Desa CGR50NA, CGR35NA Determining FRESH-AIR Flow for Heater Location, Draft Hood Spillage Test

Page 18

AIR FOR COMBUSTION AND VENTILATION

Continued

In the absence of local codes, use the following excerpts from the National Fuel

Gas Code NFPA 54/ANSI Z223.1, Air for Combustion and Ventilation.

DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION

Example 1: Locating Heater in Unconfined (Open) Area

NOTICE

An unconfined area has a minimum air volume of 50 cubic feet for each 1000 BTU/Hr input rating of all appliances in the area (cubic feet equals length x width x height of area). Include adjoining rooms only if there are no doors between the rooms or if you add ventila- tion grills between the rooms (see Ventilating Confined Area, page 20).

In an open area, the air that leaks around doors and windows may provide enough fresh air for combustion and ventilation.

Draft Hood Spillage Test

Follow the steps below to see if enough fresh air is available.

1.Close all windows and doors.

2.If you have a fireplace, start a fire. Build fire until flames are burning strongly.

3.Turn on all exhaust fans. These include exhaust fans for kitchen, bathroom, water heaters (gas or electric), etc.

4.Turn on all vented gas appliances. These include any room heaters, water heaters, clothes dryer, etc.

5.Wait ten minutes for drafts to regulate.

6.Check for draft-hood spillage at each vented gas appliance. Do this by holding a lit match two inches from the draft opening (see Figure 14). If match flame pulls toward the draft hood, there is no spillage. If match flame blows away from the draft hood, there is spillage. This is a hazardous condition. See Draft Hood Spillage, page 19.

Vent Pipe

Draft Hood

Match

Typical

Water

Heater

Vent Pipe

Heater

Match

Draft Hood

Opening

18

Figure 14 - Checking for Draft Spillage

No Draft Hood Spillage: This shows there is enough fresh air in area for appliances. Turn off all exhaust fans and appliances if desired.

100792

Image 18
Contents OWNER’S Operation and Installation Manual For Your SafetyWhat to do if YOU Smell GAS Contents Safety Information Carbon monoxide poisoning may lead to deathSafety Information Product IdentificationLocal Codes Unpacking Product Features Installation ItemsCheck GAS Type Locating Heater Heater ClearancesVenting Heater Venting Heater Do not vent heater in any of the following ways see FigureVenting Heater Proper Size Vent Connecting to GAS Supply Connecting Heater to Utility Gas LineGas Connection Pressure Testing Gas Supply Piping System Checking GAS ConnectionsInstalling Radiants Location of RadiantsInstalling Glass Panel Inserting Glass PanelsInserting Glass into Lower Retaining Channel AIR for Combustion and Ventilation Determining FRESH-AIR Flow for Heater Location Draft Hood Spillage TestVentilation Air from Outdoors Example 2 Locating Heater in Confined Closed Area For Your Safety Read Before Lighting Operating HeaterLighting Instructions Viewing Pilot To Turn OFF GAS to Appliance Manual Lighting ProcedureBlower Operation Shutting Off HeaterInspecting Pilot and Burner Flame Pilot Flame PatternBurner Flame Pattern Correct Burner Flame Pattern Cleaning and Maintenance Trouble Shooting Observed Possible Problem Cause RemedySee Changing Burner TROUBLE- Shooting See Removing ControlLighting Instructions Ing statement at TopService Procedures Removing Control Valve and Burner TubeRemoving Burner Blower Wiring Diagram Changing Burner Orifice35,000 BTU/Hr 50,000 BTU/Hr Technical ServiceService Hints ModelOrdering Replacement Parts Centrals Parts Under WarrantyParts Not Under Warranty Accessories Valve GA5010Illustrated Parts List Blower AssemblyCabinet Assembly Burner Assembly Thermocouple Interrupter 100792 100792 Warranty Information Limited Warranty Comfort Glow Vented Natural GAS Heaters