2. Continue Adding Vent Components

2. Continue Adding Vent Components

Refer to Cinch Pipe and Termination Cap installation in- structions.

Continue adding vent components, locking each succeed- ing component into place.

Ensure that each succeeding vent component is secure- ly fitted and locked into the preceding component in the vent system. Securing pipe sections with a maximum of two screws is recommended.

90° elbows may be installed and rotated to any point around the preceding component’s vertical axis. If an el- bow does not end up in a locked position with the pre- ceding component, attach with a minimum of two (2) sheet metal screws.

3.Install Support Brackets

Refer to Cinch Pipe and Termination Cap installation instructions.

4. Install Firestops

For Horizontal Runs - Firestops are REQUIRED on both sides of a combustible wall through which the vent passes.

NOTE: Model DVP-TRAP does not need an exterior firestop on an exterior combustible wall. The firestop is built into the cap.

To install firestops for horizontal runs that pass through either interior or exterior walls:

• Cut a 10” x 12” (254mm X 305mm) hole through the wall.

NOTE: The center of the hole is one (1) inch (25.4mm) above the center of the horizontal vent pipe.

Position the firestops on both sides of the hole previ- ously cut and secure the firestops with nails or screws.

The heat shields of the firestops MUST BE placed to- wards the top of the hole.

Continue the vent run through the firestops.

NOTE: There must be NO INSULATION or other combustibles inside the framed firestop opening.

10"

INTERIOR

WALL SHIELD

12"

Figure 23. 10" x 12" Hole and Vent Pipe

HEAT SHIELD

TRIM HEAT SHIELD IF TOO LONG, ADD TO SHIELD IF TOO SHORT

EXTERIOR

FIRESTOP

INTERIOR

FIRESTOP

Figure 24 Heat Shield, Interior & Exterior Firestops

For Vertical Runs - One ceiling firestop is REQUIRED at the hole in each ceiling through which the vent passes.

To install firestops for vertical runs that pass through ceilings:

Position a plumb bob directly over the center of the verti- cal vent component.

Mark the ceiling to establish the centerpoint of the vent.

Drill a hole or drive a nail through this centerpoint.

Check the floor above for any obstructions, such as wir- ing or plumbing runs.

Reposition the fireplace and vent system, if necessary, to accommodate the ceiling joists and/or obstructions.

Cut an 10-inch X 10-inch (254mm x 254mm) hole through the ceiling, using the centerpoint previously marked.

Frame the hole with framing lumber the same size as the ceiling joists.

Quadra-FireQV-PIER, QV-ST Series: HV-IPI2005-901 Rev. G • 2/06

25

Image 25
Contents What to do if you smell gas Models QV-Pier QV-ST Series HV-IPIPROHIBITED Safety and Warning InformationTable of Contents QV-Pier-HV-IPI Service Parts List6 Log Assembly QV-PIER-HV-IPI ACCESSORIESCOMMON PART SERIAL #11710 Service PartsQV-ST-HV-IPI NG, LP Exploded Parts DiagramQV-ST-HV-IPI QV-PIER-HV-IPI Service PartsQV-ST-HV-IPI Installation Codes 1Approvals and CodesHigh Altitude Installations Appliance CertificationPre-installPreparation 2Getting StartedIntroducing the Quadra-FireGas Fireplaces Diagram of the QV-PIER-HV-IPI ELECTRICAL ACCESS GAS LINE ACCESSTOP STANDOFFS REAR VENTStep 1. Locating the Fireplace 3Installing the FireplaceStep 2. Framing the Fireplace QV-PIER-HV-IPI Model35-3/4 QV-ST-HV-IPIDVP90ST NOTE PIPES OVERLAP 1-1/4INCHES AT EACH JOINTA. Vent System Approvals Step 3. Installing the Vent SystemTEMS OR COMPONENTS MAY BE USED Identifying Vent ComponentsFlue Restrictor Instructions Figure 14. Venting with One 90 Elbow Figure 13. Venting with One 90 ElbowFigure 15. Venting with Two 90 Elbows Figure 17. Venting with Two 90 Elbows Venting with Two 90 ElbowsFigure 18. Venting with three 90 elbows Figure 19. Venting with three 90 elbows Venting Out Vertically B. Installing Vent Components2. Continue Adding Vent Components Figure 25 Hole & New Framing Members Figure 29. Vent Termination Minimum Clearances = AREA WHERE TERMINAL IS NOT PERMITTED= VENT TERMINAL X = AIR SUPPLY INLETMark the roof hole accordingly Step 5. The Gas Control System Natural Gas PressurePropane 5.0 inchesFor Intermittent Pilot Ignition Wiring Step 8. Wiring the FireplaceOperation using Battery Power Appliance RequirementsOptional Accessories Figure 35. Fan Wiring DiagramFan Installation Wall SwitchIN ANY MANNER Step 9. FinishingFigure 40. Sealant Material Hearth Extensions ANDIRONS 1/2”ANDIRON TABS Page Placing the Ember Material Figure 53. Placement of the Ember MaterialStep 11. Before Lighting the Fireplace After the InstallationStep 12. Lighting the Fireplace Fireplace Maintenance 4Maintaining and Servicing Your FireplaceSymptom 5 TroubleshootingPossible Causes Corrective ActionsIntellifire Ignition System - continued SymptomPossible Causes Corrective ActionsLIMITED LIFETIME WARRANTY Lifetime WarrantyTHREE YEAR WARRANTY TWO YEAR WARRANTY