Samsung AR24KQJSBWKNMG manual Evacuating the air

Page 48

Control box

Remove the screw for the control box cover

Remove the gas and liquid

For connecting the

service port caps

refrigerant pipes

Gas service port <Low pressure>

CAUTION

When installing, make sure there is no leakage. When recovering the refrigerant, ground the compressor first before removing the connection pipe. If the refrigerant pipe is not properly connected and the compressor works with the stop valve open, the pipe inhales the air and it makes the pressure inside of the refrigerant cycle abnormally high. It may cause explosion and injury.

1Leave the system in the standby mode.

WARNING

Do not turn on the system! This is necessary for better vacuum operation (full OPEN position of Electronic Expansion Valve).

2Connect the charging hose of the low pressure side of manifold gauge to a gas service port as seen in the picture.

Liquid service port

Connect the gas and liquid

<High pressure>

refrigerant pipes

Step 3.3 Evacuating the air

The outdoor unit is loaded with sufficient R-410A refrigerant. Do not vent R-410A into atmosphere: it is a fluorinated greenhouse gas, covered by Kyoto Protocol, with a Global Warming Potential (GWP) = 2088. You should evacuate the air in the indoor unit and in the pipe. If air remains in the refrigerant pipes, it affects the compressor. It may cause reduction of cooling capacity and malfunction. Use a vacuum pump.

3

Valve

15 minutes

4

Vacuum

Pump (Backward flowing prevention)

Liquid service port <Low pressure>

5

Liquid service port <High pressure>

English 47

Installation

MG_GOOD_R-410A_A3050_IB&IM_EN_ DB68-06070A-00.indd 47

12-May-16 11:30:01 AM

Image 48
Contents Samsung Air conditionergioner Contents Installation Safety Information on Installation PreparationSafety Information For InstallationSafety Information For Power Supply For Using Safety Information Safety Information For Cleaning MGGOODR-410AA3050IB&IMEN DB68-06070A-00.indd Indoor Unit Overview DisplayRemote Control Overview Inserting batteriesRemote Control Operation Controlling temperatureOperation modes Controlling fan speed Controlling air flow directionCool mode Cooling OperationStep cooling function Dry mode Dehumidifying OperationHeat mode Heating OperationQuick Smart Features Auto modeFan mode Fast function Comfort function Beep sound functionEnergy-Saving Operation Single user functionTimed on/Timed off function Good’sleep function Cleaning at a Glance Running Auto cleanCleaning the filter Troubleshooting Cleaning and Maintenance Technical Specifications ThailandModel AR24KRJSRWK/MG AR24KQJSBWK/MG Safety Information on Installation General informationPower supply line, fuse, or circuit breaker Choosing the installation location Overview of installation location requirementsPreparation Minimum clearances for the outdoor unitPacking and Unpacking Indoor unitOutdoor unit Checking and preparing accessories and tools AccessoriesDrilling a hole through the wall ToolsTaping the pipes, cables, and drain hose Indoor Unit Installation Disassembling the installation plateDisassembling the cover panel Connecting the cables Assembly cableOptional Extending the power cable Prepare a compressor and the following toolsInstalling and connecting the drain hose Optional Extending the drain hoseOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe 10 Fixing the installation plate When fixing the indoor unit on a wallWhen fixing the indoor unit on a window frame 11 Fixing the indoor unit to the installation plate When fixing the indoor unit on a gypsum board12 Assembling the cover panel Outdoor Unit Installation Connecting the cables and the refrigerant pipesFixing the outdoor unit in place Optional Fixing the outdoor unit to a wall with a rackEvacuating the air Adding refrigerant Installation Inspection Running the Smart Install modePerforming the gas leak tests LED Performing final check and trial operation Pumping down refrigerantPumping down for removing the product