Samsung AR36HCFUAWKNMG, AR30HPFUAWKNMG manual CuttingAA or extending the pipe, Outer Diameter

Page 32

CuttingAA or extending the pipe

5. Check if you flared the pipe correctly (see examples of incorrectly flared pipes below).

Correct

Inclined

Damaged

Cracked

Uneven

 

 

Surface

 

Thickness

6.Align the pipes to connect them easily. Tighten the flare nuts first with your hands, and then with a torque wrench, applying the following torque:

Flare nut

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor outlet

 

pipe

 

 

 

 

 

Connecting pipe

Outer Diameter

Torque (kgf•cm)

ø6.35 mm

140~170

ø9.52 mm

250~280

ø12.70 mm

380~420

ø15.88 mm

440~480

ø19.05 mm

990~1210

ø22.23 mm

990~1210

• Excessive torque can be cause of gas leakage. In case brazing the pipe, the nitrogen gas must be blown into the

pipe (50 Pa). The joint must be accessible and serviceable.

7. For further details on how to connect to the outdoor unit and purge the air, refer to page 34~35.

• Tighten the flare nut with torque wrench according to specified method.

If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Installing and connecting the drain hose of the indoor unit

When installing the drain hose for the indoor unit, check if condensation draining is adequate. When passing the drain hose through the 65-mm hole drilled in the wall, check the followings:

Wall

Indoor unit

Drain hose

The drain hose must not be bent.

The drain hose must NOT slant upwards.

5cm

less

Keep a clearance of at least 5cm between the end of the drain hose and the ground.

The end of the drain hose must NOT be placed under water.

Ditch

Do not place the end of the drain hose in a hollow.

32

SSEC_UMG_IB&IM_DB68-04508A_EN.indd 32

2014-2-10 14:57:01

Image 32
Contents English Contents SafetAA y precautions Important safety symbols and precautionsFollow directions Wall socketFor Using For Cleaning ChecAA king before use Operation rangesDisplay ChecAA king the name of the partsMain parts ChecAA king the remote controller Remote controller buttonsRemote controller display Battery changing timeStoring the remote controller Inserting the batteriesBasicAA function Press the button to adjust the temperature Press the button to set the desired fan speedUsing the Turbo function Press the Air swing button on the remote controllerAdjusA ting the air flow direction Vertical air flowAA mode Press the button on the remote controllerPress the Time Up or Time Down button to set the time Press the Set button to active it onSettinAA g the On/Off timer Press the On Timer/Off Timer buttonAdditional options available in On timer mode You can select from Auto/Cool/Dry/Fan/Heat ARHPmodelUsing the Smart Saver function From the moment you have set the timerIf the air conditioner is on If the air conditioner is off Turn off automaticallyWhen the air conditioner is turned on UsingAA the Auto Clean functionUsing the Quiet function Cleaning the indoor unit Cleaning the outdoor unit heat exchangerOpening the panel Heat exchangerCleanAA ing the air conditioner Cleaning the air filterRemoving the Air filter Open the panel and put the Air filter outMaintAA aining the air conditioner Periodical checksTroubAA leshooting Flow movement changes. It is normal ConnectionSafety precautions General informationChoosing the installation location Installing the unitPower supply line, fuse or circuit breaker  a place where the air filter can be replaced easilyOutdoor Unit ChooAA sing the installation locationWhere sulfide gas exists When installing more than 1 outdoor unit When the air outlet is towards the wall Figure Description Top view Side viewAccessories in the outdoor unit case AccessoriesAccessories in the indoor unit case Fixing the installation plate Optional accessoriesTools required for installation General Tools Tools for test operationsConnecting the cable Connecting the assembly cableCable specification Installation Extend the assembly cable if necessaryEach wire is labeled with the corresponding terminal number Smooth the cut edges Cut off the remaining foam insulationAAPurging the indoor unit Cutting or extending the pipeUnscrew the caps at the end of each pipe Put a flare nut slightly into the pipe and modify the flareCuttingAA or extending the pipe Outer DiameterDrain hose installation Two hoses are firmly connected, there is no water leakageHose tight Check for leakage on both side of the drain outletPurging the connected pipes ARHPseriesAdding Refrigerant Add refrigerant charge according to table below30g of refrigerant R-22 must be added for each extra meter If you use a pipe shorter than 4 mPerfoAA rming the gas leak tests Fixing the indoor unit in placeAppropriate support wall or ground Outdoor unit installed on the wall by rackFixing the outdoor unit in place Press the Power button and check the following Press the Power button to stop the operationFinalAA Check and Trial Operation Check the followingsInsulation tape to finish Apply heat to the contraction tube to contract itAfter tube contraction work is completed, wrap it with TechnAA ical Specifications AR30HCFUAWK/MG AR36HCFUAWK/MGEnglish Questions or COMMENTS? EgyptAir Conditioner