InstallAA ing and connecting the drain hose of the outdoor unit

(ARHPseries)

While heating, ice may accumulate. During the process of defrosting, check if condensation draining is adequate. For adequate draining, do the following:

1. Insert the drain plug into the drain hole on the underside of the outdoor unit.

• To avoid drain plug from contacting the ground, secure gap between the ground and the bottom surface of the outdoor unit.

 

Drain hole

Drain plug

 

 

2. Connect a drain hose to the drain plug.

Bottom surface of outdoor unit

 

Drain hole

 

 

Drain plug

Drain hose

3. Ensure that condensation draining is adequate.

 

Snow-proof hood

 

 

• In areas with heavy snow fall, piled snow could block the air intake.

 

 

To avoid this incident, install a frame that is higher than estimated snow

 

 

fall. In addition, install a snow-proof hood to avoid snow from piling on the

 

outdoor unit.

Estimated

 

snow fall Frame

 

 

Ground

Purging the connected pipes

The outdoor unit is loaded with sufficient R-22 refrigerant .You should purge the air in the indoor unit and in the pipe.If air remains in the refrigerant pipes, it affects the compressor. It may cause reduction of cooling capacity and malfunction.

• When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the service valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high. It may cause explosion and injury.

1.

Connect each assembly pipe to the appropriate valve on the outdoor unit and Outdoor unit

Indoor unit

 

tighten the flare nut.

 

 

 

 

 

 

Gas pipe side

 

 

2.

Tighten the flare nut first with your hands, and then with a torque wrench,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid pipe side

 

 

 

applying the following torque:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

34

SSEC_UMG_IB&IM_DB68-04508A_EN.indd 34

2014-2-10 14:57:03

Image 34
Contents English Contents Follow directions SafetAA y precautionsImportant safety symbols and precautions Wall socketFor Using For Cleaning ChecAA king before use Operation rangesMain parts ChecAA king the name of the partsDisplay ChecAA king the remote controller Remote controller buttonsStoring the remote controller Remote controller displayBattery changing time Inserting the batteriesBasicAA function Press the button to adjust the temperature Press the button to set the desired fan speedAdjusA ting the air flow direction Using the Turbo functionPress the Air swing button on the remote controller Vertical air flowPress the Time Up or Time Down button to set the time AA modePress the button on the remote controller Press the Set button to active it onAdditional options available in On timer mode SettinAA g the On/Off timerPress the On Timer/Off Timer button You can select from Auto/Cool/Dry/Fan/Heat ARHPmodelIf the air conditioner is on If the air conditioner is off Using the Smart Saver functionFrom the moment you have set the timer Turn off automaticallyUsing the Quiet function UsingAA the Auto Clean functionWhen the air conditioner is turned on Opening the panel Cleaning the indoor unitCleaning the outdoor unit heat exchanger Heat exchangerRemoving the Air filter CleanAA ing the air conditionerCleaning the air filter Open the panel and put the Air filter outMaintAA aining the air conditioner Periodical checksTroubAA leshooting Flow movement changes. It is normal ConnectionSafety precautions General informationPower supply line, fuse or circuit breaker Choosing the installation locationInstalling the unit  a place where the air filter can be replaced easilyWhere sulfide gas exists ChooAA sing the installation locationOutdoor Unit  Figure Description When installing more than 1 outdoor unitWhen the air outlet is towards the wall Top view Side viewAccessories in the indoor unit case AccessoriesAccessories in the outdoor unit case Tools required for installation General Tools Fixing the installation plateOptional accessories Tools for test operationsCable specification Connecting the assembly cableConnecting the cable Each wire is labeled with the corresponding terminal number Extend the assembly cable if necessaryInstallation Smooth the cut edges Cut off the remaining foam insulation Unscrew the caps at the end of each pipe AAPurging the indoor unit Cutting or extending the pipe Put a flare nut slightly into the pipe and modify the flareCuttingAA or extending the pipe Outer DiameterHose tight Drain hose installationTwo hoses are firmly connected, there is no water leakage Check for leakage on both side of the drain outletPurging the connected pipes ARHPseries30g of refrigerant R-22 must be added for each extra meter Adding RefrigerantAdd refrigerant charge according to table below If you use a pipe shorter than 4 mPerfoAA rming the gas leak tests Fixing the indoor unit in placeFixing the outdoor unit in place Outdoor unit installed on the wall by rackAppropriate support wall or ground FinalAA Check and Trial Operation Press the Power button and check the followingPress the Power button to stop the operation Check the followingsAfter tube contraction work is completed, wrap it with Apply heat to the contraction tube to contract itInsulation tape to finish TechnAA ical Specifications AR30HCFUAWK/MG AR36HCFUAWK/MGEnglish Questions or COMMENTS? EgyptAir Conditioner