Bryant 345MAV instruction manual ÐCombustion-Air Inlet Pipe Assembly

Page 24

FIELD-SUPPLIED

 

2-IN. DIAMETER

FIELD-SUPPLIED

PVC 90°ELBOW

2-IN. DIAMETER

 

 

 

 

 

 

PVC PIPE

 

 

 

 

 

 

 

 

 

 

 

 

A

COMBUSTION-AIR DISC (FACTORY-SUPPLIED IN

NOT IN HORIZONTAL SECTION

FURNACE

PIPE DIAMETER

TRANSITION IN

VERTICAL SECTION

A93034

LOOSE PARTS BAG)

A96211

LENGTH OF STRAIGHT PIPE PORTION OF

COMBUSTION-AIR INLET PIPE ASSEMBLY (IN.)

CASING WIDTH

A

17-1/2

8-1/2 ± 1/2

21

10-1/2 ± 1/2

24-1/2

12 ± 1/2

 

 

Fig. 29ÐCombustion-Air Inlet Pipe Assembly

NOTE: Do not attach combustion-air intake pipe permanently to combustion-air intake housing since it may be necessary to remove pipe for service of ignitor or flame sensor.

The combustion-air intake plug fitting must be installed in unused combustion-air intake housing. This fitting must be attached by using RTV sealant, or by drilling a 1/8-in. hole in fitting, using hole in intake housing as a guide. Install a field-supplied No. 6 or No. 8 sheet metal screw.

NOTE: DO NOT OVERTIGHTEN SCREW. Breakage to intake housing or fitting may cause air leakage to occur.

A plugged drain connection has been provided on this fitting for use when moisture is found in combustion-air intake pipe and combustion box. If use of this drain connection is desired, drill out fitting's tap plug with a 3/16-in. drill and connect a field-supplied 3/8-in. tube. This tube should be routed to open condensate drain for furnace and A/C (if used), and should be trapped. (See Fig. 30.)

 

HOUSING

COMBUSTION–AIR

 

PLUG

 

INTAKE HOUSING

3/8ID TUBE

BURNER

 

 

BOX

3/16

 

 

DRILL

 

COMBUSTION–

 

 

 

 

AIR PIPE

 

4″￿

 

TRAP

MIN

 

 

 

TO OPEN

 

 

DRAIN

 

 

 

A96190

Fig. 31ÐVent Pipe Diameter Transition Location and

Elbow Configuration

Determine vent pipe diameter and maximum pipe lengths using Table 4.

Furnace vent pipe connection must be attached as shown in Fig.

28.Inducer housing alternate vent cap may need to be relocated in some applications.

NOTE: Starting at furnace, slope vent pipe a minimum of 1/4 in. per linear ft upward to termination(s) with no sags between hangers.

CAUTION: When vent pipe is exposed to temperatures below freezing, such as when it passes through an unheated space or when a chimney is used as a raceway, pipe must be insulated as described in Table 5 with Armaflex-type insulation.

WARNING: Vent pipes must be airtight and watertight. Failure to follow this warning could result in property damage, personal injury, or death.

NOTE: The minimum vent pipe length for these furnaces is 5 ft. Short pipe lengths (5-8 ft) may discharge water droplets. These droplets may be undesirable, and a 12-in. minimum offset pipe section is recommended to reduce excessive droplets from exiting vent pipe outlet. (See Fig. 32.)

NOTE: Do not count elbows or pipe sections in terminations or within furnace. See shaded areas in Fig. 34.

EXAMPLE:

An 036080 size furnace located in Indianapolis, eleva- tion 650 ft above sea level, could be installed in an application requiring 3 elbows and 32 ft of vent pipe. Table 4 indicates this application would allow a 2-in. diameter vent pipe. At 0-2000 ft elevation, 2-in. pipe is good for up to 35 ft with 3 elbows. If same installation were in Albuquerque, elevation 5250 ft above sea level, installation would require 2-1/2 in. vent pipe. At 5001- to 6000-ft elevation, 2-in. pipe is allowed for up to 23 ft with 3 elbows, but 2-1/2 in. pipe can be used for up to 70 ft with 3 elbows.

Fig. 30ÐIntake Housing Plug Fitting Drain

C.Vent Pipe

NOTE: Furnace vent pipe connections are sized for 2-in. pipe. Any vent pipe size change should be made outside furnace casing in vertical pipe. (See Fig. 31.) This allows proper drainage of vent condensate.

Install vent pipe as follows:

1.Determine location of vent pipe connection to inducer housing as shown in Fig. 28 for application.

2. Reposition elastomeric (rubber) inducer housing outlet cap and clamp to appropriate unused inducer housing connec- tion. Tighten clamp.

