Installation

3Open the valve of the low pressure side of manifold gauge anticlockwise.

4Evacuate the air in the connected pipes using the vacuum pump for about 15 minutes.

Make sure that pressure gauge shows -0.1 MPa (-76 cmHg, 5 torr) after about 10 minutes. This procedure is very important to avoid a gas leak.

Close the valve of the low pressure side of manifold gauge clockwise.

Turn off the vacuum pump.

Check for 2 minutes if there is any pressure change.

Remove the hose of the low pressure side of manifold gauge.

5Set a valve cork of liquid and gas service port to the open position.

Step 3.4 Adding refrigerant

If you use a pipe longer than the length specified in the piping codes and standards, you must add

10 g (for ✴✴12✴✴) and 20 g (for ✴✴18/24✴✴) of refrigerant R-410A for each extra metre. If you use a pipe shorter than the length specified in the piping codes and standards, the evacuating time is normal. Refer to the Service Manual for further details.

CAUTION

The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction of the compressor.

Always contact the service centre or a professional installation agency for product installation.

R-410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment, take the following instructions:

Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the refrigerant:

 

 

Siphon

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charge the refrigerant

Charge the refrigerant turning

standing the cylinder upright.

the cylinder upside down.

<Cylinder with siphon>

<Cylinder without siphon>

NOTE

If R-410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment vary.

During the measuring operation of refrigerant quantity added, use electronic scales. If cylinder doesn't have siphon, upset it.

48English

Image 49
Contents Samsung DB68-06042A-02 AirconditionerContents Correct Disposal of This Product Failing to do so may result in electric shock or fire Safety InformationThis may result in electric shock or fire For Power Supply This may result in electric shock Do not touch the circuit breakerwith wet handsThis may result in electric shock or burns This may result in children seriously injuring themselvesDo not operate the appliance with wet hands Do not place objects or devices under the indoor unitDo not drink the water from the air conditioner Do not touch the pipes connected with the productDo not clean the inside of the air conditioner by yourself For CleaningSingle user indicator Operation indicatorIndoor Unit Overview DisplayInserting batteries Remote Control OverviewControlling temperature Remote Control OperationOperation modes Vertical air flow Controlling air flow directionHorizontal air flow manual Cooling Operation Cool modeStep cooling function Dehumidifying Operation Dry modeMode is running Heat modeHeating Operation Is running The blade looks almost closedAuto mode Quick Smart FeaturesFan mode Fast function Select Beep Comfort functionEnergy-Saving Operation Cool mode When the Single user function starts,Single user function Timed on/Timed off function Good’sleep function Default operation time for the good’sleep functionRunning Auto clean Cleaning at a GlanceDo not clean the display by using alkaline detergent Cleaning the filter Troubleshooting To pass the error code to the service centre Check whether the drains are clean. Clean them regularlyDoes not work Electric wavesTechnical Specifications 27˚C 20000 Btu/h AR18MQFNEWK/MG AR24MRFNEWK/MG AR24MQFNRWK/MG Installation of the unit Safety Information on InstallationGeneral information Install the unit in a place where water can drain smoothly Power supply line, fuse, or circuit breakerPreparation Choosing the installation locationMinimum clearances for the outdoor unit 5cases Packing and UnpackingUnit mm Indoor unitAccessories in the indoor unit package Checking and preparing accessories and tools AccessoriesOptional accessories Tools Drilling a hole through the wallTaping the pipes, cables, and drain hose Disassembling the installation Indoor Unit InstallationDisassembling the cover panel PlateCircular terminal Connecting the cables assembly cableCompression dimension should be Optional Extending the power cablePrepare the following tools Apply heat to the contraction tube to contract itPressing socket Incomplete wire Installing and connecting the drain hoseInstall the drain hose Optional Extending the drain hoseOptional Changing the direction of the drain hose Depth a Shortening or extending the refrigerant pipes assembly pipeWhen fixing the indoor unit on a wall 10 Fixing the installation plateWhen fixing the indoor unit on a window frame When fixing the indoor unit on a gypsum board 11 Fixing the indoor unit to the installation plateFix the installation plate without inclining to one side 12 Assembling the cover panelConnecting the cables and the refrigerant pipes Outdoor Unit InstallationFixing the outdoor unit in place Optional Fixing the outdoor unit to a wall with a rackEvacuating the air Leave the system in the standby modeCooling capacity and malfunction. Use a vacuum pump Siphon Adding refrigerantPerforming the gas leak tests Running the Smart Install modeError Error indicatorBlocking error Open Appears when anTurn on th air conditioner and select Fast Cool mode Check the following Strength of the installation sitePerforming final check and trial operation Pumping down refrigerantEnglish English English