Desa SF20NT installation manual Ventilation AIR, Ventilation Air From Inside Building

Page 6

AIR FOR COMBUSTION

AND VENTILATION

Continued

1.Determine the volume of the space (length x width x height).

Length x Width x Height =__________cu. ft. (volume of space)

Example: Space size 20 ft. (6.1 m) (length) x 16 ft. (4.88 m) (width) x 8 ft. (2.44 m) (ceiling height) = 2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Multiply the space volume by 20 to determine the maximum Btu/Hr the space can support.

__________ (volume of space) x 20 = (Maxi- mum Btu/Hr the space can support)

Example: 2560 cu. ft. (72.4 m3) (volume of space) x 20 = 51,200 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

_____________ Btu/Hr

Gas water heater*

_____________ Btu/Hr

Gas furnace

_____________ Btu/Hr

Vented gas heater

_____________ Btu/Hr

Gas fireplace logs

_____________ Btu/Hr

Other gas appliances* +____________ Btu/Hr

Total

=____________ Btu/Hr

*Do not include direct-vent gas appliances. Di- rect-vent draws combustion air from the outdoors and vents to the outdoors.

Example:

 

 

 

Gas water heater

 

40,000

Btu/Hr

Vent-free heater

+

20,000

Btu/Hr

Total

=

60,000

Btu/Hr

C.Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an un- confined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be oper- ated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA54 Section 5.3 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining un- confined space. When ventilating to an adjoining unconfined space, you must provide two perma- nent openings: one within 12" (30.4 cm) of the ceiling and one within 12" (30.4 cm) of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________ Btu/Hr (maximum the space can support)

_________ Btu/Hr (actual amount of Btu/Hr used)

Example: 51,200 Btu/Hr (maximum the space can support)

60,000 Btu/Hr (actual amount of Btu/Hr used)

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

The space in the above example is a confined space because the actual Btu/Hr used is more than the maxi- mum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework worksheet, adding the space of an adjoin- ing room. If the extra space provides an unconfined space, remove door to adjoining room or add ventilation grills between rooms. See Ventilation Air From Inside Building.

B.Vent room directly to the outdoors. See Ventila- tion Air From Outdoors, page 7.

12"