Ð24Ð

Image 24
Contents Electrostatic Discharge ESD Precautions Ð1ÐDimensions → ÐDimensional DrawingÐ2Ð Unit SizeSafety Considerations Electrostatic Discharge ESD PrecautionsMinimum Inches Clearance to Combustible Construction → ÐClearances to CombustiblesIntroduction Applications GeneralII. Upflow Applications Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow OrientationPressure Switch Tubing Ð6ÐCondensate Trap Field Drain Attachment Condensate Trap Freeze Protection III. Downflow ApplicationsCondensate Trap Location Condensate Trap TubingIV. Horizontal Left SUPPLY-AIR Discharge Applications Ð8ÐHorizontal Right SUPPLY-AIR Discharge Applications Construct a Working PlatformÐ9Ð ÐAttic Location and Working Platform Front Upflow or Downflow Horizontal II. Furnace Location Relative to Cooling Equipment III. Hazardous Locations AIR for Combustion and Ventilation GeneralII. Unconfined Space III. Confined SpaceInstallation Leveling Legs if Desired Combustion AIR from Outdoors Through Vertical DuctsCombustion AIR from Outdoors Through Horizontal Ducts II. Installation on a Concrete Slab Opening DimensionsFurnace Casing Width IV. Installation in Horizontal Applications AIR DuctsGeneral Requirements Ductwork acoustical treatmentReturn Air Connections VI. Filter ArrangementÐfilter Information VII. Bottom Closure PanelVIII. GAS Piping 171⁄2-IN. Wide Casings onlyÐmaximum Capacity of Pipe CU FT PER HR Electrical ConnectionsNominal Length of Pipe FT Iron Internal Diameter Size Wiring Length FT³ CKT BKR Amps PhaseÐelectrical Data Amps SizeÐWiring Diagram II -V Wiring III. AccessoriesVenting Removal of Existing Furnaces from Common Vent SystemsII. COMBUSTION-AIR and Vent Piping GeneralCombustion Air Pipe ÐCombustion-Air Inlet Pipe Assembly Ðmaximum Allowable Vent Pipe Length FT 3001 to4001 to 5000² Ðmaximum Allowable Vent Pipe Length FT 5001 to 6000²6001 to 7000² 7001 to 8000²ÐShort Vent 5 to 8 Ft System 9001 to 10,000²Vent Extension Pipe 040 060 080 100 120III. Vent Termination IV. MultiventingCondensate Drain General Ðvent Pipe Termination ClearancesÐRoof Termination Preferred Heating Mode II. Cooling ModeIII. Continuous Blower Mode IV. Heat Pump ModeSTART-UP Procedures General Component TestComponent Test Sequence II. Prime Condensate Trap with Water→ ÐInducer Housing Drain Tube IV. AdjustmentsIII. Purge GAS Lines Set Gas Input RateBTU/CU FT AltitudeOnly 40015000 Only 50017001 7758000 Only 8001Ðaltitude Derate Multiplier for U.S.A ExampleAltitude Derate Multiplier Factor for U.S.A Set Temperature Rise Blower Off Delay Heat ModeÐgas Rate CU FT/HR ±SPEED SelectorCheck Safety Controls Check Primary Limit Control II. Check Pressure SwitchChecklist Checklistðinstallation CHECKLISTÐSTART-UPLoad Calculation Vent Piping
Related manuals
Manual 12 pages 26.52 Kb Manual 12 pages 34 Kb

345MAV specifications

The Bryant 345MAV is a premier choice in the realm of residential heating and cooling systems, encapsulating advanced technologies, high efficiency, and remarkable performance. Designed for homeowners seeking reliability and comfort, this model exemplifies modern HVAC (Heating, Ventilation, and Air Conditioning) innovations.

One standout feature of the Bryant 345MAV is its impressive energy efficiency. With a high SEER (Seasonal Energy Efficiency Ratio) rating, it operates at peak levels while consuming less energy. This not only reduces utility bills but also supports environmental sustainability, making it an ideal selection for eco-conscious consumers. The model employs variable-speed technology, which allows the system to adjust its output based on current heating and cooling needs. As a result, it provides consistent indoor comfort while minimizing temperature fluctuations.

The Bryant 345MAV incorporates advanced refrigerant technologies designed for optimal performance. It uses R-410A refrigerant, which is known for its lower environmental impact compared to traditional refrigerants like R-22. This environmentally friendly aspect aligns with regulations aimed at reducing ozone depletion, thereby promoting a greener approach to heating and cooling.

Reliability is another hallmark of the Bryant 345MAV. Engineered with precision, this model features a durable build designed to withstand varying weather conditions. The system is equipped with a robust compressor that is engineered for longevity and minimal noise during operation. Homeowners will appreciate the quiet performance of the 345MAV, ensuring peace in their living spaces.

Comfort also extends to the user experience with the inclusion of a smart thermostat option. This integration allows homeowners to manage their heating and cooling systems remotely, enhancing convenience and control. Programmable settings can optimize energy use based on individual schedules, facilitating both comfort and savings.

In summary, the Bryant 345MAV is a top-tier solution for residential climate control, blending energy efficiency, innovative technology, and unmatched reliability. With its variable-speed operation, environmentally friendly refrigerant, and smart features, the 345MAV represents a significant advancement in the HVAC field. Homeowners investing in this model can expect a system that not only meets their heating and cooling needs but exceeds them in terms of efficiency and comfort.