Samsung AQV09KBAN, AQV12KBAN, AQV12YWAN, AQV09YWAX manual Please fill in with indelible ink, 1975

Page 38

Purging the connected pipes

Important information regulation regarding the refrigerant used

This product contains fluorinated greenhouse gases covered by the Kyoto Protocol.

Do not vent gases into the atmosphere.

1.Please fill in with indelible ink,

the factory refrigerant charge of the product,

the additional refrigerant amount charged in the field and

+the total refrigerant charge. on the refrigerant charge label supplied with the product.

a. Factory refrigerant charge of the product: see unit name plate

b.Additional refrigerant amount charged in the field (Refer to the above information for the quantity of refrigerant replenishment.)

c.Total refrigerant charge

d.Refrigerant cylinder and manifold for charging

Refrigerant type

GWP value

R410A

1975

GWP=Global Warming Potential

Contains fluorinated greenhouse gases covered by the Kyoto Protocol.

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

 

 

 

 

 

 

 

Outdoor unit

= (

 

 

) kg

 

 

 

 

 

 

 

= (

 

 

) kg += (

 

) kg

 

 

 

b

 

 

 

 

c

• The filled-out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve cover).

Charging the refrigerant under conditions of liquid by using a liquid pipe

R410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment, follow the instructions below.

1.Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the refrigerant.

Cylinder with siphon

Cylinder without siphon

siphon

Charge the refrigerant standing the cylinder upright.

Charge the refrigerant turning the cylinder upside down.

• If R410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the

characteristics of the equipment vary.

During the measuring operation of refrigerant quantity added use an electronic balance.

If cylinder doesn’t have syphon, upset it.

38

AQV09K&Y@@_Jungfrau_IBIM_E_32448A.indd 38

2011-3-19 15:45:56

Image 38 Contents
AQV09K&Y@@JungfrauIBIME32448A.indd 2011-3-19 Contents Follow directions Safety precautionsImportant safety symbols and precautions Wall socketFor Using For Cleaning Model RJ Checking before useOperation ranges Display Checking the name of the partsMain parts Checking the remote controller Remote controller buttonsStoring the remote controller Remote controller displayBattery changing time Inserting the batteriesBasic function Button to adjust the temperature PressPress the Air swing button on the remote controller Adjusting the air flow directionUsing the Turbo function Vertical air flowPress the Set/Cancel button to active it When the air conditioner is on and in cool/heat modePress the button on the remote controller ModeSetting the Current time Setting the On/Off timerAdditional options available in On timer mode Follow the same process for setting on timer and off timerUsing the Smart Saver function Using the SPi functionWhen the air conditioner is turned on Using the Auto Clean functionUsing the dlight Cool function Cancel Press the Auto clean button once againUsingAA the Quiet function You can reduce the noise generated from an indoor unitOpening the panel Cleaning the indoor unitCleaning the outdoor unit heat exchanger Heat exchangerRemoving the Full HD filter Cleaning the air conditionerCleaning the Full HD filter Dry the Full HD filter in a ventilated areaMaintaining the air conditioner Periodical checksTroubleshooting Noise is generated Error is indicatedAll blink Outdoor unitGeneral information Included Models RemarkPower supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit  a place where the air filter can be replaced easilyModel Where sulfide gas existsOutdoor Unit Space Requirements for Outdoor Unit When installing 1 outdoor unitWhen installing more than 1 outdoor unit Side viewAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case Unit mmTools required for installation General Tools Fixing the installation plateOptional accessories Tools for test operationsConnecting the cable Connecting the assembly cableCable specification Extend the assembly cable if necessary Each wire is labeled with the corresponding terminal numberSmooth the cut edges Cut off the remaining foam insulationUnscrew the caps at the end of each pipe Purging the indoor unitCutting or extending the pipe Put a flare nut slightly into the pipe and modify the flareCracked Pipe 50 Pa. The joint must be accessible and serviceableCorrect Inclined Outer DiameterDrain hose installation Drain hole Drain plug Drain hose Purging the connected pipesConnect a drain hose to the drain plug Ensure that condensation draining is adequateIf you use a pipe longer than 5m Gas service port as seen in the pictureAdding Refrigerant If you use a pipe shorter than 5m1975 Please fill in with indelible ink the factory refrigerant charge of the product To check for gas leaks on the indoor unit Performing the gas leak testsTo check for gas leaks on the outdoor unit Leak test with nitrogen before opening valvesFixing the outdoor unit in place Then place the indoor unit on the installation plateFixing the indoor unit in place 612Final Check and Trial Operation After tube contraction work is completed, wrap it with How to connect your extended power cablesApply heat to the contraction tube to contract it Insulation tape to finishSub PCB installationoptional Only for multi system Wried remote controller, central remote controller etcQuestions or COMMENTS? Air Conditioner
Related manuals
Manual 45 pages 23.92 Kb Manual 43 pages 36.93 Kb Manual 43 pages 57.93 Kb Manual 45 pages 57.87 Kb Manual 43 pages 7.81 Kb Manual 43 pages 10.58 Kb Manual 45 pages 17.94 Kb Manual 43 pages 52.7 Kb Manual 42 pages 45.49 Kb Manual 43 pages 11.43 Kb Manual 43 pages 54.66 Kb Manual 45 pages 44.27 Kb Manual 23 pages 29.57 Kb Manual 52 pages 58.4 Kb Manual 52 pages 46.07 Kb Manual 1 pages 8.03 Kb Manual 23 pages 40.87 Kb Manual 25 pages 1.01 Kb Manual 23 pages 9.1 Kb Manual 52 pages 18.48 Kb Manual 23 pages 42.75 Kb Manual 23 pages 46.31 Kb Manual 16 pages 35.53 Kb Manual 23 pages 46.82 Kb Manual 16 pages 16.35 Kb