6Termination Locations

A. Vent Termination Minimum Clearances

WARNING

Fire Risk.

Maintain vent clearance to combustibles as speci ed.

DO NOT pack air space with insulation or other materials.

Failure to keep insulation or other materials away from vent pipe may cause overheating and re.

Direct Vent Gas, Wood or Fuel

Oil Termination

20 in.

 

 

A

(508 mm)

18 in.

 

(minimum) to

 

 

 

 

Perpendicular

(457 mm)

 

 

Wall

 

B

 

(DV only)

 

 

 

Gas

Termination

24 in. min.

(610 mm)

Termination

Cap

Storm Collar

20 in. (508 mm)

Lowest

Discharge

Opening

12

Horizontal overhang

Vertical wall

X

Termination Caps Staggered Height

A

Gas Termination

Wood or Fuel Oil Termination

B

6 in. (152 mm) min.

20 in. (508 mm) min.

Figure 6.2 Staggered Termination Caps

Direct Vent Gas, Wood or Fuel

Oil Termination

Wood, Gas or

Fuel Oil

Roof Flashing

Roof Pitch is X / 12

H (min.) - Minimum height from roof to lowest discharge opening.

Termination

 

 

 

 

20 in.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(508 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(minimum) to

 

 

 

 

20 in. min. *

 

 

 

Perpendicular

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wall

 

 

 

 

 

 

(508 mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(DV only)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Roof Pitch

H (Min.) Ft.

Roof Pitch

H (Min.) Ft.

Flat to 6/12

 

1.0*

Over 11/12 to 12/12

4.0

Over 6/12 to 7/12

1.25*

Over 12/12 to 14/12

5.0

Over 7/12 to 8/12

1.5*

Over 14/12 to 16/12

6.0

Over 8/12 to 9/12

2.0*

Over 16/12 to 18/12

7.0

Over 9/12 to 10/12

2.5

Over 18/12 to 20/12

7.5

Over 10/12 to 11/12

3.25

Over 20/12 to 21/12

8.0

 

* 3 ft. minimum in snow regions

 

 

Termination Caps Same Height

*If using decorative cap cover(s), this distance may need to be increased. Refer to the installation instruc- tions supplied with the decorative cap cover.

