Samsung AQV18YWAX manual Connecting the assembly cable, Cable specification, Connecting the cable

Page 30

Fixing the installation plate

2.Determine the position of the pipe and drain hose hole as seen in the picture and drill the hole with an inner diameter of 65mm so that it slants slightly downwards.

Pipe hole

 

(Ø65mm)

 

A

D

B

C

3. Fix the indoor unit.

If you fix the indoor unit on a wall

(Unit : mm)

Model

A

B

C

D

AQVK/Y

20

120

95

20

Make sure to drill only one hole after choosing the direction of the pipe.

(1) Fix the installation plate to the wall giving attention to the weight of the indoor unit.

 

 

 

 

• If you mount the plate to a concrete wall using plastic anchors, make sure that

Plastic

 

 

 

 

 

 

 

 

 

 

 

 

gaps between the wall and the plate, created by projected anchor, is less than

Anchor

 

 

 

 

 

 

 

 

 

 

 

 

<20mm

 

 

 

 

 

 

 

20mm.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If you fix the indoor unit on a window frame

If you fix the indoor unit on a gypsum board

 

 

 

Wall

(1)Determine the positions of the wooden uprights to be attached to the window frame.

(2)Attach the wooden uprights to the window frame giving attention to the weight of the indoor unit.

(3)Attach the installation plate to the wooden upright using tapping screws.

(1)Use stud finder to find out locations of the studs.

(2)Fix the plate hanger on two studs.

Search for other spots if there are less than two studs, or the distance between the studs are different from the plate hanger.

Fix the installation plate without inclining to one side.

Make sure that a wall can withstand the weight of the product. If you install the product in a place where it is not

strong enough to withstand the product weight, the unit could fall and cause injury.

Connecting the assembly cable

If using a multi system, refer to the manual supplied with the outdoor unit.

Cable specification

Model

Power cable

Power

Interconnection cable

Type GL

(Outdoor Unit)

(Indoor-Outdoor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

09/12

3G, 2.5mm² H07RN-F

Power Supply

3G,1.5mm², H07RN-F

 

20A

F1/F2 Communication

2G,0.75mm², H05RN-F

 

 

 

 

 

 

18

3G, 2.5mm² H07RN-F

Power Supply

3G, 1.5mm², H07RN-F

 

25A

F1/F2 Communication

2G, 0.75mm², H05RN-F

 

 

 

 

 

 

• Connect the power cable to the auxiliary circuit breaker. If every pole fails to connect to the power supply,

it must be incorporated in a wire with a contact opening of ≥3mm.

Connecting the cable

When you install the unit, make first refrigerant connections and then electrical connections. Connect the air conditioner to grounding system before performing the electrical connection. If unit is uninstalled, first disconnect electrical cables, then refrigerant connections.

If the outdoor unit is more than 5 meters away from the indoor unit, you must extend the cable. The maximum length of the cable is 15(09/12)/20(18) meters.

30

Jungfrau_AQV09K&Y@@_IBIM_32448A_E.indd 30

2012-4-7 16:43:08

Image 30 Contents
AQV09K&Y@@JungfrauIBIME32448A.indd 2011-3-19 Contents Follow directions Safety precautionsImportant safety symbols and precautions Wall socketFor Using For Cleaning Checking before use Operation rangesModel RJ Checking the name of the parts Main partsDisplay Checking the remote controller Remote controller buttonsStoring the remote controller Remote controller displayBattery changing time Inserting the batteriesBasic function Button to adjust the temperature PressPress the Air swing button on the remote controller Adjusting the air flow directionUsing the Turbo function Vertical air flowPress the Set/Cancel button to active it When the air conditioner is on and in cool/heat modePress the button on the remote controller ModeSetting the Current time Setting the On/Off timerAdditional options available in On timer mode Follow the same process for setting on timer and off timerUsing the Smart Saver function Using the SPi functionWhen the air conditioner is turned on Using the Auto Clean functionUsing the dlight Cool function Cancel Press the Auto clean button once againUsingAA the Quiet function You can reduce the noise generated from an indoor unitOpening the panel Cleaning the indoor unitCleaning the outdoor unit heat exchanger Heat exchangerRemoving the Full HD filter Cleaning the air conditionerCleaning the Full HD filter Dry the Full HD filter in a ventilated areaMaintaining the air conditioner Periodical checksTroubleshooting Noise is generated Error is indicatedAll blink Outdoor unitGeneral information Included Models RemarkPower supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit  a place where the air filter can be replaced easilyWhere sulfide gas exists Outdoor UnitModel Space Requirements for Outdoor Unit When installing 1 outdoor unitWhen installing more than 1 outdoor unit Side viewAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case Unit mmTools required for installation General Tools Fixing the installation plateOptional accessories Tools for test operationsConnecting the assembly cable Cable specificationConnecting the cable Extend the assembly cable if necessary Each wire is labeled with the corresponding terminal numberSmooth the cut edges Cut off the remaining foam insulationUnscrew the caps at the end of each pipe Purging the indoor unitCutting or extending the pipe Put a flare nut slightly into the pipe and modify the flareCracked Pipe 50 Pa. The joint must be accessible and serviceableCorrect Inclined Outer DiameterDrain hose installation Drain hole Drain plug Drain hose Purging the connected pipesConnect a drain hose to the drain plug Ensure that condensation draining is adequateIf you use a pipe longer than 5m Gas service port as seen in the pictureAdding Refrigerant If you use a pipe shorter than 5mPlease fill in with indelible ink  the factory refrigerant charge of the product1975 To check for gas leaks on the indoor unit Performing the gas leak testsTo check for gas leaks on the outdoor unit Leak test with nitrogen before opening valvesFixing the outdoor unit in place Then place the indoor unit on the installation plateFixing the indoor unit in place 612Final Check and Trial Operation After tube contraction work is completed, wrap it with How to connect your extended power cablesApply heat to the contraction tube to contract it Insulation tape to finishSub PCB installationoptional Only for multi system Wried remote controller, central remote controller etcQuestions or COMMENTS? Air Conditioner
Related manuals
Manual 45 pages 23.92 Kb Manual 43 pages 36.93 Kb Manual 43 pages 57.93 Kb Manual 45 pages 57.87 Kb Manual 43 pages 7.81 Kb Manual 43 pages 10.58 Kb Manual 45 pages 17.94 Kb Manual 43 pages 52.7 Kb Manual 42 pages 45.49 Kb Manual 43 pages 11.43 Kb Manual 43 pages 54.66 Kb Manual 45 pages 44.27 Kb Manual 23 pages 29.57 Kb Manual 52 pages 58.4 Kb Manual 52 pages 46.07 Kb Manual 1 pages 8.03 Kb Manual 23 pages 40.87 Kb Manual 25 pages 1.01 Kb Manual 23 pages 9.1 Kb Manual 52 pages 18.48 Kb Manual 23 pages 42.75 Kb Manual 23 pages 46.31 Kb Manual 16 pages 35.53 Kb Manual 23 pages 46.82 Kb Manual 16 pages 16.35 Kb