Samsung AR24KQJSBWKNMG manual Adding refrigerant

Page 49

Installation

3Open the valve of the low pressure side of manifold gauge anticlockwise.

4Evacuate the air in the connected pipes using the vacuum pump for about 15 minutes.

Make sure that pressure gauge shows -0.1 MPa (-76 cmHg, 5 torr) after about 10 minutes. This procedure is very important to avoid a gas leak.

Close the valve of the low pressure side of manifold gauge clockwise.

Turn off the vacuum pump.

Check for 2 minutes if there is any pressure change.

Remove the hose of the low pressure side of manifold gauge.

5Set a valve cork of liquid and gas service port to the open position.

Step 3.4 Adding refrigerant

If you use a pipe longer than the length specified in the piping codes and standards, you must add 20 g (for ✴✴18/24✴✴) of refrigerant R-410A for each extra metre. If you use a pipe shorter than the length specified in the piping codes and standards, the evacuating time is normal. Refer to the Service Manual for further details.

CAUTION

The remaining air in the Refrigeration cycle, which contains moisture, may cause malfunction of the compressor.

Always contact the service centre or a professional installation agency for product installation.

R-410A is a mixed type of refrigerant. It is necessary for recharging under conditions of liquid. When recharging refrigerant from the refrigerant cylinder to the equipment, take the following instructions:

Before recharging, check whether the cylinder has a siphon or not. There are two ways to recharge the refrigerant:

 

 

 

 

Siphon

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Charge the refrigerant

Charge the refrigerant turning

standing the cylinder upright.

the cylinder upside down.

<Cylinder with siphon>

<Cylinder without siphon>

NOTE

If R-410A refrigerant is charged with gas, the composition of the charged refrigerant changes and the characteristics of the equipment vary.

During the measuring operation of refrigerant quantity added, use electronic scales. If cylinder doesn't have siphon, upset it.

48English

MG_GOOD_R-410A_A3050_IB&IM_EN_ DB68-06070A-00.indd 48

12-May-16 11:30:01 AM

Image 49
Contents Samsung Air conditionergioner Contents Safety Information on Installation Preparation InstallationFor Installation Safety InformationSafety Information For Power Supply For Using Safety Information Safety Information For Cleaning MGGOODR-410AA3050IB&IMEN DB68-06070A-00.indd Display Indoor Unit OverviewInserting batteries Remote Control OverviewControlling temperature Remote Control OperationOperation modes Controlling air flow direction Controlling fan speedCooling Operation Cool modeStep cooling function Dehumidifying Operation Dry modeHeating Operation Heat modeAuto mode Quick Smart FeaturesFan mode Fast function Beep sound function Comfort functionSingle user function Energy-Saving OperationTimed on/Timed off function Good’sleep function Running Auto clean Cleaning at a GlanceCleaning the filter Troubleshooting Cleaning and Maintenance Thailand Technical SpecificationsModel AR24KRJSRWK/MG AR24KQJSBWK/MG General information Safety Information on InstallationPower supply line, fuse, or circuit breaker Overview of installation location requirements Choosing the installation locationPreparation Minimum clearances for the outdoor unitIndoor unit Packing and UnpackingOutdoor unit Accessories Checking and preparing accessories and toolsTools Drilling a hole through the wallTaping the pipes, cables, and drain hose Disassembling the installation plate Indoor Unit InstallationDisassembling the cover panel Assembly cable Connecting the cablesPrepare a compressor and the following tools Optional Extending the power cableOptional Extending the drain hose Installing and connecting the drain hoseOptional Changing the direction of the drain hose Shortening or extending the refrigerant pipes assembly pipe When fixing the indoor unit on a wall 10 Fixing the installation plateWhen fixing the indoor unit on a window frame When fixing the indoor unit on a gypsum board 11 Fixing the indoor unit to the installation plate 12 Assembling the cover panel Connecting the cables and the refrigerant pipes Outdoor Unit InstallationFixing the outdoor unit in place Optional Fixing the outdoor unit to a wall with a rackEvacuating the air Adding refrigerant Running the Smart Install mode Installation InspectionPerforming the gas leak tests LED Pumping down refrigerant Performing final check and trial operationPumping down for removing the product
Related manuals
Manual 53 pages 47.38 Kb