product introduction
Input Port Format Setup
15 input ports are provided by default. For these ports, you can specify if the format of the incoming signal is blocked (NO) or connected (NC) in normal operation. This setting will make all ports operate same regardless of the output status of the input device.
Time Scheduling
You can specify a time range during which a specific operation is performed. You can specify a specific time range for a schedule code, which will be transferred to the applicable device. You can specify up to 5 different time intervals for a day, ranging from Monday to Sunday including holidays. Each time schedule code can produce a single different (or same) holiday code.
Door Open Alarm and Forced Door Open Alarm
The Door Open Alarm function notifies the administrator that the door is still open if a door stays open after the normal door open time and the standby time. (The output signal can be transferred via the output port, data on any abnormal state will be stored in memory, which will be transferred upon request from the PC software. The Forced Door Open Alarm function produces an alert when the door is forced to open and makes an alert again if the door is still open after the timeout.
I/O Settings
This product is equipped with 15 input ports, 12 relay output ports, and 3 TTL output ports. You can use the input ports to receive signals from the Exit button and the fire sensor, and utilize this product to meet various situations such as attaching the door lock to any of the 12 relays. You can also set the output time for these output ports.
Holiday Setup
You can specify a holiday (legal holiday or
ARM/DISARM
In the condition where the ARM/DISARM code is specified, if you enter the ARM/DISARM code and present the card of the administrator (with master permissions) to the reader, the device triggers the alarm mode where you can control the output signal in sync with the security system. In this mode, all connected readers will not take the card input any further.
Duress Mode
This is used in a situation where you should open the door inevitably by a robber insisting to do so. Open the door
by entering the
Two Men Operation Mode
This will allow access by visitors only under the control of the visitor guide.
Access will be permitted only if two cards are presented within a specified time (10 seconds).
Dual Door Time Control
This allows you to specify two different settings for the entrance door control time according to the
Data Maintenance
In the event of power failure, the controller retains all card information and the access/alert history (event data) until it is damaged on the memory.
J You can use the application program (SAMS Basic) to configure all theses settings to your preference.
6_ product introduction