Samsung AR18MRFNEWKXMG Error indicator, Outdoor units, Not, Blocking error Open, Models only

Page 51

When error occurs, take necessary measures by referring to the following table. For more information on necessary measures for errors, refer to the service manual.

 

 

 

Error indicator

 

 

 

 

 

 

 

 

 

LED Display

 

Error

Measures for the installer to take

 

Display

LED 1

LED 2

LED 3

 

 

 

 

 

 

 

 

 

/

/

 

 

 

 

 

 

 

 

 

 

Communication

• Check the connection wire

 

 

 

 

 

 

 

 

error between

between the indoor and outdoor

 

 

 

 

 

 

 

 

indoor and

units (whether the power cable or

 

 

 

 

 

 

 

 

outdoor units

communication cable is crossed or

 

 

 

 

 

 

 

 

 

not).

 

 

 

 

 

 

 

 

Error on indoor

• Check the connection of the

 

 

 

 

 

 

 

 

temperature

connector.

 

 

 

 

 

 

 

 

sensor

 

 

,

 

 

 

 

 

 

Error on indoor

• Check the connection of the

 

 

 

 

 

 

 

 

heat exchanger

connector.

 

 

 

 

 

 

 

 

Error on indoor fan

• Check the connection of the

 

 

 

 

 

 

 

 

motor

connector.

 

 

 

 

 

 

 

 

 

• Remove foreign substance. (Check

 

 

 

 

 

 

 

 

 

for the cause that restrains motor.)

 

display

 

 

 

 

 

 

EEPROM/Option

Re-set options.

 

and all LEDs

 

 

 

 

error

 

 

blink.

 

 

 

 

 

 

 

 

 

,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant flow

• Check if the stop valve is completely

 

 

 

 

 

 

 

 

blocking error

open.

 

 

 

 

 

 

 

 

 

• Check if there is any blockage in the

 

 

 

 

 

 

 

 

 

refrigerant pipe which connects the

 

 

 

 

 

 

 

 

 

indoor and outdoor units.

Installation

 

 

 

 

 

 

 

 

• Check for refrigerant leak.

 

 

 

 

 

 

 

Lack of refrigerant

• Check if a sufficient amount of

 

 

 

 

 

 

 

 

(for inverter

refrigerant is additionally charged

 

 

 

This LED pattern

 

models only)

for the pipe longer than specified in

 

 

 

 

 

piping codes and standards.

 

 

 

 

appears when an

 

 

 

 

 

 

• Check for refrigerant leak between

 

 

 

 

error occurs on the

 

 

 

 

 

outdoor unit.

 

 

valve and pipe connection.

: Off,

: Blinking,

: On

 

 

 

 

50English

Image 51
Contents Samsung DB68-06042A-02 AirconditionerContents Correct Disposal of This Product Safety Information Failing to do so may result in electric shock or fireThis may result in electric shock or fire For Power Supply This may result in children seriously injuring themselves Do not touch the circuit breakerwith wet handsThis may result in electric shock This may result in electric shock or burnsDo not touch the pipes connected with the product Do not place objects or devices under the indoor unitDo not operate the appliance with wet hands Do not drink the water from the air conditionerDo not clean the inside of the air conditioner by yourself For CleaningDisplay Operation indicatorSingle user indicator Indoor Unit OverviewInserting batteries Remote Control OverviewRemote Control Operation Controlling temperatureOperation modes Controlling air flow direction Vertical air flowHorizontal air flow manual Cool mode Cooling OperationStep cooling function Dehumidifying Operation Dry modeIs running The blade looks almost closed Heat modeMode is running Heating OperationQuick Smart Features Auto modeFan mode Fast function Select Beep Comfort functionCool mode When the Single user function starts, Energy-Saving OperationSingle user function Timed on/Timed off function Good’sleep function Default operation time for the good’sleep functionCleaning at a Glance Running Auto cleanDo not clean the display by using alkaline detergent Cleaning the filter Troubleshooting Electric waves Check whether the drains are clean. Clean them regularlyTo pass the error code to the service centre Does not workTechnical Specifications 27˚C 20000 Btu/h AR18MQFNEWK/MG AR24MRFNEWK/MG AR24MQFNRWK/MG Safety Information on Installation Installation of the unitGeneral information Install the unit in a place where water can drain smoothly Power supply line, fuse, or circuit breakerChoosing the installation location PreparationMinimum clearances for the outdoor unit Indoor unit Packing and Unpacking5cases Unit mmChecking and preparing accessories and tools Accessories Accessories in the indoor unit packageOptional accessories Tools Drilling a hole through the wallTaping the pipes, cables, and drain hose Plate Indoor Unit InstallationDisassembling the installation Disassembling the cover panelCircular terminal Connecting the cables assembly cableApply heat to the contraction tube to contract it Optional Extending the power cableCompression dimension should be Prepare the following toolsOptional Extending the drain hose Installing and connecting the drain hosePressing socket Incomplete wire Install the drain hoseOptional Changing the direction of the drain hose Depth a Shortening or extending the refrigerant pipes assembly pipe10 Fixing the installation plate When fixing the indoor unit on a wallWhen fixing the indoor unit on a window frame 12 Assembling the cover panel 11 Fixing the indoor unit to the installation plateWhen fixing the indoor unit on a gypsum board Fix the installation plate without inclining to one sideOptional Fixing the outdoor unit to a wall with a rack Outdoor Unit InstallationConnecting the cables and the refrigerant pipes Fixing the outdoor unit in placeLeave the system in the standby mode Evacuating the airCooling capacity and malfunction. Use a vacuum pump Siphon Adding refrigerantPerforming the gas leak tests Running the Smart Install modeAppears when an Error indicatorError Blocking error OpenPumping down refrigerant Check the following Strength of the installation siteTurn on th air conditioner and select Fast Cool mode Performing final check and trial operationEnglish English English