Quadra-Fire QFP38-NG, QFP38-LP owner manual Troubleshooting

Page 64

16 Troubleshooting

A. Troubleshooting

With proper installation, operation, and maintenance your gas appliance will provide years of trouble-free service. If you do experience a problem, this troubleshooting guide will assist a qualified service technician in the diagnosis of a problem and the corrective action to be taken. This troubleshooting guide can only be used by a qualified service technician. Con- tact your dealer to arrange a service call by a qualified service technician.

The normal behaviors of the board could be inhibited by the anomalies described in the following tables.

Note on the automatic ignition sequence:

The supervised pilot flame detection is activated only after a command is correctly received.

The sparking means are activated only after no parasitic flame is detected, before the ignition.

The pilot gas valve is energized, and the gas will flow, only after the sparking means are activated.

The main burner gas valve is energized, and gas will flow, only if commanded and after the supervised pilot flame is detected to be continuously lit.

The system will try two times for ignition.

Each try for ignition will last approximately 60 seconds.

The wait time between the two tries is approximately 35 seconds.

If there is no positive ignition, after two tries, the ignition module will go into lockout.

Note: To reset the ignition module lockout - turn the unit off for five seconds, then back on.

 

Symptom

 

Possible Cause

Corrective Action

1.

The ignitor/

a.

Incorrect wiring.

Verify “S” wire (white) for sensor and “I” wire (orange) for ignitor are connected to the

 

module makes

 

 

correct terminals on the module and the pilot assembly. Reversed wires at the module

 

noise, but no

 

 

may cause the system to make a sparking noise, but the spark may not be present at

 

spark.

 

 

pilot hood.

 

 

 

 

 

 

 

b.

Loose connections or

Verify there are no loose connections or electrical shorts in wiring from module to

 

 

 

electrical shorts in the wiring.

pilot assembly. The rod closest to the pilot hood should be ignitor. Verify connections

 

 

 

 

underneath pilot assembly are tight; also verify the connections are not grounding out

 

 

 

 

to the metal chassis, pilot burner, pilot enclosure, mesh screen if present, or any other

 

 

 

 

metal object.

 

 

 

 

 

 

 

c.

Ignitor gap is too large.

Verify gap of ignitor to pilot hood. The gap should be approximately .17 in. or 1/8 in.

 

 

 

 

 

 

 

d.

Faulty module.

Turn ON/OFF rocker switch or wall switch to OFF position. Remove ignitor wire “I”

 

 

 

 

from module. Place ON/OFF rocker switch or wall switch in ON position. Hold ground

 

 

 

 

wire about 3/16 in. away from “I” terminal on module. If there is no spark at “I” terminal,

 

 

 

 

module must be replaced. If there is a spark at “I” terminal, module is fine. Inspect pilot

 

 

 

 

assembly for shorted sparker wire or cracked insulator around electrode.

 

 

 

 

 

2.

Pilots won’t light,

a.

Fireplace burner control

Verify that fireplace burner control is installed and plugged into module. Check voltage

 

there is no noise

 

installed incorrectly.

of transformer under load at space connection on module with ON/OFF switch in ON

 

or spark.

 

 

position. Acceptable readings of a good transformer are between 3.2 and 2.8 volts AC.

 

 

 

 

 

 

 

b.

A shorted or loose

Remove and install the wiring harness that plugs into module. Verify there is a tight fit.

 

 

 

connection in wiring

Verify pilot assembly wiring to module. Remove and verify continuity of each wire in

 

 

 

configuration or wiring

wiring harness.

 

 

 

harness.

 

 

 

 

 

 

 

 

c.

Module not grounded.

Verify green ground wire from module wire harness is grounded to metal chassis of

 

 

 

 

appliance.

 

 

d.

No gas flow out of pilot

Check gas mains supply and pressure. Check gas valve wirings and connections to the

 

 

 

burner.

board. Check for pilot burner obstruction.

 

 

e.

