INSTALLATION
Continued
MANTEL CLEARANCES
In addition to meeting noncombustible material clearances, you must also meet required clearances between fireplace opening and mantel shelf. If you do not meet the clearances listed below, you will need a hood.
Determining Minimum Mantel Clearance If you meet minimum clearance between mantel shelf and top of fireplace opening, a hood is not required (see Figure 6).
Determining Minimum Mantel Clearance When Using a Hood
If minimum clearances in Figure 6 are not met, you must have a hood. When using a hood there are still certain minimum mantel clearances required. Follow minimum clearances shown in Figure 7 when using hood.
NOTICE: Surface temperatures of adjacent walls andmantels be- comehotduringoperation.Walls and mantels above the firebox may become hot to the touch. If installed properly, these tem- peratures meet the requirement of the national product standard. Follow all minimum clearances shown in this manual.
NOTICE: If your installation does not meet the minimum clear- ances shown, you must do one of the following:
• operate the logs only with the |
flue damper open and damper |
clamp installed |
10"
8"
6"
2 1/2"
Minimum Non- |
| (A) |
| ||
Combustible |
| |
|
| |
Material | 12" | |
| ||
| 8" |
Mantel Shelf
18" | 20" | 22" |
14" | 17" | 19" |
Underside
of Mantel
Shelf
All minimum distances are in inches
Log Set
24" 24" Models
20" 18" Model
• | raise the mantel to an ac- |
| ceptable height |
• | remove the mantel |
FLOOR CLEARANCES
A. | If installing appliance on the floor level, you |
| must maintain the minimum distance of 14" |
| to combustibles (see Figure 8). |
B. | If combustible materials are less than 14" to |
Minimum Non- | Distances to |
Combustible | Underside of |
Material Height | Mantel |
Top of
Fireplace
Opening
the fireplace, you must install appliance at |
least 5" above the combustible flooring (see |
Figure 9). |
Figure 6 - Minimum Mantel Clearances |
|
| |||
Without Using Hood |
|
|
| Combustible | |
|
|
|
|
| |
12" |
| Underside of | 14" | Material | |
10" |
|
| |||
| Mantel Shelf | Min. |
| ||
8" |
|
| |||
|
|
|
|
| |
6" |
|
| All minimum |
|
|
2 1/2" |
|
| distances are |
|
|
Minimum Non- |
|
| in inches |
| Noncombustible |
Combustible |
|
|
|
| Material |
Material |
|
| Log Sets | Figure 8 - Minimum Fireplace Clearances | |
8" | 12" 15" 18" | 20" | 18", 24" | ||
Min. |
|
| Models | If Installed at Floor Level | |
|
|
| |||
|
| Top of |
|
| |
Hood | Distances to | Fireplace |
|
| |
Opening |
|
| |||
(GA6050, |
|
| |||
Underside of |
|
| |||
|
|
|
| ||
GA6052 |
|
|
|
| |
Mantel |
|
|
|
| |
or GA6053) |
|
|
|
| |
|
|
|
|
| |
|
|
|
| Hearth | Combustible |
Figure 7 - Minimum Mantel Clearances |
| ||||
| Material | ||||
When Using Hood |
|
|
| ||
|
| 5" |
| ||
|
|
|
| Min. | |
|
|
|
| Figure 9 - Minimum Fireplace Clearances | |
|
|
|
| Above Combustible Flooring |
www.desatech.com | 11 |