Desa NATURAL GAS LOG HEATER installation manual AIR for, Combustion, Ventilation AIR

Page 7

AIR FOR

 

 

WARNING ICONG 001

WARNING

 

COMBUSTION

 

 

 

 

 

 

 

If the area in which the heater may be operated is smaller than

 

AND

 

that defined as an unconfined space, provide adequate combus-

 

 

tion and ventilation air by one of the methods described in the

 

VENTILATION

 

National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.

 

Continued

VENTILATION AIR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ventilation Air From Inside Building

 

 

This fresh air would come from an adjoining unconfined space. When ventilating to an

 

 

adjoining unconfined space, you must provide two permanent openings: one within 12" of the

 

 

ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and

 

 

2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow

 

 

the National Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and

 

 

Ventilation for required size of ventilation grills or ducts.

 

 

 

 

 

 

 

 

 

 

 

 

 

WARNING ICONG 001

WARNING

 

 

 

Rework worksheet, adding the space of the adjoining unconfined

 

 

 

space. The combined spaces must have enough fresh air to supply all

 

 

 

appliances in both spaces.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12"

 

 

 

 

Ventilation

 

 

 

 

 

 

 

 

 

 

 

Ventilation Grills

 

 

 

Grills

 

 

 

 

 

 

Into Adjoining

Or

 

 

Into Adjoining Room,

 

 

 

Room,

 

 

Option 2

 

 

 

Remove

 

 

 

 

 

Option 1

 

 

 

 

 

 

 

Door into

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adjoining

 

 

 

 

 

 

 

 

Room,

 

 

 

 

 

 

 

 

Option

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12"

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 2 - Ventilation Air from Inside Building

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two perma- nent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermo- stat-controlled power vent. Heated air entering the attic will activate the power vent.

 

Outlet

Ventilated

 

 

Attic

 

 

Air

 

 

 

 

Outlet

 

 

 

Air

 

To Attic

 

 

 

 

 

 

To

 

 

 

Crawl

 

Inlet

 

Space

 

 

 

 

Air

 

 

 

 

Inlet Air

Ventilated

 

 

Crawl Space

 

 

 

 

Figure 3 - Ventilation Air from Outdoors

7

 

 

 

101308

Image 7
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualContents Safety Information Information SafetyOperation Local Codes Unpacking Product FeaturesSafety Device Product IdentificationVentilation AIR for CombustionProviding Adequate Ventilation Determining AIR Flow for Heater Location AIR for Combustion and VentilationDetermining if You Have a Confined or Unconfined Space Combustion AIR forVentilation AIR Check GAS Type InstallingMinimum Wall and Ceiling Clearances see Figure To Combustible MaterialsLOG Sizing Requirements Ances from floor, ceiling, and adjoining wallMinimum Non Combustible Material Clearances Accessories,For Vented Operation, InstallingFloor Clearances Attaching Damper Clamp Installing Damper Clamp Accessory for Vented OperationInstallation Items Needed Installing Heater Base AssemblyAttaching Flexible Gas Hose to Heater Gas Regulator Installation Items Needed Connecting to GAS SupplyGas Connection Checking GAS ConnectionsTest Pressures Equal To or Less Than 1/2 Psig Pressure Testing Heater Gas ConnectionsInstalling Front Log Installing LogsOperating Heater For Your Safety Read Before LightingHeater OperatingThermostat-Controlled Models Only Operating Heater Models Pilot Flame Pattern Inspecting BurnersFront Burner Flame Pattern ODS/PILOT and Burners Trouble ShootingLogs TROUBLE- Shooting Cleaning and MainteTrouble Gas leak. See Warning Positioning OptionalSensing Bulb For Masonry Factory-built Metal Fireplace Optional Positioning Thermostat Sensing BulbHints ServiceService TechnicalParts Under Warranty Replacement PartsParts Not Under Warranty Hood GA6052 AccessoriesValve GA5010 Hood GA6050Illustrated Parts Break Down Description QTY Parts ListThermostat Controlled Models Parts List 101308 101308 Keep this Warranty Warranty Information