Figure 6.3 Leveled Termination Caps

Figure 6.1 Minimum Height From Roof To Lowest Discharge Opening

Quadra-Fire • QFP44 • 4051-300 Rev M • 09/08

27

Image 27
Contents Installation and Operation ModelsWhat to do if you smell gas Homeowner Reference Information CongratulationsTable of Contents Installer GuideUser Guide Troubleshooting CONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Gas Fireplace Safety Operating InstructionsYour Fireplace Dashboard Control Fixed Glass AssemblyClear Space Decorative Doors and FrontsIgnitor Battery Box Remote OperationCanadian Equipment Requirements Transmitter Remote ReceiverOperating Instructions Transmitter SettingsSetting the Clock Matching Security CodesOperating the Fan Operates in on or THER- MO mode Setting F/C ScaleSetting Desired Room Temperature Ther- mo Operations Setting the Countdown TimerThermo-Updating and Communication-Safety Features Adjusting the Flame Height Operates in on or Thermo modeLow/Battery Indicator Transmitter Safety FeaturesGeneral Information Transmitter Wall Bracket Timer OperationBattery Life Before Lighting FireplaceLighting Instructions SP For Your Safety Read Before LightingFrequently Asked Questions Initial Break-in ProcedureAfter Fireplace is Lit Remote Control Maintenance and ServiceMaintenance Tasks-Homeowner Glass CleaningMaintenance Tasks-Quali ed Service Technician Standing Pilot Flame Patterns Typical Appliance System Getting StartedDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Select Appliance Location Framing and ClearancesClearances Construct the Appliance ChaseMantel and Wall Projections MantelsMantel Legs or Wall Projections Vent Termination Minimum Clearances Termination LocationsMinimum Clearances for Termination Use of Elbows Vent Information and DiagramsApproved Pipe Vent Table KeyVent Diagrams Top Vent Horizontal TerminationOne Elbow Three Elbows Two 45 Elbows replacing One 90 ElbowTop Vent Vertical Termination No ElbowTwo Elbows 12 ft 3.66 m min 60 ft 18.29 m max Combustible Wall Penetration Vent Clearances and FramingPipe Clearances to Combustibles Wall Penetration FramingInstalling Ceiling Firestop Install the Ceiling FirestopInstall Attic Insulation Shield Flat Ceiling InstallationVaulted Ceiling Installation Secure and Level the Appliance Appliance PreparationAssemble Pipe Sections Install Vent PipeAttach Pipe to the Firebox Assembly Assemble Vent SectionsSlip Section Pilot Holes Assemble Slip SectionsDisassemble Vent Sections Secure the Vent SectionsCaulk Install Metal Roof Flashing13 Assembling the Storm Collar Assemble and Install Storm CollarApply Sealant Top & Partial Sides Install RF4-8Heat Shield Requirements for Horizontal Termination Install Vertical Termination Cap20 Venting through the wall Install Horizontal Termination CapConverting to LP Gas Kit contentsGas Information Fuel Conversion44CKP Gas Connection Gas PressureElectrical Information Wiring RequirementsStanding Pilot Ignition System Wiring Optional Accessories RequirementsJunction Box Installation Electrical Service and RepairMantel Leg or Perpendicular Wall FinishingFacing Material Facing Template RemovalMantel Clean the Appliance Appliance SetupRemove Glass Assembly Install the RefractoryInstall Upper Back Refractory Adjust the Air ShutterInstall Logs, Ember Bed & Rockwool Adjust the Vertical Baf e12 Positioning Right Front Leg Install Andirons Reinstall Glass Install Door FrontsPlace Lava Rock and Vermiculite Standing Pilot Ignition System TroubleshootingSymptom Possible Cause Corrective Action TroubleshootingReference Materials Appliance Dimension DiagramDVP45 Vent Components DiagramsBEK DVP-BEK2 DVP-TVHW DVP-TRAP Parts ServiceDescription Serial # Part Number Service PartsOptional Components Contact Information

QFP44 specifications

The Quadra-Fire QFP44 is a highly efficient and versatile pellet stove designed to provide warmth and comfort while offering a range of advanced features and technologies. It stands out in the market for its blend of efficiency, user-friendly operation, and aesthetic appeal.

One of the key features of the QFP44 is its impressive heat output. With a heating capacity of up to 2,500 square feet, it is suitable for medium to larger living spaces, making it an ideal choice for families looking for an effective heating solution. The stove boasts an adjustable output, allowing users to set the heat level according to their specific needs, which promotes energy efficiency and enhances comfort.

The QFP44 utilizes a patented feed system that ensures a consistent and reliable supply of pellets for combustion. This technology not only maximizes fuel efficiency but also minimizes the need for frequent refueling. In addition, the stove features a large hopper capacity, capable of holding up to 45 pounds of pellets. This translates into longer burn times, enabling users to enjoy hours of warmth without constant supervision.

Another notable characteristic of the QFP44 is its advanced control system. The innovative electronic control board allows users to monitor and adjust the stove settings easily. The system includes programmable temperature settings, which enable homeowners to schedule heating times according to their lifestyle. This convenience makes the stove ideal for those who want to return to a warm home without wasting energy.

The QFP44 is also engineered with a clean-burning technology that significantly reduces emissions. This feature not only makes the stove environmentally friendly but also enhances its safety profile. The high-efficiency combustion system effectively converts pellets into heat with minimal smoke and pollutants, fulfilling strict environmental standards.

For aesthetic appeal, the QFP44 is designed with a contemporary look, featuring a large viewing window that allows users to enjoy the beautiful ambiance of the flame. The stove is available in various finishes, making it a stylish addition to any home décor.

Overall, the Quadra-Fire QFP44 combines efficiency, user-friendly technology, and an elegant design, making it a top choice for anyone seeking an effective and attractive pellet heating solution. Its blend of features ensures homeowners can enjoy both comfort and convenience during the cold months while maintaining an environmentally responsible heating option.