Napoleon Fireplaces GD80PT, GD80NT manual V190

Page 8

8

TOP EXIT / HORIZONTAL TERMINATION

when (HT) > (VT)

Simple venting configuration (only one 90° elbow)

FIGURE 6

See graph to determine the required verti- cal rise VT for the required horizontal run HT.

Example 3:

V1

 

 

90°

 

 

 

 

 

 

H4

 

H1

 

 

 

 

V2

 

 

H2

 

 

H3

90°

 

 

 

 

 

 

FIGURE 8

REQUIRED

VERTICAL

RISE IN

INCHES

VT

HORIZONTAL VENT RUN PLUS OFFSET IN FEET HT

The shaded area within the lines represents acceptable values for HT and VT .

For vent configurations requiring more than one 90° elbow the following formulas apply:

V1

= 4 ft

V2

= 1.5 ft

VT

= V1 + V2 = 4 + 1.5 = 5.5 ft

H1

= 2 ft

H2

= 1 ft

H3

= 1 ft

H4

= 1.5 ft

HR

= H1 + H2 + H3 + H4 = 2 + 1 + 1 + 1. 5 = 5.5 ft

HO

= .03(four 90° elbows - 90°) = .03(360° - 90°) = 8.1 ft

HT

= HR + HO = 5.5 + 8.1 = 13.6 ft

HT + VT

= 13.6 + 5.5 = 19.1 ft

Formula 1: HT < 4.2 VT

4.2 VT = 4.2 x 5.5 = 23.1 ft 13.6 < 23.1

Formula 2: HT + VT < 24.75 feet

19.1 < 24.75

Formula 1: HT < 4.2 VT

Formula 2: HT + VT < 24.75 feet Example 2:

V190°

H1

H2

FIGURE 7

Since both formulas are met, this vent configuration is acceptable.

V1

= VT = 6 ft

 

H1

= 3 ft

 

H2

= 5 ft

 

HR

= H1 + H2

= 3 + 5 = 8 ft

HO

= .03(two 90° elbows - 90°) = .03(180° - 90°) = 2.7 ft

HT

= HR + HO = 8 + 2.7 = 10.7 ft

HT + VT = 10.7 + 6 =16.7

Formula 1: HT < 4.2 VT

4.2VT = 4.2 x 6 = 25.2 ft

10.7< 25.2

Formula 2: HT + VT < 24.75 feet 16.7 < 24.75

Since both formulas are met, this vent configuration is ac- ceptable.

W415-0447 / B / 05.24.05

Image 8
Contents W415-0447 / B What to do if YOU Smell GAS Table of Contents Napoleon GAS Fireplace Presidents Lifetime Limited Warranty General Instructions General InformationVenting Lengths & AIR Terminal Locations VentingCare of GLASS, and Plated Parts Elbow Vent Length Values TOP Exit / Horizontal TerminationDefinitions V190 TOP Exit Vertical Termination TOP Vertical Termination Formula 1 HT 3VT Formula 2 HT + VT 40 feet ExampleAIR Terminal Installations Vertical Installation Installation Wall and Ceiling ProtectionHorizontal Installation Vertical AIR Terminal Installation Using Flexible Vent ComponentsHorizontal AIR Terminal Installation Fireplace Vent Connection Using Rigid Vent ComponentsExtended Horizontal AIR Terminal Installation Vertical Venting Installation GAS Installation Restricting Vertical VentsFraming Clearance to CombustiblesHard Wiring Connection SchematicElectrical Connection Mantle ClearancesFinishing LOG Shipping BracketLOG Placement Baffle InstallationGlowing Embers Charcoal EmbersBlower Replacement Lamp ReplacementRemote and Valve Access Inner Access DoorControl Door Remote Receiver RemovalHand Held Remote Operation Operation / MaintenanceFireplace Operation Operating Instructions Adjustments MaintenancePilot Burner Adjustment Venturi AdjustmentReplacements W415-0447 / B Trouble Shooting Guide Symptom Problem Test SolutionStanding Main