-F)

Power & Communication cable shall not exceed 30m.

CAUTION

For the terminal block wiring, use a wire with a ring terminal socket only. Regular wires without a ring terminal socket may become a hazard due to overheating of the electrical contact during installation.

If you need to extend the pipe, be sure to extend the cable, too.

 

(Unit : m)

 

 

Model

Cable (Maximum)

 

 

**07*******

 

**09*******

 

**12*******

30

**18*******

 

**24*******

 

Do not connect two or more different cables to extend the length. This connection may cause fire.

Each circular terminal must match the size of its corresponding screw in the terminal block.

After connecting the cables, make sure that terminal numbers on the indoor and outdoor units match.

Ensure that power and communication cables are separated, they must not be in the same cable.

10English

Image 10
Contents Air conditioner Contents Safety Information on Installation General informationInstall the unit in a place where water can drain smoothly Fires, explosions or injuriesMinimum clearances for the outdoor unit Choosing the installation locationPreparation CasesAccessories in the indoor unit package AccessoriesUnit mm Tools for test operation Accessories in the outdoor unit package Tools General tools Thermometer Resistance meter Electroscope EnglishDrilling a hole through the wall Taping the pipes, cables, and drain hoseDisassembling the cover panel Indoor Unit InstallationInstallation plate Remove the cap screws, then the screwsConnecting the Power and communication cables assembly cable Optional Extending the power cable Compression dimension should beOptional Extending the drain hose Installing and connecting the drain hoseInstall the drain hose FireOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe Pass the pipe through the hole in the wallWhen fixing the indoor unit on a wall 10 Fixing the installation plateWhen fixing the indoor unit on a window frame Fix the installation plate without inclining to one side 11 Fixing the indoor unit to the installation plateWhen fixing the indoor unit on a gypsum board 12 Assembling the cover panelRefrigerant pipes Outdoor Unit InstallationFixing the outdoor unit in place That the fan can operate correctlyEvacuating the air Leave the system in the standby modeCooling capacity and malfunction. Use a vacuum pump Adding refrigerant Siphon①+②, c Installation Inspection Running the Smart Install modeMotor Connector Remove foreign substance. Check Error betweenPower cable or communication Blocking error OpenPumping down for removing the product Check the following Strength of the installation sitePerforming final check and trial operation Let the compressor run for more than 5 minutesAttach the Sub PCB to the Case Sub PCB Sub PCB installationoptionalAssemble the Case Sub PCB to the indoor unit DB68-06732A-03