Napoleon Fireplaces GD19N, GD19P manual Top Exit / Horizontal Termination

Page 11
Manual background

11

TOP EXIT / HORIZONTAL TERMINATION

 

 

(HT) > (VT)

 

 

 

Example 2:

 

 

 

 

 

 

FIGURE 9

 

V1

= VT

= 6 ft

 

 

 

 

 

 

 

H1

= 3 ft

 

 

 

 

 

 

 

 

H2

= 5 ft

 

 

 

 

 

 

 

 

HR

= H1

+ H2 = 3 + 5 = 8 ft

Simple venting configuration

 

 

 

HO

= .03(two 90° elbows - 90°) = .03(180° - 90°) = 2.7 ft

 

 

 

HT

= HR + HO = 8 + 2.7 = 10.7 ft

(only one 90° elbow)

 

 

 

 

 

 

HT

+ VT= 10.7 + 6 =16.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Formula 1:

HT < 4.2 VT

 

 

 

 

 

 

 

 

 

 

4.2 VT = 4.2 x 6 = 25.2 ft

 

 

 

 

 

 

 

 

 

10.7 < 25.2

 

 

 

 

 

 

 

 

Formula 2:

HT + VT < 24.75 feet

 

 

 

 

 

 

 

 

 

16.7 < 24.75

 

 

 

 

 

 

 

 

Since both formulas are met, this vent configuration is

See graph to determine the required vertical rise VT for the

acceptable.

 

 

 

 

 

 

required horizontal run HT.

 

 

 

 

Example 3:

 

REQUIRED

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

140

 

 

 

 

 

 

 

 

 

VERTICAL

 

 

 

 

 

 

 

 

90°

RISE IN

130

 

 

 

 

 

 

 

 

INCHES VT

120

 

 

 

 

 

 

 

H1

H4

 

 

 

 

 

 

 

 

 

110

 

 

 

 

 

 

 

 

V2

 

100

 

 

 

 

 

 

 

 

H3

 

 

 

 

 

 

 

V1

90°

H2

 

90

 

 

 

 

 

 

FIGURE 11

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

V1

= 4 ft

 

 

30

 

 

 

 

 

 

 

 

 

 

 

 

V2

= 1.5 ft

 

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

VT

= V1 + V2 = 4 + 1.5 = 5.5 ft

 

10

 

 

 

 

 

H1

= 2 ft

 

 

 

0

5

10

15

20

H2

= 1 ft

 

 

 

H3

= 1 ft

 

HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT

 

H4

= 1.5 ft

 

 

 

 

 

 

 

 

HR

= H1 + H2 + H3 + H4

= 2 + 1 + 1 + 1. 5 = 5.5 ft

The shaded area within the lines represents acceptable

HO

= .03(four 90° elbows - 90°) = .03(360° - 90°) = 8.1 ft

values for HT and VT .

 

 

 

 

HT

= HR + HO = 5.5 + 8.1 = 13.6 ft

 

 

 

 

HT

+ VT = 13.6 + 5.5 = 19.1 ft

 

 

 

 

 

 

 

For vent configurations requiring more than one 90° elbow

Formula 1: HT < 4.2 VT

 

the following formulas apply:

 

 

 

 

 

 

4.2 VT = 4.2 x 5.5 = 23.1 ft

Formula 1: HT

< 4.2 VT

 

 

 

 

 

13.6 < 23.1

 

Formula 2: HT

+ VT < 24.75 feet

 

 

Formula 2: HT + VT < 24.75 feet

 

 

 

H1

 

 

 

 

 

19.1 < 24.75

 

FIGURE10

 

 

 

H2

 

Since both formulas are met, this vent configuration is

 

 

 

 

 

 

 

 

 

 

 

 

 

acceptable.

 

 

 

V1

 

90°

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W415-0612 / C / 01.25.08

Image 11
Contents GD19P INSTALLATION AND OPERATION INSTRUCTIONSSAFETY INFORMATION GD19NRETAIN THIS MANUAL FOR FUTURE REFERENCE TABLE of CONTENTSCONDITIONS AND LIMITATIONS CARE OF GLASS AND PLATED PARTS GENERAL INSTRUCTIONSGENERAL INFORMATION VENTING FOR SPECIFIC VENTING PARAMETERS, REFER TO PAGES VENT INSTALLATIONSHORIZONTAL VENT SECTIONS VERTICAL VENT SECTIONSTOP EXIT TYPICAL VENT INSTALLATIONSSPECIAL VENT INSTALLATIONS REAR EXITW415-0612 /C MINIMUM AIR TERMINAL LOCATION CLEARANCESTOP EXIT VENTING APPLICATION FLOW CHARTFIREPLACE VENT EXIT REAR EXITHT VT TOP EXIT / HORIZONTAL TERMINATIONDEFINITIONS ELBOW VENT LENGTH VALUESTOP EXIT / HORIZONTAL TERMINATION HT VT REAR EXIT / HORIZONTAL TERMINATIONH2 REAR EXIT / HORIZONTAL TERMINATION HT VT TOP OR REAR EXIT VERTICAL TERMINATIONHT VT TOP EXIT CONVERSION 3/4” INSTALLATION WALL AND CEILING PROTECTIONHORIZONTAL INSTALLATION VERTICAL INSTALLATIONVERTICAL AIR TERMINAL INSTALLATION USING FLEXIBLE VENT COMPONENTSHORIZONTAL AIR TERMINAL INSTALLATION FIREPLACE VENT CONNECTION EXTENDED HORIZONTAL AND CORNER VERTICAL VENTING INSTALLATIONAIR TERMINAL INSTALLATION RESTRICTING VERTICAL VENTSOPTIONAL WALL SWITCH INSTALLATION MOBILE HOME INSTALLATIONGAS INSTALLATION ELECTRICAL INSTALLATIONCombustible Framing 0 to stand-offs FRAMINGREAR VENT TOP VENTFIGURES 41a&b MINIMUM MANTEL AND ENCLOSURE CLEARANCESFIREBOX FRONT FACING AND INSET KIT INSTALLATIONLENS ASSEMBLY INSTALLATION BLOWER INSTALLATIONNIGHT LIGHT REPLACEMENT BULB REPLACEMENTLOG PLACEMENT FINISHINGGLASS DOOR INSTALLATION AND REMOVAL DOOR GLASS REPLACEMENTNIGHT LIGHTTM SWITCH LOGO PLACEMENTMAIN BURNER SWITCH FLAME ADJUSTMENTSee detail for optional wall switch GD-660wiring WIRING DIAGRAMOPERATING INSTRUCTIONS OPERATION / MAINTENANCEMAINTENANCE FOR YOUR SAFETY READ BEFORE OPERATINGFLAME ADJUSTMENT ADJUSTMENTSPILOT INJECTOR AND ORIFICE REPLACEMENT VENTURI ADJUSTMENTFOR WARRANTY REPLACEMENT PARTS, A PHOTOCOPY OF REPLACEMENTSREPLACEMENT PARTS ACCESSORIESW415-0612 /C TEST SOLUTION TROUBLE SHOOTING GUIDESYMPTOM PROBLEMPilot lights SYMPTOMPROBLEM TEST SOLUTIONW415-0612 /C Fireplace Service Historyserviced annually depending on usage This fireplace must beW415-0612 /C