1Cut out the appropriate knock-out piece (A, B, C) on the rear of the indoor unit unless you connect the pipe directly from the rear.

2Smooth the cut edges.

3Remove the protection caps of the pipes and connect the assembly pipe to each pipe. Tighten the nuts first with your hands, and then with a torque wrench, applying the following torque:

Outer diameter (mm)

Torque (N•m)

Torque (kgf•cm)

 

 

 

ø 6.35

14 to 18

140 to 180

 

 

 

ø 9.52

34 to 42

350 to 430

 

 

 

ø 12.70

49 to 61

500 to 620

 

 

 

ø 15.88

68 to 82

690 to 830

 

 

 

Step 2.9 Shortening or extending the refrigerant pipes (assembly pipe)

 

 

Pipe cutter

 

 

 

Pipe

 

90°

Oblique

Rough

Burr

NOTE

If you want to shorten or extend the pipes, see Step 2.9 Shortening or extending the refrigerant pipes (assembly pipe) on page 43.

4Cut off the remaining foam insulation.

5If necessary, bend the pipe to fit along the bottom of the indoor unit. Then pull it out through the appropriate hole.

The pipe should not project from the rear of the indoor unit.

The bending radius should be 100 mm or more.

6Pass the pipe through the hole in the wall.

NOTE

The pipe will be insulated and fixed permanently into position after finishing the installation and the gas leak test. For further details. see Step 4.1 Performing the gas leak tests on page 49.

CAUTION

Tighten the flare nut with a torque wrench according to specified method. If the flare nut is over-tightened, the flare may break and cause refrigerant gas leakage.

Do not box in or cover the pipe connection. All refrigerant pipe connection must be easily accessible and serviceable.

D

 

 

90°±2°

 

 

 

 

 

A

45°±2°

 

 

 

 

 

 

L

 

 

 

R 0.4 to 0.8

Pipe

Flare

D

 

 

 

 

 

 

(Unit: mm)

Outer diameter (D)

 

Depth (A)

Flare dimension (L)

ø 6.35

 

1.3

8.7 to 9.1

ø 9.52

 

1.8

12.8 to 13.2

ø 12.70

 

2.0

16.2 to 16.6

ø 15.88

 

2.2

19.3 to 19.7

 

 

 

Flare nut

Indoor outlet pipe

 

 

Connecting pipe

Outer diameter (mm)

Torque (N•m)

Torque (kgf•cm)

ø 6.35

 

14 to 18

140 to 180

ø 9.52

 

34 to 42

350 to 430

ø 12.70

 

49 to 61

500 to 620

ø 15.88

 

68 to 82

690 to 830

Installation

English 43

Image 44
Contents Samsung Airconditioner DB68-06042A-02Contents Correct Disposal of This Product This may result in electric shock or fire Safety InformationFailing to do so may result in electric shock or fire For Power Supply Do not touch the circuit breakerwith wet hands This may result in electric shockThis may result in electric shock or burns This may result in children seriously injuring themselvesDo not place objects or devices under the indoor unit Do not operate the appliance with wet handsDo not drink the water from the air conditioner Do not touch the pipes connected with the productFor Cleaning Do not clean the inside of the air conditioner by yourselfOperation indicator Single user indicatorIndoor Unit Overview DisplayRemote Control Overview Inserting batteriesOperation modes Remote Control OperationControlling temperature Horizontal air flow manual Controlling air flow directionVertical air flow Step cooling function Cool modeCooling Operation Dry mode Dehumidifying OperationHeat mode Mode is runningHeating Operation Is running The blade looks almost closedFan mode Quick Smart FeaturesAuto mode Fast function Comfort function Select BeepSingle user function Cool mode When the Single user function starts,Energy-Saving Operation Timed on/Timed off function Default operation time for the good’sleep function Good’sleep functionDo not clean the display by using alkaline detergent Cleaning at a GlanceRunning Auto clean Cleaning the filter Troubleshooting Check whether the drains are clean. Clean them regularly To pass the error code to the service centreDoes not work Electric wavesTechnical Specifications 27˚C 20000 Btu/h AR18MQFNEWK/MG AR24MRFNEWK/MG AR24MQFNRWK/MG General information Safety Information on InstallationInstallation of the unit Power supply line, fuse, or circuit breaker Install the unit in a place where water can drain smoothlyMinimum clearances for the outdoor unit Choosing the installation locationPreparation Packing and Unpacking 5casesUnit mm Indoor unitOptional accessories Checking and preparing accessories and tools AccessoriesAccessories in the indoor unit package Drilling a hole through the wall ToolsTaping the pipes, cables, and drain hose Indoor Unit Installation Disassembling the installationDisassembling the cover panel PlateConnecting the cables assembly cable Circular terminalOptional Extending the power cable Compression dimension should bePrepare the following tools Apply heat to the contraction tube to contract itInstalling and connecting the drain hose Pressing socket Incomplete wireInstall the drain hose Optional Extending the drain hoseOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe Depth aWhen fixing the indoor unit on a window frame 10 Fixing the installation plateWhen fixing the indoor unit on a wall 11 Fixing the indoor unit to the installation plate When fixing the indoor unit on a gypsum boardFix the installation plate without inclining to one side 12 Assembling the cover panelOutdoor Unit Installation Connecting the cables and the refrigerant pipesFixing the outdoor unit in place Optional Fixing the outdoor unit to a wall with a rackCooling capacity and malfunction. Use a vacuum pump Leave the system in the standby modeEvacuating the air Adding refrigerant SiphonRunning the Smart Install mode Performing the gas leak testsError indicator ErrorBlocking error Open Appears when anCheck the following Strength of the installation site Turn on th air conditioner and select Fast Cool modePerforming final check and trial operation Pumping down refrigerantEnglish English English