Samsung AR09MSPXASIXEU manual Shortening or extending the refrigerant pipes assembly pipe

Page 14

Installation

3Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

Outer diameter (mm)

Torque (N•m)

Torque (kgf•cm)

 

 

 

ø 6.35

14 to 18

140 to 180

 

 

 

ø 9.52

34 to 42

350 to 430

 

 

 

ø 12.70

49 to 61

500 to 620

 

 

 

ø 15.88

68 to 82

690 to 830

 

 

 

NOTE

If you want to shorten or extend the pipes, see Step 2.9 Shortening or extending the refrigerant pipes (assembly pipe) on page 14.

4Cut off the remaining foam insulation.

5If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

6Pass the pipe through the hole in the wall.

7Fix the indoor unit on the wall.Pass the cables, pipes and hose through the knock-out hole which would be connected to the outdoor unit .

8Use 2 screws to fix the indoor unit as shown in the picture 2.

9Assemble the Guide into the position of A or B as shown in the picture 3.

NOTE

The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test. For further details. see Step 4.1 Performing the gas leak tests on page 21.

CAUTION

Tighten the flare nut with a torque wrench according to specified method. If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Do not box in or cover the pipe connection. All refrigerant pipe connection must be easily accessible and serviceable.

Step 2.9 Shortening or extending the refrigerant pipes (assembly pipe)

 

 

Pipe cutter

 

 

 

Pipe

 

90°

Oblique

Rough

Burr

D

 

90°±2°

 

 

 

A

45°±2°

 

 

 

 

L

 

 

R 0.4 to 0.8

Pipe

Flare

D

 

 

 

 

(Unit: mm)

Outer diameter (D)

Depth (A)

Flare dimension (L)

ø 6.35

1.3

8.7 to 9.1

ø 9.52

1.8

12.8 to 13.2

ø 12.70

2.0

16.2 to 16.6

ø 15.88

2.2

19.3 to 19.7

 

 

Flare nut

Indoor outlet pipe

 

Connecting pipe

Outer diameter (mm) Torque (N•m)

Torque (kgf•cm)

ø 6.35

14 to 18

140 to 180

ø 9.52

34 to 42

350 to 430

ø 12.70

49 to 61

500 to 620

ø 15.88

68 to 82

690 to 830

14English

Image 14
Contents Air conditioner Contents Safety Information on Installation General informationInstall the unit in a place where water can drain smoothly Fires, explosions or injuriesMinimum clearances for the outdoor unit Choosing the installation locationPreparation CasesUnit mm AccessoriesAccessories in the indoor unit package Tools for test operation Accessories in the outdoor unit packageTools General tools Thermometer Resistance meter Electroscope EnglishDrilling a hole through the wall Taping the pipes, cables, and drain hoseDisassembling the cover panel Indoor Unit InstallationInstallation plate Remove the cap screws, then the screwsConnecting the Power and communication cables assembly cable Optional Extending the power cable Compression dimension should beOptional Extending the drain hose Installing and connecting the drain hoseInstall the drain hose FireOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe Pass the pipe through the hole in the wallWhen fixing the indoor unit on a window frame 10 Fixing the installation plateWhen fixing the indoor unit on a wall Fix the installation plate without inclining to one side 11 Fixing the indoor unit to the installation plateWhen fixing the indoor unit on a gypsum board 12 Assembling the cover panelRefrigerant pipes Outdoor Unit InstallationFixing the outdoor unit in place That the fan can operate correctlyCooling capacity and malfunction. Use a vacuum pump Leave the system in the standby modeEvacuating the air Adding refrigerant Siphon①+②, c Installation Inspection Running the Smart Install modeMotor Connector Remove foreign substance. Check Error betweenPower cable or communication Blocking error OpenPumping down for removing the product Check the following Strength of the installation sitePerforming final check and trial operation Let the compressor run for more than 5 minutesAssemble the Case Sub PCB to the indoor unit Sub PCB installationoptionalAttach the Sub PCB to the Case Sub PCB DB68-06732A-03