INSTALLING

Continued

18

3.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

4.Check all joints of gas supply piping system. Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Re-connect heater and manual shutoff valve to gas supply. Check re-connected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Figure 14).

2.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to manual shutoff valve (see Figure 15). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Pressure Testing Heater Gas Connections

1.Open manual shutoff valve (see Figure 14).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of heater is in the OFF position.

4.Check all joints from manual shutoff valve to thermostat gas valve (thermostat-con- trolled models) or control valve (manually-controlled models) (see Figure 15). Apply mixture of liquid soap and water to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light heater (see Operating Heater, pages 20 through 23). Check all other internal joints for leaks.

7.Turn off heater (see To Turn Off Gas to Appliance, page 21 [thermostat- controlled models] or page 23 [manually-controlled models]).

Open

Manual

Shutoff

Valve

Closed

Figure 14 - Manual Shutoff Valve

Manual

Thermostat Gas Valve or

Shutoff

Control Valve Location

Valve

 

Gas Meter

 

Figure 15 - Checking Gas Joints

101308

Image 18
Contents OWNER’S Operation and Installation Manual What to do if YOU Smell GASContents Safety Information Safety InformationProduct Identification Local Codes Unpacking Product FeaturesSafety Device OperationAIR for Combustion VentilationProviding Adequate Ventilation AIR for Combustion and Ventilation Determining AIR Flow for Heater LocationDetermining if You Have a Confined or Unconfined Space AIR for CombustionVentilation AIR Installing Check GAS TypeAnces from floor, ceiling, and adjoining wall To Combustible MaterialsLOG Sizing Requirements Minimum Wall and Ceiling Clearances see FigureAccessories, Minimum Non Combustible Material ClearancesInstalling For Vented Operation,Floor Clearances Installing Damper Clamp Accessory for Vented Operation Attaching Damper ClampInstalling Heater Base Assembly Installation Items NeededAttaching Flexible Gas Hose to Heater Gas Regulator Connecting to GAS Supply Installation Items NeededChecking GAS Connections Gas ConnectionPressure Testing Heater Gas Connections Test Pressures Equal To or Less Than 1/2 PsigInstalling Logs Installing Front LogFor Your Safety Read Before Lighting Operating HeaterOperating HeaterThermostat-Controlled Models Only Operating Heater Models Inspecting Burners Pilot Flame PatternFront Burner Flame Pattern Trouble Shooting ODS/PILOT and BurnersLogs Cleaning and Mainte TROUBLE- ShootingTrouble Gas leak. See Warning Optional PositioningSensing Bulb Optional Positioning Thermostat Sensing Bulb For Masonry Factory-built Metal FireplaceTechnical ServiceService HintsReplacement Parts Parts Under WarrantyParts Not Under Warranty Hood GA6050 AccessoriesValve GA5010 Hood GA6052Illustrated Parts Break Down Parts List Description QTYThermostat Controlled Models Parts List 101308 101308 Warranty Information Keep this Warranty