Jotul GF 400 DV manual Fuel Conversion Procedure, #33 for NG Mm for LPG, Burner Plate

Page 17

Fuel Conversion Procedure

Refer to fig. 47, Illustrated Parts Breakdown, to identify part numbers below.

1.Turn off gas supply to stove.

2.Remove the stove Top Plate (41).

3.Disengage the two Glass Frame Latches at the top of the firebox. See illustration on page 5. Carefully lift the glass panel up and out of the stove.

4.If installed, remove the Embers and Log Set using care not to damage the fragile log parts.

5.Lift out the Burner Skirt (33). Tilt the skirt at an angle to clear the firebox sides and front.

6.Reach under the stove and remove the Air Shutter wingnut from its stud. As you face the right side, it is the one closest to you. See fig. 21.

7.Lift out the Burner Plate: NOTE: There are no screws securing the Burner to the floor of the firebox. Pull the Air Shutter forward and lift the burner together with shutter up and out of the stove as a unit. See fig. 22.

8.Change the Main Burner Orifice. See fig. 23. Using a ½” open ended wrench or deep-well socket remove the burner orifice from its brass elbow housing and replace with the appropriate orifice supplied in the kit.

#33 for NG

1.65mm for LPG

9.Replace the Air Shutter with its gasket and push it all the way back to allow replacement of the Burner Plate.

10.Replace the Burner Plate. Engage the Air Inlet Tube with the Air Shutter and burner orifice. Properly seated, the burner plate will be engaged at its front corners with the two support brackets located at the front of the firebox.

Replace the wingnut loosely on the air shutter stem under the stove. Air shutter adjustment will be done last.

11.CHANGE THE PILOT ORIFICE: From within the firebox, remove the Pilot Head by pulling it straight up from the pilot base. See fig. 25.

Using the 4 mm allen wrench that is included with the conversion kit, unscrew the pilot orifice (counter- clockwise). Replace with the appropriate orifice:

# 51 for natural gas #30 for propane gas

12.Tighten orifice into the base of the pilot assembly. To prevent bypass leaks, be sure the orifice is secured tightly and flush with the base. Replace pilot head by pushing it down onto the pilot base.

13.Replace the Variable Regulator. Using a Torx T-20 screwdriver, remove the three screws from the front of the valve regulator. See fig. 26.

Air

 

 

Shutter

Open

 

Wingnut

Close

 

FRONT

BACK

LEG

LEG

 

Figure 21. Locate and remove the Air Shutter wingnut from under the right side of the stove.

Air Shutter

Burner Plate

Figure 22. Remove the Air Shutter and Burner as a unit.

Brass Elbow

Burner

Orifice

Figure 23. Change the Burner Orifice.

Air Shutter

Air Inlet

Tube

Opening

Dimension

Burner Plate

Figure 24. Air Shutter Setting

17

Image 17
Contents Jøtul GF 400 DV Sebago Gas Heater Welcome to Jøtul Jøtul GF 400 DV Sebago Direct Vent Gas Heater Table of ContentsInput Rates GF 400 DV Sebago SpecificationsSuggested Tools for Installation and Service Glass Panel Hardware Bag ContentsUnpacking your stove Hearth Requirements Safety InformationLocation Minimum Clearances from the Vent Pipe to Combustibles Alcove InstallationHorizontal Run Vertical RunVent Restriction Venting RequirementsIntake Air Restrictor Exhaust Restrictor„ Minimum Vertical run must be at least 8 ft .43 m Vertical Vent TerminationFront LEG Back Vertical Termination for Vent Termination Zones Natural GasVenting Must Terminate END Within the Shaded Area Vent Termination Zones PropaneThese installation requirements must be followed Co-linear Vent InstallationMasonry or Prefabricated Chimney Conversion Snorkel Terminations Horizontal Termination„ With a 14 Snorkel „ With a 36 SnorkelMin inches, U.S. / *12 inches 30 cm can Horizontal Termination ClearanceConversion Kit Contents Mobile Home InstallationTools required Regulator tower labeled for propane Regulator tower screws#33 for NG Mm for LPG Fuel Conversion ProcedureBurner Plate Brass Elbow Burner OrificeNever USE AN Open Flame to Check for GAS Leaks Adjust the Air ShutterGas Supply Connection Gas Pressure High Altitude AdjustmentLeak test Always Test Pressures with Valve Control Knob SET on HighOptional Wall Thermostat or Remote Control Flame Appearance / Air Shutter AdjustmentRemote Control FrontInstall Right Log Log Set InstallationProper pilot flame appearance System CheckLighting of the appliance. This fog will disappear as OperationGlass Care Annual CleaningVent System Burner and LogsetShort phillips screwdriver Connect power cord to outletBlower Operation Wingscrew Snapstat Connectors Male QuickconnectorBlocking the Pilot Assembly Opening Install the Rear PanelReplace the Glass Frame Replace the Top PlateGF 400 DV Sebago Illustrated Parts Breakdown GF 400 DV Sebago Parts List Serial Number Name of InstallerDate of Purchase Purchased fromPush in gas control knob slightly and turn clockwise toOFF What to do if YOU Smell GASControl Valve Jøtul AS November 2005 137750-EBox Fredrikstad Norway Jøtul North America

GF 400 DV specifications

The Jotul GF 400 DV is a highly sought-after gas stove, known for its excellent efficiency and stylish design. This innovative heating solution combines traditional aesthetics with modern technology to create a product that is not only functional but also enhances any living space.

One of the standout features of the Jotul GF 400 DV is its elegant cast iron construction. The durability of cast iron ensures that the stove retains heat longer, providing warmth even after the fire goes out. The design incorporates a large viewing window that allows for an unparalleled view of the flames, fostering a cozy atmosphere. The stove is available in several finishes, including classic black, which complements a variety of home decors.

Efficiency is a key characteristic of the GF 400 DV, as it is designed to achieve a high thermal efficiency rating. It utilizes direct venting technology, allowing for easy installation and efficient combustion. This technology facilitates the venting of exhaust gases outside the home, ensuring indoor air quality remains pristine. The adjustable heat output allows users to customize the warmth according to their needs.

Another impressive feature of the Jotul GF 400 DV is the inclusion of a variable flame adjustment system. This system enables users to control the intensity of the flames, providing both ambiance and practicality. The stove can produce up to 25,000 BTUs, making it suitable for heating medium to large spaces, with an estimated heating area of around 800 to 1,500 square feet.

The GF 400 DV is equipped with electronic ignition for hassle-free startup. Additionally, it features a remote control option, allowing users to operate the stove conveniently from a distance. The manual control option is also available for those who prefer a more traditional experience.

In terms of safety, the stove comes with built-in safety measures, including a flame failure device that automatically shuts off the gas supply if the flame goes out unexpectedly.

Overall, the Jotul GF 400 DV gas stove represents the perfect blend of traditional craftsmanship and modern efficiency. Its combination of aesthetics, innovative features, and practical heating capabilities makes it an ideal choice for homeowners looking to add warmth and character to their living spaces. Whether you’re enjoying a quiet evening at home or entertaining guests, this stove is sure to impress with its performance and beauty.