Quadra-Fire QFP44 owner manual Install Attic Insulation Shield, Flat Ceiling Installation

Page 36

D. Install Attic Insulation Shield

WARNING! Fire Risk. DO NOT allow loose materials or insulation to touch vent. Hearth & Home Technologies Inc. requires the use of an attic shield.

The National Fuel Gas Code ANSI Z223.1 and NFPA 54 requires an attic shield constructed of 26 gauge minimum metal that extends at least 2 in. (51 mm) above insulation.

Attic shields must meet speci ed clearance and be se- cured in place.

Flat Ceiling Installation

Remove one shield from box.

NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.

Wrap shield around pipe if pipe is already installed in area to be insulated.

Match the three holes in each side and fasten with three screws to form a tube.

Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling restop.

Bend the remaining bottom tabs inward 90° to maintain the air space between the pipe and the shield. Set the shield on the ceiling restop and attach to the restop.

Bend all tabs inward 90° around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.

Vaulted Ceiling Installation

The attic insulation shield has been laser-etched with ceiling pitch cut lines to make eld trimming easier.

Remove one shield from box.

NOTICE: Cut previously installed batt insulation to make room for the attic insulation shield.

Cut the attic insulation shield (if application is for vaulted ceiling) using a laser-etched cut line, to t your ceiling pitch. Snip cut edge to recreate 1 in. bend tabs all the way around the bottom.

Wrap shield around pipe if pipe is already installed in area to be insulated.

Match the three holes in each side and fasten with three screws to form a tube.

Bend three tabs on the bottom of the shield outward to allow attachment to the ceiling restop.

Bend the remaining bottom tabs inward 90° to maintain the air space between the pipe and the shield. Set the shield on the ceiling restop and attach to the restop.

Bend all tabs inward 90° around the top of the shield. These tabs must be used to prevent blown insulation from getting between the shield and vent pipe, and to maintain air space clearance.

 

Laser-etched

Bend all tabs inward

cut lines

Insert 3

90° to maintain

screws

clearance and

Bend 4 tabs

prevent insulation

from falling inside

inward 90°

 

to maintain

 