No ionization current

Remove/clean eventual bridging carbon deposits betweeh the pilot burner and the

 

 

 

established through flame

ionization rod.

 

 

 

within ignition time.

 

 

 

 

 

 

 

 

f.

No gas flow out of pilot

Check gas mains supply and pressure. Check the correct gas type setting on the valve

 

 

 

burner or pilot gas presure

and pilot burner assembly orifice.

 

 

 

dropout upon main burner

 

 

 

 

gas valve opening.

 

 

 

 

 

 

 

 

g.

No spark generation.

Check parasitic pilot flame existence.

 

 

 

 

 

 

 

h.

No spark voltage reaches

Check for cracks in the rod ceramic insulator, replace as necessary. Check pilot

 

 

 

the spark rod, or spark

assembly wirings and spark return connections to the board.

 

 

 

developes near pilot

 

 

 

 

assembly.

 

 

 

 

 

 

64

Quadra-Fire • QFP38 Series • 4061-300 Rev i • 9/09

Image 64
Contents Installation and Operation ModelsHomeowner Reference Information CongratulationsModel Number Serial Number Table of Contents Appliance Setup = Contains updated informationLimited Lifetime Warranty Limited Lifetime Warranty Listing and Code Approvals Requirements for the Commonwealth of Massachusetts Operating Instructions Gas Fireplace SafetyYour Fireplace Fixed Glass Assembly Remote ControlsClear Space Decorative Doors and FrontsFan Control Module System DescriptionAUX Outlet Plug Accent Lighting Initializing the System for the First Time ReceiverPRG Key PIN terminal Positions Slider Transmitter Remote Control with LCD Display Operating Procedure with Split Flow dual burner control Turn on the Appliance Temperature Indication DisplayTurn off the Appliance Remote Flame Control 11 Remote Flame ControlRoom Thermostat Transmitter Option Smart Thermostat Transmitter OperationFan Speed Control Remote Actuated 120V Auxiliary Outlet accent lightingLow Battery Power Detection Manual Bypass of the Remote SystemRemote Operation Key LockFor Your Safety Read Before Lighting Lighting Instructions IPIFrequently Asked Questions Initial Break-in ProcedureAfter Fireplace is Lit This cures the materials used to manufacture the fire- placeMaintenance and Service Maintenance Tasks-HomeownerMaintenance Tasks-Qualified Service Technician Fan Replacement & Maintenance Bend Down TabRemove Wing nuts Both sides Getting Started Typical Appliance SystemTools and Supplies Needed Design and Installation ConsiderationsInspect Appliance and Components Framing and Clearances Select Appliance LocationConstruct the Appliance Chase ClearancesMantels Mantel and Wall ProjectionsMantel Legs or Wall Projections Vent Termination Minimum Clearances Termination LocationsGas, Wood or Fuel Oil Termination Cap Minimum Clearances for Termination Vent Information and Diagrams Approved PipeVent Table Key Use of ElbowsTop Vent Horizontal Termination Vent DiagramsOne Elbow Two 45 Elbows replacing One 90 Elbow Two ElbowsTop Vent Vertical Termination No ElbowVent Clearances and Framing Pipe Clearances to CombustiblesWall Penetration Framing Non-Combustible Wall PenetrationInstall the Ceiling Firestop Ceiling firestop Must be used between floors and atticsFlat Ceiling Installation Install Attic Insulation ShieldVaulted Ceiling Installation Appliance Preparation Intake Adapter AssemblySecure and Level the Appliance Install Vent Pipe Attach Pipe to the Firebox AssemblyAssemble Vent Sections Assemble Pipe SectionsAssemble Slip Sections Slip Section Pilot HolesSecure the Vent Sections Disassemble Vent SectionsInstall Metal Roof Flashing CaulkAssemble and Install Storm Collar 13 Assembling the Storm CollarInstall Vertical Termination Cap Heat Shield Requirements for Horizontal TerminationInstall Horizontal Termination Cap Failure to maintain overlap may cause overheating and fireShrouds HHT ShroudsField Constructed Shrouds Open Top Shroud may be used with DVP-TV, DVP-TVHW, SLP-TVHWMailbox Style Shroud Dimensions Min. Base Dims Gas Pressure Gas InformationGas Connection Wiring Requirements Technical DataIntellifire Ignition System Wiring Electrical InformationIPI Module 4 from Sleeve Install the Heat Zone Kit before enclosing the appliance Junction Box InstallationHeat-Zone-Gas Facing Material Finishing43 3/8 Doors Outside Surface Fit Facing Template RemovalDoors Recessed Fit Minimum Vertical and Maximum Horizontal Dimensions Appliance Setup Remove Fixed Glass AssemblyClean the Appliance Install the RefractoryInstall Logs, Ember Bed Log Bracket is Pre-set for NG or LPOverall placement of the first eight logs is shown in Figure Install Andirons, Lava Rock, Rockwool Complete Log InstallationAccent Lighting Set Up ScrewsAdjust the Air Shutter Adjust the Vertical BaffleRemoving Fixed Glass Assembly Install Door FrontsReplacing Fixed Glass Assembly Troubleshooting TroubleshootingThis Opening Appliance Dimension Diagram Reference MaterialsVent Components Diagrams DVP Vent ComponentsDVP-TRAPFL DVP-HPC DVP-TRAP Service Parts QFP38-NG, QFP38-LPStocked Log Set Assembly Log 1 Back Log 4061-170 Ember BedAt Depot Light Assembly Valve Assembly Valve Assembly NG Optional Components Quadra-Fire, a brand of Hearth & Home Technologies Inc Contact Information7571 215th Street West, Lakeville, MN

