Samsung SSA-P400/EXP, SSA-P400T/EXP manual Troubleshooting, Problem Action

Page 24

troubleshooting

TROUBLESHOOTING

If the product does not work properly, please check the followings before contacting us. If the trouble persists, please contact the SAMSUNG Customer Service near you.

PROBLEM

 

ACTION

 

 

 

Can I specify RF only or RF+P/W

1)

It is not available.

mode differently according to the

2)

The mode is defined for each reader device, not the card.

card?

 

Thus, you can not specify the mode for each card differently.

 

 

 

Ever since I mass-transferred data

1)

You might have not saved card information to the PC, but just to the device

using the PC application, some

 

when registering card using the PC application.

cards are not allowed for access.

2)

Check if there is a registered, but disallowed card in the PC.

 

3)

For an unregistered card, try to enter it again and save to the PC before

 

 

transferring to the device.

 

4)

The Mass Transfer/Group Transfer function of the PC application will delete

 

 

all card data in the device before transferring the PC data to the device. As

 

 

such, if you usually register one card on a daily basis, you may not save it

 

 

to the PC but transfer to the device, which causes unsaved card numbers

 

 

not to be registered with the device in the operation of a mass-transfer.

 

5)

If this is not the case, the problem may be caused by the defective of an

 

 

internal circuit.

 

 

Contact the nearest customer service for technical assistance.

 

 

The RF card works normally, but

Use the provided software program to check the use of the keypad while the

the key input (for the card number)

reader is operating in a certain mode.

using the keypad does not work

Enable the use of the keypad before downloading data to the device.

properly.

 

 

 

 

 

The reader reads a card normally

1)

Check the power source of the reader. (Check if the LED indicator of the

but no reaction is made by the

 

reader is blinking when it has read a card.)

device or an irrelevant card number

2)

Check if the reader works properly. (Disconnect the reader from the system

is displayed.

 

and use a measuring device such as an oscilloscope to measure the output

 

 

port of the reader.)

 

3)

Check if the reader is properly connected to the system (device).

 

 

- Check if the Wiegand communication lines between the reader and the

 

 

system are properly established. (D0, D1)

 

 

- The Wiegand communication line should be connected to GND. (A

 

 

different power source may be fine but the earth-grounding point should

 

 

be connected to GND of the device.)

 

4)

If you find the output signal from the device but with severe noise when

 

 

using a measuring device to measure the Wiegand communication line,

 

 

please check the followings:

 

 

- Connect the shield wire and the spare wire of the cable to GND.

 

 

- Use the repeater.

 

5)

If the problem persists after performing all the checkpoints above, contact the customer

 

 

service for technical help.

 

 

 

24_ troubleshooting

Image 24
Contents Access Control Panel Please visit our websiteSafety information Safety informationImportant Safety Instructions Contents Features Product introductionInput Port Format Setup Door Open Alarm and Forced Door Open AlarmSettings Holiday SetupWHAT’S Included Main UnitCD Manual Board ID Setup SwitchSwitch System after the initialization Output Relay #1 ~ Address Setup 5V for any output occurrence SwitchIndicatoradditionally Input LED IndicatorSignal occurs Buzzer control settingsConnector used to connect to the main board BoardInput port #8 Input port #9Input port #10 Input port #11Cable Selection Host P.CConnecting the Termination Resistor and Diode Termination ResistorBypass Diode Connection Termination Resistor in RS-485 CommunicationInstallation and external connection EARTH-GROUNDING the Communication CablesPOWER, READER, and I/O Connection Power ConnectionReader Connection Input Connection Exit Button Connection Input #1, Input #3Output Connection DC +12V GNDCommunication Line Connection RS-232 Communication Port ConnectionHost PC Check the location of the communication portRS-422 Communication Port Connection Standalone HostTX+ RX+RS-422 Communication Port Connection Multiple Units TX+ RX+TCP/IP Communication Port Connection HUB TCP / IPTCP/IP Communication Configuration TCP/IP ConnectionInitializing the system using the Initialize switch Switches simultaneouslyInitialization System InitializationBoard ID Setting You can specify between 0 and 255 for the board IDTroubleshooting TroubleshootingProblem Action Problem When the system is in sync withNo communication is available Product Specifications Product specificationsCorrect disposal of batteries in this product