INSTALLING HEATER

Continued

Installation must include a manual shutoff valve, ground joint union, plugged 1/8" NPT tap, and a sediment trap. Locate NPT tap within reach for test gauge hook up. NPT tap must be upstream from heater (see Figure 7).

Apply pipe joint sealant lightly to male threads. This will prevent excess sealant from going into pipe. Excess sealant in pipe could result in clogged heater valves.

CAUTION

Use pipe joint sealant that is resistant to liquid petro- leum (LP) gas.

Install sediment trap in supply line as shown in Figure 7. Locate sediment trap where it is within reach for cleaning. Locate sediment trap where trapped matter is not likely to freeze. A sediment trap traps moisture and contaminants. This keeps them from going into heater controls. If sediment trap is not installed or is installed wrong, heater may not run properly.

IMPORTANT: Use two pipe wrenches when connecting gas piping to gas control valve of heater. This will prevent turning or damaging control valve.

Control

Valve

Ground

Joint

Union

 

 

Reducer

 

 

 

Bushing to

 

Test

 

1/8" NPT

 

 

1/8" NPT

 

Gauge

 

 

 

Plug Tap

Connection*

 

 

Tee Joint

 

 

Sediment

 

 

Trap

Manual

Shutoff

Valve *

Tee Joint

Pipe

Nipple

Cap

Acceptable construction of inlet gas line

From Gas

Meter (5" W.C.

Min** to 7"

W.C. Max)

Preferred construction of inlet gas line

From

Gas Meter (5" W.C. Min** to 7" W.C. Max)

12

Figure 7 - Gas Connection

*An A.G.A. design-certified manual shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge connection. Purchase the optional A.G.A. design-certified manual shutoff valve from your dealer. See Accessories, page 37.

**For purposes of input adjustment.

100792

Image 12
Contents OWNER’S Operation and Installation Manual For Your SafetyWhat to do if YOU Smell GAS Contents Safety Information Carbon monoxide poisoning may lead to deathSafety Information Product IdentificationLocal Codes Unpacking Product Features Installation ItemsCheck GAS Type Locating Heater Heater ClearancesVenting Heater Venting Heater Do not vent heater in any of the following ways see FigureVenting Heater Proper Size Vent Connecting to GAS Supply Connecting Heater to Utility Gas LineGas Connection Pressure Testing Gas Supply Piping System Checking GAS ConnectionsInstalling Radiants Location of RadiantsInstalling Glass Panel Inserting Glass PanelsInserting Glass into Lower Retaining Channel AIR for Combustion and Ventilation Determining FRESH-AIR Flow for Heater Location Draft Hood Spillage TestVentilation Air from Outdoors Example 2 Locating Heater in Confined Closed Area For Your Safety Read Before Lighting Operating HeaterLighting Instructions Viewing Pilot Manual Lighting Procedure Blower OperationTo Turn OFF GAS to Appliance Shutting Off HeaterInspecting Pilot and Burner Flame Pilot Flame PatternBurner Flame Pattern Correct Burner Flame Pattern Cleaning and Maintenance Trouble Shooting Observed Possible Problem Cause RemedySee Changing Burner TROUBLE- Shooting See Removing ControlLighting Instructions Ing statement at TopService Procedures Removing Control Valve and Burner TubeRemoving Burner Blower Wiring Diagram Changing Burner OrificeTechnical Service Service Hints35,000 BTU/Hr 50,000 BTU/Hr ModelOrdering Replacement Parts Centrals Parts Under WarrantyParts Not Under Warranty Accessories Valve GA5010Illustrated Parts List Blower AssemblyCabinet Assembly Burner Assembly Thermocouple Interrupter 100792 100792 Warranty Information Limited Warranty Comfort Glow Vented Natural GAS Heaters