Quadra-Fire QFP44 owner manual Requirements for the Commonwealth of Massachusetts

Page 8

Note: The following requirements reference various Massachusetts and national codes not contained in this document.

H. Requirements for the Commonwealth of Massachusetts

For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above nished grade in the area of the venting, in- cluding but not limited to decks and porches, the following requirements shall be satis ed:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gas tter shall observe that a hard wired carbon mon- oxide detector with an alarm and battery back-up is installed on the oor level where the gas equipment is to be installed. In addition, the installing plumber or gas tter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or struc- ture served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of quali ed licensed profes- sionals for the installation of hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level.

In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements; provided, however, that dur- ing said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accor- dance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certi ed.

Signage

A metal or plastic identi cation plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) in. in size,

“GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizon- tally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector ob- serves carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.

Exemptions

The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and

Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or structure used in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:

Detailed instructions for the installation of the venting system design or the venting system components; and

A complete parts list for the venting system design or venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the ue gases, but identi- es “special venting systems”, the following requirements shall be satis ed by the manufacturer:

The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and

The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.

A copy of all installation instructions for all Product Ap- proved side wall horizontally vented gas fueled equip- ment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

See Gas Connection section for additional Common- wealth of Massachusetts requirements.

8

Quadra-Fire • QFP44 • 4051-300 Rev M • 09/08

Image 8
Contents What to do if you smell gas Installation and OperationModels Congratulations Homeowner Reference InformationUser Guide Table of ContentsInstaller Guide Troubleshooting CONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Your Fireplace Gas Fireplace SafetyOperating Instructions Fixed Glass Assembly Clear SpaceDecorative Doors and Fronts Dashboard ControlCanadian Equipment Requirements Ignitor Battery BoxRemote Operation Remote Receiver TransmitterTransmitter Settings Setting the ClockMatching Security Codes Operating InstructionsSetting F/C Scale Setting Desired Room Temperature Ther- mo OperationsSetting the Countdown Timer Operating the Fan Operates in on or THER- MO modeAdjusting the Flame Height Operates in on or Thermo mode Low/Battery IndicatorTransmitter Safety Features Thermo-Updating and Communication-Safety FeaturesTimer Operation Battery LifeBefore Lighting Fireplace General Information Transmitter Wall BracketFor Your Safety Read Before Lighting Lighting Instructions SPAfter Fireplace is Lit Frequently Asked QuestionsInitial Break-in Procedure Maintenance and Service Maintenance Tasks-HomeownerGlass Cleaning Remote ControlMaintenance Tasks-Quali ed Service Technician Standing Pilot Flame Patterns Getting Started Typical Appliance SystemInspect Appliance and Components Design and Installation ConsiderationsTools and Supplies Needed Framing and Clearances Select Appliance LocationConstruct the Appliance Chase ClearancesMantel Legs or Wall Projections Mantel and Wall ProjectionsMantels Termination Locations Vent Termination Minimum ClearancesMinimum Clearances for Termination Vent Information and Diagrams Approved PipeVent Table Key Use of ElbowsOne Elbow Vent DiagramsTop Vent Horizontal Termination Two 45 Elbows replacing One 90 Elbow Three ElbowsTwo Elbows Top Vent Vertical TerminationNo Elbow 12 ft 3.66 m min 60 ft 18.29 m max Vent Clearances and Framing Pipe Clearances to CombustiblesWall Penetration Framing Combustible Wall PenetrationInstall the Ceiling Firestop Installing Ceiling FirestopVaulted Ceiling Installation Install Attic Insulation ShieldFlat Ceiling Installation Appliance Preparation Secure and Level the ApplianceInstall Vent Pipe Attach Pipe to the Firebox AssemblyAssemble Vent Sections Assemble Pipe SectionsAssemble Slip Sections Slip Section Pilot HolesSecure the Vent Sections Disassemble Vent SectionsInstall Metal Roof Flashing CaulkAssemble and Install Storm Collar 13 Assembling the Storm CollarInstall RF4-8 Apply Sealant Top & Partial SidesInstall Vertical Termination Cap Heat Shield Requirements for Horizontal TerminationInstall Horizontal Termination Cap 20 Venting through the wallKit contents Gas InformationFuel Conversion Converting to LP Gas44CKP Gas Pressure Gas ConnectionWiring Requirements Standing Pilot Ignition System WiringOptional Accessories Requirements Electrical InformationElectrical Service and Repair Junction Box InstallationFinishing Mantel Leg or Perpendicular WallMantel Facing MaterialFacing Template Removal Appliance Setup Remove Glass AssemblyInstall the Refractory Clean the ApplianceAdjust the Air Shutter Install Upper Back RefractoryAdjust the Vertical Baf e Install Logs, Ember Bed & Rockwool12 Positioning Right Front Leg Place Lava Rock and Vermiculite Install Andirons Reinstall GlassInstall Door Fronts Troubleshooting Standing Pilot Ignition SystemTroubleshooting Symptom Possible Cause Corrective ActionAppliance Dimension Diagram Reference MaterialsVent Components Diagrams DVP45BEK DVP-BEK2 DVP-TVHW DVP-TRAP Service PartsService Parts Description Serial # Part NumberOptional Components Contact Information

QFP44 specifications

The Quadra-Fire QFP44 is a highly efficient and versatile pellet stove designed to provide warmth and comfort while offering a range of advanced features and technologies. It stands out in the market for its blend of efficiency, user-friendly operation, and aesthetic appeal.

One of the key features of the QFP44 is its impressive heat output. With a heating capacity of up to 2,500 square feet, it is suitable for medium to larger living spaces, making it an ideal choice for families looking for an effective heating solution. The stove boasts an adjustable output, allowing users to set the heat level according to their specific needs, which promotes energy efficiency and enhances comfort.

The QFP44 utilizes a patented feed system that ensures a consistent and reliable supply of pellets for combustion. This technology not only maximizes fuel efficiency but also minimizes the need for frequent refueling. In addition, the stove features a large hopper capacity, capable of holding up to 45 pounds of pellets. This translates into longer burn times, enabling users to enjoy hours of warmth without constant supervision.

Another notable characteristic of the QFP44 is its advanced control system. The innovative electronic control board allows users to monitor and adjust the stove settings easily. The system includes programmable temperature settings, which enable homeowners to schedule heating times according to their lifestyle. This convenience makes the stove ideal for those who want to return to a warm home without wasting energy.

The QFP44 is also engineered with a clean-burning technology that significantly reduces emissions. This feature not only makes the stove environmentally friendly but also enhances its safety profile. The high-efficiency combustion system effectively converts pellets into heat with minimal smoke and pollutants, fulfilling strict environmental standards.

For aesthetic appeal, the QFP44 is designed with a contemporary look, featuring a large viewing window that allows users to enjoy the beautiful ambiance of the flame. The stove is available in various finishes, making it a stylish addition to any home décor.

Overall, the Quadra-Fire QFP44 combines efficiency, user-friendly technology, and an elegant design, making it a top choice for anyone seeking an effective and attractive pellet heating solution. Its blend of features ensures homeowners can enjoy both comfort and convenience during the cold months while maintaining an environmentally responsible heating option.