Samsung AQV12YWAX, AQV12KBAN manual Smooth the cut edges, Cut off the remaining foam insulation

Page 32

Installing and connecting the assembly pipe of the indoor unit

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

The smaller one is for the liquid refrigerant

The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You may need to extend the pipe using the assembly pipe (optional).

The connection procedure for the refrigerant pipe varies according to the exit position of the pipe when facing the wall:

• Right(A)

A

B

 

 

• Left(B)

 

C

• Underside(C)

 

 

 

• Rear

 

 

1.Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2.Smooth the cut edges.

3.Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque.

• If you want to shorten or extend the pipes, refer to page 33~34.

4.Cut off the remaining foam insulation.

5.If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

6.Pass the pipe through the hole in the wall.

7.For further details on how to connect to the outdoor unit and purge the air, refer to page 36~38.

• The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test;

refer to page 39~40 for further details.

Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

DO NOT WALL UP THE PIPE CONNECTION !

All refrigerant pipe connection must be easy accessible and serviceable.

32

AQV09K&Y@@_Jungfrau_IBIM_E_32448A.indd 32

2011-3-19 15:45:43

Image 32 Contents
AQV09K&Y@@JungfrauIBIME32448A.indd 2011-3-19 Contents Safety precautions Important safety symbols and precautionsFollow directions Wall socketFor Using For Cleaning Model RJ Checking before useOperation ranges Display Checking the name of the partsMain parts Checking the remote controller Remote controller buttonsRemote controller display Battery changing timeStoring the remote controller Inserting the batteriesBasic function Button to adjust the temperature PressAdjusting the air flow direction Using the Turbo functionPress the Air swing button on the remote controller Vertical air flowWhen the air conditioner is on and in cool/heat mode Press the button on the remote controllerPress the Set/Cancel button to active it ModeSetting the Current time Setting the On/Off timerAdditional options available in On timer mode Follow the same process for setting on timer and off timerUsing the Smart Saver function Using the SPi functionUsing the Auto Clean function Using the dlight Cool functionWhen the air conditioner is turned on Cancel Press the Auto clean button once againUsingAA the Quiet function You can reduce the noise generated from an indoor unitCleaning the indoor unit Cleaning the outdoor unit heat exchangerOpening the panel Heat exchangerCleaning the air conditioner Cleaning the Full HD filterRemoving the Full HD filter Dry the Full HD filter in a ventilated areaMaintaining the air conditioner Periodical checksTroubleshooting Error is indicated All blinkNoise is generated Outdoor unitGeneral information Included Models RemarkChoosing the installation location Installing the unitPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyModel Where sulfide gas existsOutdoor Unit When installing 1 outdoor unit When installing more than 1 outdoor unitSpace Requirements for Outdoor Unit Side viewAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case Unit mmFixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsConnecting the cable Connecting the assembly cableCable specification Extend the assembly cable if necessary Each wire is labeled with the corresponding terminal numberSmooth the cut edges Cut off the remaining foam insulationPurging the indoor unit Cutting or extending the pipeUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flarePipe 50 Pa. The joint must be accessible and serviceable Correct InclinedCracked Outer DiameterDrain hose installation Purging the connected pipes Connect a drain hose to the drain plugDrain hole Drain plug Drain hose Ensure that condensation draining is adequateGas service port as seen in the picture Adding RefrigerantIf you use a pipe longer than 5m If you use a pipe shorter than 5m1975 Please fill in with indelible ink the factory refrigerant charge of the product Performing the gas leak tests To check for gas leaks on the outdoor unitTo check for gas leaks on the indoor unit Leak test with nitrogen before opening valvesThen place the indoor unit on the installation plate Fixing the indoor unit in placeFixing the outdoor unit in place 612Final Check and Trial Operation How to connect your extended power cables Apply heat to the contraction tube to contract itAfter tube contraction work is completed, wrap it with Insulation tape to finishSub PCB installationoptional Only for multi system Wried remote controller, central remote controller etcQuestions or COMMENTS? Air Conditioner
Related manuals
Manual 45 pages 23.92 Kb Manual 43 pages 36.93 Kb Manual 43 pages 57.93 Kb Manual 45 pages 57.87 Kb Manual 43 pages 7.81 Kb Manual 43 pages 10.58 Kb Manual 45 pages 17.94 Kb Manual 43 pages 52.7 Kb Manual 42 pages 45.49 Kb Manual 43 pages 11.43 Kb Manual 43 pages 54.66 Kb Manual 45 pages 44.27 Kb Manual 23 pages 29.57 Kb Manual 52 pages 58.4 Kb Manual 52 pages 46.07 Kb Manual 1 pages 8.03 Kb Manual 23 pages 40.87 Kb Manual 25 pages 1.01 Kb Manual 23 pages 9.1 Kb Manual 52 pages 18.48 Kb Manual 23 pages 42.75 Kb Manual 23 pages 46.31 Kb Manual 16 pages 35.53 Kb Manual 23 pages 46.82 Kb Manual 16 pages 16.35 Kb