Samsung AR24KQJSBWKNMG manual Optional Changing the direction of the drain hose

Page 43

Step 2.7 Optional: Changing the direction of the drain hose

Drain pan outlet

Rubber cap

Step 2.8 Installing and connecting the assembly pipes to the refrigerant pipes (assembly pipe)

Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa. Under no circumstances must sanitary type copper pipe be used.

Pour water in the direction of arrow.

<Front view>

Direction of the drained water

<Side view>

There are 2 refrigerant pipes of different diameters:

The smaller one is for the liquid refrigerant

The larger one is for the gas refrigerant

A short liquid refrigerant pipe and a short gas refrigerant pipe are already fitted to the air conditioner. The connection procedure for the refrigerant pipes varies according to the exit position of each pipe when facing the wall:

Left

Right

Underside

<Front view>

Installation

CAUTION

Make sure that the indoor unit is in upright position when you pour water to check for leakage. Make sure that the water does not overflow onto the electrical part.

42English

Rear right or left

<Side view>

MG_GOOD_R-410A_A3050_IB&IM_EN_ DB68-06070A-00.indd 42

12-May-16 11:29:54 AM

Image 43
Contents Samsung Air conditionergioner Contents Safety Information on Installation Preparation InstallationFor Installation Safety InformationSafety Information For Power Supply For Using Safety Information Safety Information For Cleaning MGGOODR-410AA3050IB&IMEN DB68-06070A-00.indd Display Indoor Unit OverviewInserting batteries Remote Control OverviewControlling temperature Remote Control OperationOperation modes Controlling air flow direction Controlling fan speedCooling Operation Cool modeStep cooling function Dehumidifying Operation Dry modeHeating Operation Heat modeAuto mode Quick Smart FeaturesFan mode Fast function Beep sound function Comfort functionSingle user function Energy-Saving OperationTimed on/Timed off function Good’sleep function Running Auto clean Cleaning at a GlanceCleaning the filter Troubleshooting Cleaning and Maintenance Thailand Technical SpecificationsModel AR24KRJSRWK/MG AR24KQJSBWK/MG General information Safety Information on InstallationPower supply line, fuse, or circuit breaker Minimum clearances for the outdoor unit Choosing the installation locationOverview of installation location requirements PreparationIndoor unit Packing and UnpackingOutdoor unit Accessories Checking and preparing accessories and toolsTools Drilling a hole through the wallTaping the pipes, cables, and drain hose Disassembling the installation plate Indoor Unit InstallationDisassembling the cover panel Assembly cable Connecting the cablesPrepare a compressor and the following tools Optional Extending the power cableOptional Extending the drain hose Installing and connecting the drain hoseOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe When fixing the indoor unit on a wall 10 Fixing the installation plateWhen fixing the indoor unit on a window frame When fixing the indoor unit on a gypsum board 11 Fixing the indoor unit to the installation plate12 Assembling the cover panel Optional Fixing the outdoor unit to a wall with a rack Outdoor Unit InstallationConnecting the cables and the refrigerant pipes Fixing the outdoor unit in placeEvacuating the air Adding refrigerant Running the Smart Install mode Installation InspectionPerforming the gas leak tests LED Pumping down refrigerant Performing final check and trial operationPumping down for removing the product