QFP38-NG, QFP38-LP specifications

The Quadra-Fire QFP38-NG and QFP38-LP are high-performance gas fireplaces designed to deliver both warmth and aesthetic appeal to homes. These models are known for their advanced features, reliable technologies, and user-friendly characteristics, making them ideal choices for homeowners looking to enhance their living spaces.

One of the key features of the QFP38 series is its efficient heating capability. With impressive BTU output, both the QFP38-NG (natural gas) and QFP38-LP (liquid propane) models provide ample warmth, making them suitable for various room sizes. They utilize a powerful burner system that maximizes combustion efficiency, thereby delivering consistent heat while minimizing fuel consumption.

The QFP38 series is designed with a contemporary and elegant appearance, featuring a large viewing area that showcases the mesmerizing flame. The clean, modern lines and glass front make it an eye-catching centerpiece in any room. Additionally, these fireplaces come with customizable options, allowing homeowners to choose from different interior styles, including log sets and decorative fire glass, to match their decor preferences.

Another standout technology in these models is the advanced control system. The QFP38 series is compatible with remote control operation, enabling users to adjust the flames and heat settings from the comfort of their seating area. This feature enhances convenience, allowing homeowners to set the desired ambiance and warmth with ease.

Safety is a paramount concern, and the QFP38 fireplaces are equipped with several safety features. These include a built-in oxygen depletion sensor that automatically shuts off the gas supply in case of insufficient oxygen levels. Additionally, the sealed combustion design prevents indoor air contamination, providing peace of mind to users.

The installation process of the QFP38-NG and QFP38-LP is straightforward, thanks to their venting options that accommodate various home layouts. Both models are designed to be versatile, with horizontal and vertical venting capabilities, offering greater flexibility for installation.

In terms of maintenance, the QFP38 series is user-friendly, requiring minimal upkeep to ensure optimal performance. Regular cleaning and inspection of the glass and burner components are typically all that is needed to maintain the fireplace's efficiency and aesthetic appeal.

Overall, the Quadra-Fire QFP38-NG and QFP38-LP gas fireplaces combine cutting-edge technology, modern design, and safety features, making them excellent options for anyone looking to add warmth and style to their home. Whether used as a primary heat source or as an elegant focal point, these models are sure to enhance any living space.