clearance

Figure 8.5 Attic Insulation Shield

36

Quadra-Fire • QFP44 • 4051-300 Rev M • 09/08

Image 36
Contents Installation and Operation ModelsWhat to do if you smell gas Congratulations Homeowner Reference InformationTable of Contents Installer GuideUser Guide Troubleshooting CONDITIONS, Exclusions & Limitation of Liability Limited Lifetime Warranty Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Gas Fireplace Safety Operating InstructionsYour Fireplace Fixed Glass Assembly Clear SpaceDecorative Doors and Fronts Dashboard ControlIgnitor Battery Box Remote OperationCanadian Equipment Requirements Remote Receiver TransmitterTransmitter Settings Setting the ClockMatching Security Codes Operating InstructionsSetting F/C Scale Setting Desired Room Temperature Ther- mo OperationsSetting the Countdown Timer Operating the Fan Operates in on or THER- MO modeAdjusting the Flame Height Operates in on or Thermo mode Low/Battery IndicatorTransmitter Safety Features Thermo-Updating and Communication-Safety FeaturesTimer Operation Battery LifeBefore Lighting Fireplace General Information Transmitter Wall BracketFor Your Safety Read Before Lighting Lighting Instructions SPFrequently Asked Questions Initial Break-in ProcedureAfter Fireplace is Lit Maintenance and Service Maintenance Tasks-HomeownerGlass Cleaning Remote ControlMaintenance Tasks-Quali ed Service Technician Standing Pilot Flame Patterns Getting Started Typical Appliance SystemDesign and Installation Considerations Tools and Supplies NeededInspect Appliance and Components Framing and Clearances Select Appliance LocationConstruct the Appliance Chase ClearancesMantel and Wall Projections MantelsMantel Legs or Wall Projections Termination Locations Vent Termination Minimum ClearancesMinimum Clearances for Termination Vent Information and Diagrams Approved PipeVent Table Key Use of ElbowsVent Diagrams Top Vent Horizontal TerminationOne Elbow Two 45 Elbows replacing One 90 Elbow Three ElbowsTop Vent Vertical Termination No ElbowTwo Elbows 12 ft 3.66 m min 60 ft 18.29 m max Vent Clearances and Framing Pipe Clearances to CombustiblesWall Penetration Framing Combustible Wall PenetrationInstall the Ceiling Firestop Installing Ceiling FirestopInstall Attic Insulation Shield Flat Ceiling InstallationVaulted Ceiling Installation Appliance Preparation Secure and Level the ApplianceInstall Vent Pipe Attach Pipe to the Firebox AssemblyAssemble Vent Sections Assemble Pipe SectionsAssemble Slip Sections Slip Section Pilot HolesSecure the Vent Sections Disassemble Vent SectionsInstall Metal Roof Flashing CaulkAssemble and Install Storm Collar 13 Assembling the Storm CollarInstall RF4-8 Apply Sealant Top & Partial SidesInstall Vertical Termination Cap Heat Shield Requirements for Horizontal TerminationInstall Horizontal Termination Cap 20 Venting through the wallKit contents Gas InformationFuel Conversion Converting to LP Gas44CKP Gas Pressure Gas ConnectionWiring Requirements Standing Pilot Ignition System WiringOptional Accessories Requirements Electrical InformationElectrical Service and Repair Junction Box InstallationFinishing Mantel Leg or Perpendicular WallFacing Material Facing Template RemovalMantel Appliance Setup Remove Glass AssemblyInstall the Refractory Clean the ApplianceAdjust the Air Shutter Install Upper Back RefractoryAdjust the Vertical Baf e Install Logs, Ember Bed & Rockwool12 Positioning Right Front Leg Install Andirons Reinstall Glass Install Door FrontsPlace Lava Rock and Vermiculite Troubleshooting Standing Pilot Ignition SystemTroubleshooting Symptom Possible Cause Corrective ActionAppliance Dimension Diagram Reference MaterialsVent Components Diagrams DVP45BEK DVP-BEK2 DVP-TVHW DVP-TRAP Service PartsService Parts Description Serial # Part NumberOptional Components Contact Information

QFP44 specifications

The Quadra-Fire QFP44 is a highly efficient and versatile pellet stove designed to provide warmth and comfort while offering a range of advanced features and technologies. It stands out in the market for its blend of efficiency, user-friendly operation, and aesthetic appeal.

One of the key features of the QFP44 is its impressive heat output. With a heating capacity of up to 2,500 square feet, it is suitable for medium to larger living spaces, making it an ideal choice for families looking for an effective heating solution. The stove boasts an adjustable output, allowing users to set the heat level according to their specific needs, which promotes energy efficiency and enhances comfort.

The QFP44 utilizes a patented feed system that ensures a consistent and reliable supply of pellets for combustion. This technology not only maximizes fuel efficiency but also minimizes the need for frequent refueling. In addition, the stove features a large hopper capacity, capable of holding up to 45 pounds of pellets. This translates into longer burn times, enabling users to enjoy hours of warmth without constant supervision.

Another notable characteristic of the QFP44 is its advanced control system. The innovative electronic control board allows users to monitor and adjust the stove settings easily. The system includes programmable temperature settings, which enable homeowners to schedule heating times according to their lifestyle. This convenience makes the stove ideal for those who want to return to a warm home without wasting energy.

The QFP44 is also engineered with a clean-burning technology that significantly reduces emissions. This feature not only makes the stove environmentally friendly but also enhances its safety profile. The high-efficiency combustion system effectively converts pellets into heat with minimal smoke and pollutants, fulfilling strict environmental standards.

For aesthetic appeal, the QFP44 is designed with a contemporary look, featuring a large viewing window that allows users to enjoy the beautiful ambiance of the flame. The stove is available in various finishes, making it a stylish addition to any home décor.

Overall, the Quadra-Fire QFP44 combines efficiency, user-friendly technology, and an elegant design, making it a top choice for anyone seeking an effective and attractive pellet heating solution. Its blend of features ensures homeowners can enjoy both comfort and convenience during the cold months while maintaining an environmentally responsible heating option.