Samsung AR12MSPXBWKNEU manual Performing final check and trial operation, Disconnect the pipes

Page 23

Step 4.3 Performing final check and trial operation

1Check the following:

Strength of the installation site

Tightness of pipe connection to detect gas leak

Electric wiring connection

Heat-resistant insulation of the pipe

Drainage

Grounding conductor connection

Correct operation (Take the following steps.)

2Press the (Power) button on the remote control to check the following:

The indicator on the indoor unit lights up.

The airflow blade opens and the fan gears up for operation.

3Press the (Mode) button to select Cool or Heat mode. Then take the following sub-steps:

In Cool mode, use the Temperature button to set the set temperature to 16 °C.

In Heat mode, use the Temperature button to set the set temperature to 30 °C.

Check whether, approximately 3 to 5 minutes later, the outdoor unit starts, and a cool air blows out.

After12 minutes of stationary condition, check the indoor unit air treatment.

4Press the (Air swing) button to check whether the airflow blades work properly.

5Press the (Power) button to stop the trial operation.

Pumping down for removing the product

Pump-down is an operation intended to collect all the system refrigerant in the outdoor unit. This operation must be carried out before disconnecting the refrigerant tubing in order to avoid refrigerant loss to the atmosphere.

WARNING

After installing the product, be sure to perform leak tests on the piping connections. After pumping down refrigerant to inspect or relocate the outdoor unit, be sure to stop the compressor and then remove the connected pipes.

–– Do not operate the compressor while a valve is open due to refrigerant leakage from a pipe or an unconnected or incorrectly connected pipe. Failure to do so may cause air to flow into the compressor and too a high pressure to develop inside the refrigerant circuit, leading to an explosion or product malfunction.

1Hold down the (Power) button on the indoor unit for 5 seconds. Beep sounds immediately to indicate that the product is ready for pump down procedure.

2Let the compressor run for more than 5 minutes.

3Release the valve caps on High and Low pressure side.

4Use L-wrench to close the valve on the high pressure side.

5After approximately1 minute, close the valve on the low pressure side.

6Stop operation of the air conditioner by pressing the (Power) button on the indoor unit or remote control.

7Disconnect the pipes.

CAUTION

Compressor damage may occur if the compressor is run at a negative suction pressure.

 

1

 

1 minute

Liquid service port

Gas service port

<High pressure>

<Low pressure>

2

Off

English 23

Installation

Image 23
Contents Air conditioner Contents General information Safety Information on InstallationFires, explosions or injuries Install the unit in a place where water can drain smoothlyCases Choosing the installation locationPreparation Minimum clearances for the outdoor unitUnit mm AccessoriesAccessories in the indoor unit package Thermometer Resistance meter Electroscope English Accessories in the outdoor unit packageTools General tools Tools for test operationTaping the pipes, cables, and drain hose Drilling a hole through the wallRemove the cap screws, then the screws Indoor Unit InstallationInstallation plate Disassembling the cover panelConnecting the Power and communication cables assembly cable Compression dimension should be Optional Extending the power cableFire Installing and connecting the drain hoseInstall the drain hose Optional Extending the drain hoseOptional Changing the direction of the drain hose Pass the pipe through the hole in the wall Shortening or extending the refrigerant pipes assembly pipeWhen fixing the indoor unit on a window frame 10 Fixing the installation plateWhen fixing the indoor unit on a wall 12 Assembling the cover panel 11 Fixing the indoor unit to the installation plateWhen fixing the indoor unit on a gypsum board Fix the installation plate without inclining to one sideThat the fan can operate correctly Outdoor Unit InstallationFixing the outdoor unit in place Refrigerant pipesCooling capacity and malfunction. Use a vacuum pump Leave the system in the standby modeEvacuating the air Siphon Adding refrigerant ①+②, c Running the Smart Install mode Installation InspectionBlocking error Open Error betweenPower cable or communication Motor Connector Remove foreign substance. CheckLet the compressor run for more than 5 minutes Check the following Strength of the installation sitePerforming final check and trial operation Pumping down for removing the productAssemble the Case Sub PCB to the indoor unit Sub PCB installationoptionalAttach the Sub PCB to the Case Sub PCB DB68-06732A-03