Installation Inspection

Step 4.1 Performing the gas leak tests

1Before inspecting the leakage, use a torque wrench to close the cap for the stop valve. (Comply with a tightening torque for each size of the diameter, and tighten the cap firmly to prevent any leakage.)

Tightening torque for body cap (Refer to the table)

Charging core

Spindle

R-22: Thread of the screw - 7/16-2OUNF

R-410A: Thread of the screw -1/2-2OUNF

Tightening torque for charging port cap (Refer to the table)

Outer diameter

Tightening torque

(mm)

Body cap (N•m)

Charging port cap (N•m)

 

 

 

 

ø 6.35

20 to 25

 

 

 

 

ø 9.52

20 to 25

 

 

 

 

ø 12.70

25 to 30

10 to 12

 

 

 

ø 15.88

30 to 35

 

 

 

 

Over ø 19.05

35 to 40

 

 

 

 

( 1 N•m = 10 kgf•cm )

2Insert inert gas into the pipes connected to indoor and outdoor units.

3Test leakage on the connection parts of the indoor and outdoor units with soap lather or liquid.

Test parts for the indoor unit

Test parts for the indoor unit

Step 4.2 Running the Smart Install mode

If using a multi system, this function is not supported.

1Make sure that the air conditioner is in the standby status.

2Hold down the (Power), (Mode) and

(SET / Temperature type ()) buttons on the remote control simultaneously for 4 seconds.

3Wait until Smart Install mode succeeds or fails. It takes approximately 7 to 13 minutes.

• While Smart Install mode is proceeding:

Type

Display

LED Display

 

 

LED1

 

 

LED2

 

 

LED3

Indoor

 

 

unit

The progress is

The LEDs on the

indicator

indoor unit display

 

displayed as a

blink in sequence,

 

number between

 

then all of them

 

0 and 99 on

 

blink simultaneously.

 

the indoor unit

 

These operations

 

display.

 

repeat.

 

 

When Smart Install mode succeeds: Smart Install mode ends with ringing sound, and the air conditioner is in standby status.

When Smart Install mode fails: An error message is displayed on the indoor unit display, and Smart Install mode ends.

NOTE

Smart Install mode can be operated only with the supplied remote control.

During the Smart install mode procedure, remote control cannot be operated.

English 21

Installation

Image 21
Contents Air conditioner Contents General information Safety Information on InstallationFires, explosions or injuries Install the unit in a place where water can drain smoothlyPreparation Choosing the installation locationMinimum clearances for the outdoor unit CasesAccessories Accessories in the indoor unit packageUnit mm Tools General tools Accessories in the outdoor unit packageTools for test operation Thermometer Resistance meter Electroscope EnglishTaping the pipes, cables, and drain hose Drilling a hole through the wallInstallation plate Indoor Unit InstallationDisassembling the cover panel Remove the cap screws, then the screwsConnecting the Power and communication cables assembly cable Compression dimension should be Optional Extending the power cableInstall the drain hose Installing and connecting the drain hoseOptional Extending the drain hose FireOptional Changing the direction of the drain hose Pass the pipe through the hole in the wall Shortening or extending the refrigerant pipes assembly pipe10 Fixing the installation plate When fixing the indoor unit on a wallWhen fixing the indoor unit on a window frame When fixing the indoor unit on a gypsum board 11 Fixing the indoor unit to the installation plateFix the installation plate without inclining to one side 12 Assembling the cover panelFixing the outdoor unit in place Outdoor Unit InstallationRefrigerant pipes That the fan can operate correctly Leave the system in the standby mode Evacuating the air Cooling capacity and malfunction. Use a vacuum pump Siphon Adding refrigerant①+②, c Running the Smart Install mode Installation InspectionPower cable or communication Error betweenMotor Connector Remove foreign substance. Check Blocking error OpenPerforming final check and trial operation Check the following Strength of the installation sitePumping down for removing the product Let the compressor run for more than 5 minutesSub PCB installationoptional Attach the Sub PCB to the Case Sub PCBAssemble the Case Sub PCB to the indoor unit DB68-06732A-03