Samsung AR18HPFSBWK/MG, AR18HCFNBWK/MG manual Fixing the outdoor unit in place, English-48, 660

Page 48

Fixing the indoor unit in place

Perform the following work on the area where gas leak test was done priory.

After checking for gas leaks in the system, insulate the pipe, hose and cables. Then place the indoor unit on the installation plate.

1.To minimise condensation problems, wrap foam insulation (as shown in the figure) on a part without insulation on the end of the pipes.

2.Wind the pipe, assembly cable and drain hose with vinyl tape.

3.Place the bundle (the pipe, assembly cable and drain hose) in the lower part of the indoor unit carefully so it does not project from the rear of the indoor unit.

4.Hook the indoor unit to the installation plate and move the unit to the right and left until it is securely in place.

• Make sure pipe does not move when you install the indoor unit on an installation plate.

5.Wrap the rest of the pipe with vinyl tape.

6.Attach the pipe to the wall using clamps (optional).

Insulation

Pipes

 

Installation

 

plate

Connecting

Vinyl tape

pipes

Connecting wires

 

Drain hose

 

Fixing the outdoor unit in place

Install the outdoor unit in level on a stable base to help avoid the generation of noise and vibration, especially when installing the unit close to a neighbor.

If you install the outdoor unit in a place exposed to strong winds or at a height, fix it to an appropriate support (wall or ground).

1.Place the outdoor unit as indicated on the top of the unit to let the discharged air out properly.

2.Fix the outdoor unit in level to an appropriate support using anchor bolts.

3.If the outdoor unit is exposed to strong winds, install shield plates around the outdoor unit so that the fan can operate correctly.

• Secure the rubber leg to help prevent the generation of noise and vibration.

'X' mm

'Y' mm

Rubber leg

Model

X

Y

12HC 507 292

12HP 543 319

18HC 602 310

18HP

660 340

24

 

Outdoor unit installed on the wall by rack

Ensure the wall will be able to suspend the weight of rack and outdoor unit;

Install the rack close to the column as much as possible;

Install proper grommet in order to help reduce noise and residual vibration transferred by outdoor unit towards wall.

Designed to cut off residual vibration from outdoor unit to rack.

(not supplied with product)

Soft rubber designed to cut off vibration from rack to wall. (not supplied with product)

English-48

MG_GOOD_A3050_IB&IM_EN_DB68-04069A-00.indd 48

11/09/2013 21:11:21

Image 48
Contents Air Conditioner Features of your new air conditioner Contents Safety precautions English-4English-5 01epaPr n atioFor Using English-6English-7 Do not place objects or devices under the indoor unit English-8For Cleaning English-9Checking before use Operation rangesEnglish-10 Technical Specifications English-11T05s In llan atio Checking the name of the parts Main partsDisplay English-12Checking the remote controller Remote controller buttonsEnglish-13 Remote controller display Battery changing timeStoring the remote controller Inserting the batteriesBasic function Press the button to adjust the temperature Press the button to set the desired fan speedEnglish-16 Adjusting the air flow direction Vertical air flowHorizontal air flow English-17Using the Fast function Using the Comfort functionEnglish-18 When the air conditioner is on and in cool/heat mode ModeEnglish-19 Setting the On/Off timer Press the On Timer/Off Timer buttonEnglish-20 From the moment you have set the timer If the air conditioner is on If the air conditioner is offTurn off automatically Using the Auto Clean function When the air conditioner is turned onEnglish-22 Cleaning the air conditioner Cleaning the outdoor unit heat exchangerEnglish-23 Sre04 OthCleaning the air filter Removing the Air filterEnglish-24 Remove the air filter from the main bodyReassembling the Air filter English-25Top of the Air filter into the main body.. ➀ Maintaining the air conditioner English-26Troubleshooting Air conditionerEnglish-27 Button or disconnect the power plug/switch Check the Drains have been cleared Regular MaintenanceError is indicated Heard when refrigerant flow movement changes. It is normalGeneral information English-29Choosing the installation location Installing the unitPower supply line, fuse or circuit breaker Indoor unitWhere sulfide gas exists Outdoor UnitEnglish-31 When installing more than 1 outdoor unit When the air outlet is towards the wallEnglish-32  Figure DescriptionAccessories Accessories in the indoor unit caseEnglish-33 LlanAccessories in the outdoor unit case Optional accessoriesTools required for installation General Tools Tools for test operationsFixing the installation plate Assembling the hanger screwEnglish-35 This QR code for detail video of indoor unit installation Removing the screwsRemoving the Cover panel Before mounting the indoor unit English-36Assembling the Cover panel After mounting the indoor unit English-37Connecting the assembly cable Cable specificationConnecting the cable English-38Extend the assembly cable if necessary Each wire is labeled with the corresponding terminal numberEnglish-39 English-40 Smooth the cut edgesCut off the remaining foam insulation TorqueEvacuating the indoor unit Cutting or extending the pipeEnglish-41 Unscrew the caps at the end of each pipeEnglish-42 Put a flare nut slightly into the pipe and modify the flareDepth a Drain hose installation English-43Change the direction only when it is necessary English-44Shield Downwards as seen in the pictureEvacuating the connected pipes English-45Connect a drain hose to the drain plug Drain hole Drain plugAdding Refrigerant English-46Outer Torque If you use a pipe longer than 5 mPerforming the gas leak tests English-47Outdoor unit installed on the wall by rack Fixing the outdoor unit in placeEnglish-48 12HC 507 12HP 543 18HC 602Smart Install mode English-49English-50 Off BlinkingFinal check and trial operation English-51How to connect your extended power cables English-52Apply heat to the contraction tube to contract it After tube contraction work is completed, wrap it withMGGOODA3050IB&IMENDB68-04069A-00.indd 11/09/2013 Questions or COMMENTS? 0211