Samsung AR36HPFUAWKNMG manual Smooth the cut edges, Cut off the remaining foam insulation

Page 30

CAUTION

Make a knockout hole by driving in a nail.

When installing the cables through the knockout hole, remove all burrs and protect them with the protection tape.

Apply rust resisting paint around the hole.

Installing and connecting the assembly pipe of the indoor unit

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

There are 2 refrigerant pipes of different diameters:

• The smaller one is for the liquid refrigerant

• The larger one is for the gas refrigerant

A short pipe is already fitted to the air conditioner. You may need to extend the pipe using the assembly pipe (optional).

The connection procedure for the refrigerant pipe varies

A

B

according to the exit position of the pipe when facing the wall:

 

 

• Right(A)

C

Left(B)

Underside(C)

Rear

1.Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2.Smooth the cut edges.

3.Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

• If you want to shorten or extend the pipes, refer to page 31~32.

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

4.Cut off the remaining foam insulation.

5.If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

6.Pass the pipe through the hole in the wall.

7.For further details on how to connect to the outdoor unit and purge the air, refer to page 34~35.

• The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test;

refer to page 36 for further details.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

DO NOT WALL UP THE PIPE CONNECTION !

All refrigerant pipe connection must be easy accessible and serviceable.

30

SSEC_UMG_IB&IM_DB68-04508A_EN.indd 30

2014-2-10 14:57:00

Image 30
Contents English Contents Follow directions SafetAA y precautionsImportant safety symbols and precautions Wall socketFor Using For Cleaning ChecAA king before use Operation rangesChecAA king the name of the parts Main partsDisplay ChecAA king the remote controller Remote controller buttonsStoring the remote controller Remote controller displayBattery changing time Inserting the batteriesBasicAA function Press the button to adjust the temperature Press the button to set the desired fan speedAdjusA ting the air flow direction Using the Turbo functionPress the Air swing button on the remote controller Vertical air flowPress the Time Up or Time Down button to set the time AA modePress the button on the remote controller Press the Set button to active it onAdditional options available in On timer mode SettinAA g the On/Off timerPress the On Timer/Off Timer button You can select from Auto/Cool/Dry/Fan/Heat ARHPmodelIf the air conditioner is on If the air conditioner is off Using the Smart Saver functionFrom the moment you have set the timer Turn off automaticallyUsingAA the Auto Clean function Using the Quiet functionWhen the air conditioner is turned on Opening the panel Cleaning the indoor unitCleaning the outdoor unit heat exchanger Heat exchangerRemoving the Air filter CleanAA ing the air conditionerCleaning the air filter Open the panel and put the Air filter outMaintAA aining the air conditioner Periodical checksTroubAA leshooting Flow movement changes. It is normal ConnectionSafety precautions General informationPower supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit  a place where the air filter can be replaced easilyChooAA sing the installation location Where sulfide gas existsOutdoor Unit  Figure Description When installing more than 1 outdoor unitWhen the air outlet is towards the wall Top view Side viewAccessories Accessories in the indoor unit caseAccessories in the outdoor unit case Tools required for installation General Tools Fixing the installation plate Optional accessories Tools for test operationsConnecting the assembly cable Cable specificationConnecting the cable Extend the assembly cable if necessary Each wire is labeled with the corresponding terminal numberInstallation Smooth the cut edges Cut off the remaining foam insulationUnscrew the caps at the end of each pipe AAPurging the indoor unitCutting or extending the pipe Put a flare nut slightly into the pipe and modify the flareCuttingAA or extending the pipe Outer DiameterHose tight Drain hose installationTwo hoses are firmly connected, there is no water leakage Check for leakage on both side of the drain outletPurging the connected pipes ARHPseries30g of refrigerant R-22 must be added for each extra meter Adding RefrigerantAdd refrigerant charge according to table below If you use a pipe shorter than 4 mPerfoAA rming the gas leak tests Fixing the indoor unit in placeOutdoor unit installed on the wall by rack Fixing the outdoor unit in placeAppropriate support wall or ground FinalAA Check and Trial Operation Press the Power button and check the followingPress the Power button to stop the operation Check the followingsApply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withInsulation tape to finish TechnAA ical Specifications AR30HCFUAWK/MG AR36HCFUAWK/MGEnglish Questions or COMMENTS? EgyptAir Conditioner
Related manuals
Manual 43 pages 5.33 Kb