Samsung AR18MQFNEWKNMG, AR24KQFNRWKNMG Evacuating the air, Leave the system in the standby mode

Page 48

Control box

Remove the screw for the control box cover

Remove the gas and liquid

For connecting the

service port caps

refrigerant pipes

Gas service port <Low pressure>

CAUTION

When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the stop valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high. It may cause explosion and injury.

1Leave the system in the standby mode.

WARNING

Do not turn on the system! This is necessary for better vacuum operation (full OPEN position of Electronic Expansion Valve).

2Connect the charging hose of the low pressure side of manifold gauge to a gas service port as seen in the picture.

Liquid service port

Connect the gas and liquid

<High pressure>

refrigerant pipes

Step 3.3 Evacuating the air

The outdoor unit is loaded with sufficient R-410A refrigerant. Do not vent R-410A into atmosphere: it is a fluorinated greenhouse gas, covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 2088. You should evacuate the air in the indoor unit and in the pipe. If air remains in the refrigerant pipes, it affects the compressor. It may cause reduction

of cooling capacity and malfunction. Use a vacuum pump.

3

Valve

15 minutes

4

Vacuum

Pump (Backward ￿owing prevention)

Liquid service port <Low pressure>

5

Liquid service port <High pressure>

Installation

English 47

Image 48
Contents Samsung Airconditioner DB68-06042A-02Contents Correct Disposal of This Product Safety Information Failing to do so may result in electric shock or fireThis may result in electric shock or fire For Power Supply Do not touch the circuit breakerwith wet hands This may result in electric shockThis may result in electric shock or burns This may result in children seriously injuring themselvesDo not place objects or devices under the indoor unit Do not operate the appliance with wet handsDo not drink the water from the air conditioner Do not touch the pipes connected with the productFor Cleaning Do not clean the inside of the air conditioner by yourselfOperation indicator Single user indicatorIndoor Unit Overview DisplayRemote Control Overview Inserting batteriesRemote Control Operation Controlling temperatureOperation modes Controlling air flow direction Vertical air flowHorizontal air flow manual Cool mode Cooling OperationStep cooling function Dry mode Dehumidifying OperationHeat mode Mode is runningHeating Operation Is running The blade looks almost closedQuick Smart Features Auto modeFan mode Fast function Comfort function Select BeepCool mode When the Single user function starts, Energy-Saving OperationSingle user function Timed on/Timed off function Default operation time for the good’sleep function Good’sleep functionCleaning at a Glance Running Auto cleanDo not clean the display by using alkaline detergent Cleaning the filter Troubleshooting Check whether the drains are clean. Clean them regularly To pass the error code to the service centreDoes not work Electric wavesTechnical Specifications 27˚C 20000 Btu/h AR18MQFNEWK/MG AR24MRFNEWK/MG AR24MQFNRWK/MG Safety Information on Installation Installation of the unitGeneral information Power supply line, fuse, or circuit breaker Install the unit in a place where water can drain smoothlyChoosing the installation location PreparationMinimum clearances for the outdoor unit Packing and Unpacking 5casesUnit mm Indoor unitChecking and preparing accessories and tools Accessories Accessories in the indoor unit packageOptional accessories Drilling a hole through the wall ToolsTaping the pipes, cables, and drain hose Indoor Unit Installation Disassembling the installationDisassembling the cover panel PlateConnecting the cables assembly cable Circular terminalOptional Extending the power cable Compression dimension should bePrepare the following tools Apply heat to the contraction tube to contract itInstalling and connecting the drain hose Pressing socket Incomplete wireInstall the drain hose Optional Extending the drain hoseOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe Depth a10 Fixing the installation plate When fixing the indoor unit on a wallWhen fixing the indoor unit on a window frame 11 Fixing the indoor unit to the installation plate When fixing the indoor unit on a gypsum boardFix the installation plate without inclining to one side 12 Assembling the cover panelOutdoor Unit Installation Connecting the cables and the refrigerant pipesFixing the outdoor unit in place Optional Fixing the outdoor unit to a wall with a rackLeave the system in the standby mode Evacuating the airCooling capacity and malfunction. Use a vacuum pump Adding refrigerant SiphonRunning the Smart Install mode Performing the gas leak testsError indicator ErrorBlocking error Open Appears when anCheck the following Strength of the installation site Turn on th air conditioner and select Fast Cool modePerforming final check and trial operation Pumping down refrigerantEnglish English English