Samsung SSA-P400/EXP, SSA-P400T/EXP manual Installation and external connection

Page 14

installation and external connection

EARTH-GROUNDING THE COMMUNICATION CABLES

We recommend you to use a proper grounding system for the communication cables.

The best grounding method is to earth-ground the shield wire of the communication cable. However, the earth-grounding of the communication cable is not easy at all, and it also causes an increased installation cost. There are three grounding points available for installation:

1.Earth Ground

2.Chassis Ground

3.Power Ground

The most important thing about the earth-grounding lies in connecting neither end of the shield wire to the grounding system simultaneously. This will cause a current flow through the shield wire when the voltage level of both ends of the shield wire is not equal and this current flow will introduce some noise and interference to communications.

It is recommended to connect ONLY one end of the shield wire of the communication cable to the grounding system. If you can locate an earth grounding point nearby, connect one end of the shield wire to that point. If you could hardly locate an earth grounding point nearby, connect one end of the shield wire to the chassis ground point. If you could locate neither of an earth or chassis grounding point nearby, connect one end of the shield wire to the power ground point (GND). Note that if the chassis is not properly earthed and floated from the ground level, then grounding communication cable to the chassis will produce the worst communication. If this is the case, use the power ground point rather than the chassis ground.

HOST PC

RS-422/RS-232

RS-232Converter

RS-422

RS-422 Cable

Communication

Wires

Connect ShieldWire Open

Earth Ground

or Chasis Ground or Power Ground

GND

RS-422

RS-422

RS-422

GND

GND

GND

#1

#2

#3

#n

14_ installation and external connection

Image 14
Contents Access Control Panel Please visit our websiteSafety information Safety informationImportant Safety Instructions Contents Features Product introductionSettings Input Port Format SetupDoor Open Alarm and Forced Door Open Alarm Holiday SetupCD Manual WHAT’S IncludedMain Unit Switch System after the initialization Output Relay #1 ~ Board ID SetupSwitch Address Setup 5V for any output occurrence SwitchSignal occurs IndicatoradditionallyInput LED Indicator Buzzer control settingsConnector used to connect to the main board BoardInput port #10 Input port #8Input port #9 Input port #11Cable Selection Host P.CBypass Diode Connection Connecting the Termination Resistor and DiodeTermination Resistor Termination Resistor in RS-485 CommunicationInstallation and external connection EARTH-GROUNDING the Communication CablesReader Connection POWER, READER, and I/O ConnectionPower Connection Input Connection Exit Button Connection Input #1, Input #3Output Connection DC +12V GNDHost PC Communication Line ConnectionRS-232 Communication Port Connection Check the location of the communication portTX+ RS-422 Communication Port Connection StandaloneHost RX+RS-422 Communication Port Connection Multiple Units TX+ RX+TCP/IP Communication Configuration TCP/IP Communication Port ConnectionHUB TCP / IP TCP/IP ConnectionInitialization Initializing the system using the Initialize switchSwitches simultaneously System InitializationBoard ID Setting You can specify between 0 and 255 for the board IDProblem Action TroubleshootingTroubleshooting No communication is available ProblemWhen the system is in sync with Product Specifications Product specificationsCorrect disposal of batteries in this product