Figure 2 - Ventilation Air from Inside

Building

6

www.desatech.com

116307-01A

Image 6
Contents What to do if YOU Smell GAS Residential Models Garage ModelsTable of Contents Safety Information Product Features Local CodesUnpacking AIR for Combustion Ventilation Providing Adequate VentilationDetermining FRESH-AIR Flow for Heater Location Ventilation AIR Ventilation Air From Inside BuildingCheck GAS Type InstallationInstallation Items Ventilation Air From OutdoorsColdest part of room Installing Heater to WallLocating Heater Attaching to wall stud Attaching to wall anchorLocate hardware packet behind left side door of heater Marking Screw LocationsMark two screw locations on wall as shown in Figure Attaching To Wall Anchor MethodConnecting to GAS Supply External Regulator With Vent Pointing DownChecking GAS Connections Test Pressures In Excess Of 1/2 Psig 3.5 kPaTest Pressures Equal To or Less Than 1/2 Psig 3.5 kPa Operating Heater For Your Safety Read Before LightingInstalling Refractory and Front Panel Make sure control knob of heater is in the OFF positionLighting Instructions What to do if YOU Smell GASInspecting Heater Burner Pilot AIR Inlet Cleaning MaintenanceODS/PILOT and Burner CabinetTroubleshooting Observed Problem Possible Cause RemedyContact local propane/LP gas company Assembly Goes out when control knob is Control knob not pressedProblem could be caused by Delayed ignition of burners Manifold pressure is too lowWhen heated, vapors from Turn heater off when using Noise when burner is litDirty or partially clogged Clean burner see Cleaning Turn off air supplyWhen Gas Pressure Is Too Low Technical ServiceService Publications Service Hints Gas leak. See WarningSpecifications SF30NT SF30PTLSF30NT, VSF30NT LSF30PT, VSF30PT Accessories Replacement PartsParts Central Illustrated Parts Breakdown Parts List LSF20PTWarranty Information Keep this WarrantyQUÉ Hacer SI Percibe Olor a GAS Modelos Modelos Para CocheraTabla DE Contenido Información DE Seguridad Desempaque Códigos LocalesIdentificación DEL Producto Características DEL ProductoConstrucción inusualmente sellada Aire Para Combustión VentilaciónCómo Procurar LA Ventilación Adecuada Espacio confinado y no confinadoAire Para Ventilación Aire del interior de la construcción para ventilaciónArtículos DE Instalación InstalaciónVerifique EL Tipo DE GAS Aire del exterior para ventilaciónEn áreas con mucho viento o Ubicación DEL CalentadorColocación del calentador en los tornillos de montaje Instalación DEL Calentador EN LA ParedDoble en anclaje de pared como se muestra en la figura Coloque el calentador en los tornillos de montajeConexión AL Suministro DE GAS Ventila apuntando hacia abajoPropano o gas LP Revisión DE LAS Conexiones DE GASGas natural Repare todas las fugas inmediatamenteAbra la válvula de cierre del equipo consulte la figura Instale el panel anterior y el refractarioInstalación del panel anterior y el refractario Instrucciones DE Encendido No intente encender ningún aparatoFuncionamiento DEL Inspección DEL CalentadorEntrada DE Aire AL Piloto DEL Quemador Inspección DELLimpieza Y Mantenimiento Como se muestra en la figuraSolución DE Problemas Causa Posible RemedioEl termopar está dañado Problema Observado Causa Posible RemedioBaja presión del gas Presione totalmente la perilla de controlSe enciende o se apaga El problema desapareceráCierre el suministro de aire Silbante cuando el quemadorServicio Técnico Consejos Para ServicioCuando la presión del gas de entrada sea muy baja Especificaciones SF30NTLSF30NT, VSF30NT Accesorios Piezas DE RepuestoCentral DE Piezas Clasificación Ilustrada DE Piezas Lista DE Piezas Información DE Garantía Guarde Esta Garantía

SF20NT specifications

Desa SF20NT is a versatile and innovative gas-fired space heater designed for efficient heating solutions in various environments, whether in residential, commercial, or industrial settings. This model is known for its high performance, energy efficiency, and advanced technology, making it a popular choice among users seeking reliability and effectiveness in their heating needs.

One of the primary features of the Desa SF20NT is its impressive heating capacity. With a heating output of around 20,000 BTUs, it can effectively warm spaces up to 1,000 square feet, making it suitable for larger areas. This capability is enhanced by the heater's superior metal construction, ensuring durability and long-lasting performance.

In terms of technology, the Desa SF20NT incorporates a direct vent system that utilizes outside air for combustion. This feature not only increases efficiency but also enhances safety, as it minimizes the risk of hazardous fumes entering the living space. The direct vent system allows for installation flexibility; the unit can be vented horizontally through a wall or vertically through a roof, catering to different building designs.

Another standout characteristic of the Desa SF20NT is its thermostat control, which allows users to maintain a consistent temperature easily. This feature contributes to energy savings by enabling the heater to operate only when necessary, thus reducing unnecessary heating costs. Additionally, the unit includes a programmable timer, allowing users to set specific heating schedules, further optimizing energy use.

Safety is also a critical aspect of the Desa SF20NT design. It comes with built-in safety features such as a flame sensor and a safety shut-off system, ensuring that the heater operates under safe conditions at all times. The unit is designed to meet stringent safety standards, giving users peace of mind.

In summary, the Desa SF20NT is a powerful, efficient, and safe space heater that is equipped with modern features and technologies. With its high heating capacity, direct vent system, thermostat control, and safety mechanisms, it stands out as an excellent choice for anyone looking for reliable heating solutions. Whether for home or business use, the Desa SF20NT is built to provide comfort and efficiency year-round.