Lennox International Inc G32Q4-100, G32Q3-100, G32Q5-125, G32Q5-100, G32Q3-75 Wallringkit, Topview

Page 11

On roof terminations, the intake piping should termi- nate straight down using two 90° elbows. See figure 8.

NOTE - If winter design temperature is below 32°F (O°C), exhaust piping must be insulated with 1/2 inch (13 mm) Armaflex or equivalent when run through unheated space. Do not leave any surface area of exhaust pipe open to outside air," exterior exhaust pipe must be insu- lated with 1/2 inch (13 ram) Armaflex or equivalent. In ex- treme cold climate areas, 3/4 inch (19 mm) Armaflex or equivalent is recommended. Insulation on outside runs of

exhaust pipe must be painted or wrapped to protect in- sulation from deterioration.

NOTE - During extremely cold temperatures, below approximately 20°F (6.67°C), units with long runs of vent pipe through unconditioned space, even when insulated, may form ice in the exhaust termination that prevents the unit from operating properly. Longer run times of at least 5 minutes will alleviate most icing problems. Also, a heating cable may be installed on exhaust piping and termination to prevent freeze-ups. Heating cable installation kit is available from Lennox. See Condensate Piping section for part numbers.

NOTE - Care must be taken to avoid recirculation of ex- haust back into intake pipe.

6 - On field-supplied terminations for side wall exits, ex- haust piping should extend a maximum of 12 inches (305 mm) beyond the outside wall. Intake piping should be as short as possible. See figure 10.

 

IMAX.

Inches (ram)

3 x 2 (70 x 51) OR

 

2 x %1/2 (51 x 38)

 

PVC REDUCER

 

1/2 (13) FOAM

 

INSULATION IN

 

UNCONDrrlONED

12 (305) ABOVE

SPACE

ACCUMULATION

 

AVERAGE SNOW

 

3 (76) OR

UNCONDmONED

2 (5t) PVC

ATTIC SPACE

PROVIDE SUPPORT

 

FOR INTAKE AND

 

F.XHAUST LINES

 

ROOFTERMINATION KIT

(15F'75)LB-49107CCfor 2 (5t) Venting (44341)LB-65678Afor 3 (76)Venting

FIGURE 8

EXHAUST

12 (305) ABOVE

AVERAGE SNOW ACCUMULATION

INTAKE

TERMINATION

Inches (mm)

EXHAUSTINTAKE

CONCENTRIC ROOFTOP TERMINATION (60G77) LB-49107CE for G32-75 Units Only (33K97) LB-87942 for G32-100 & -125 Units Only

 

 

FIGURE

9

1/2 (13) ARMAFLEX

12 (305) MIN.

INSULATION

IN

 

 

UNCONDITIONED

SPACE

 

2 X 1-1/2

 

 

 

 

 

 

(51 X 38)

 

 

PV

REDUCER

 

 

_ _

'VC

1/2 (13) ARMAFLEX t' I

6 (I 52)

INSULATION

 

MAXIMUM

 

 

_

2 (_ I PVC

OUTSIDE j

 

PLING

WALL

 

 

 

Inches (ram)

 

TOPVIEW

 

WALLRINGKIT

(15J74) LB-49107CBfor2 (50,8 ! Venting

FIGURE 10

7- On field-supplied terminations, a minimum separa- tion distance between the end of the exhaust pipe and the end of the intake pipe is 8 inches (203 mm).

8- If intake and exhaust piping must be run up a side wall to position above snow accumulation or other obstructions, the piping must be supported every 3 feet (.91 m) as shown in figure 15. Refer to figures 13 and 14 for proper piping method. W'FKwall termina- tion kit must be extended for use in this application, See figure 18 or use kit WTKX shown in figure 19.

When exhaust and intake piping must be run up an outside wall, the exhaust piping is reduced to 1-1/2

inches (38 mm) after the final elbow. The intake pip- ing may be equipped with a 90°elbow turndown. Us- ing 90 ° turndown will add 5 feet (1.5 m) to the equiva- lent length of the pipe.

Page 11

Image 11
Contents Lennox AIR Outlet TOP ViewDoor Interlock Switch AssemblyAccess Panel AIR AccessInches mrn Shipping Damage Insta!iatton Setttng EquipmentKnockout Pattern for Bottom Return AIR Application Bottom Return Filter InstallationSide Return Filter Installation in.turn Bottom Return Air ApplicationsSupply Air Plenum Filter Door AssemblyPiping and Fittings Specifications BTU Termination KitsG32-100 or -125 with 3 IN. Venting OUTIventingractl es Pipe Resized to approach the minimum size as deterTopview WallringkitWall Ringtermination OutsidewallWall Termination Exhaust Termination IntakeExhaarus Front View ExhaustFront View ,, l/EXHAUST Vent Side ViewFor Right-Hand Side Condensate Exit Nipplebootorcap AdapterUse the provided condensate drain adapter 3/4 Right Side Piping Condensate PlumbingGroundjoint type Left Side PipingGAS Pipe Capacity ft.3/hr Im31hrl Connections factory- and field-installed for gas leaksPrecautions and Procedures Electrostatic Discharge ESDG32Q and Condensing Unit Interior MAKE-UP BOX InstallationExterior MAKE-UP BOX Installation Hole in the cabinet. a snaphole plug is providedtoSurelight Integrated Control Board G32Q Control BOXG32Q TWO-STAGE Control Board Typical G32Q Field Wiring DiagramTypical G32Q Schematic Wiring Diagram GAS Valve Shown in OFF Position For Your Safety Read Before OperatingHoneywell VR8205 Series GAS Valve Turn gas valve knob to on positionOperation sequence followssteps 1 through4 as out KBtuhDIFFERENTIALPRESSURESWITCHCIRCUITRY Manifold Pressure Measurement & AdjustmentBlower Speeds Temperature RiseAnnual Service 275F 135C Cleaning DuralokPlus TM Heat ExchangerBushing.Reconnect wires Reinstallthe screws to secure the burner box cover Cleaning the Bumer AssemblySimultaneous CabinetBlower Parts Heating PartsOperation Normal Heating ModeAbnormal Heating Mode Heating SequenceGAS Valve OFF. Combustion AIR Normal Heating Mode AbnormalIndoor Blower on Delay Begins Flame SignalCombustion AIR Inducer on for 2.5 Minutes High Heat GAS Valve OPEN? 8 SEC. DelayPressure Switch Watchguard Combustion AIR Inducer IprepurgeGPRRoOuPNEDRELYI Normal Cooling Mode Abnormal Cooling ModeTH Ermostat InstallerJob Number Heating Section