Preparation
Step 1.1 Choosing the installation location
If using a multi system, install as described in the installation manual supplied with the outdoor unit.
Overview of installation location requirements
|
| 100 mm or more |
125 mm |
| 125 mm |
or more |
| or more |
|
|
|
Drain hose hole
You can select the direction of
draining (left or right).
Maximum pipe height: 8/15 m
Maximum pipe length: 15/30 m
Make at least one round to reduce noise and vibration.
The actual units may look different from the images depicted here.
|
|
| (Unit : m) | |
Model |
| Pipe length | Pipe height | |
Minimum Maximum | Maximum | |||
| ||||
**07******* | 3 | 15 | 8 | |
**09******* | ||||
**12******* |
|
|
| |
**18******* | 3 | 30 | 15 | |
**24******* | ||||
|
|
| ||
Outdoor |
| Make a | ||
Unit | CAUTION | (which is connected to the indoor | ||
Outer wall |
| unit) at outer wall and cut the | ||
Indoor |
| bottom part of the insulation | ||
| (about 10 mm) to prevent | |||
Unit |
| rainwater from getting inside | ||
Cut insulation to have |
| through the insulation. | ||
|
|
| ||
rainwater drained |
|
|
|
CAUTION
•Comply with the length and height limits described in the figure above.
Minimum clearances for the outdoor unit
|
| Wall |
|
|
|
| Minimum clearance in mm |
| |
|
|
| 300 |
|
|
| 600 |
|
|
|
| Air flow direction |
| |
|
| Top view | Side view |
|
When installing 1 outdoor unit |
| (6 cases) | ||
|
|
|
| (Unit: mm) |
|
| 300 |
| 1500 |
300 |
|
| 2000 | 1500 |
| 150 | 600 |
|
|
500 | 300 |
|
| 300 |
|
|
| ||
|
|
|
| 1500 |
Installation
English 5