Bryant 345MAV instruction manual Ðgas Rate CU FT/HR, Set Temperature Rise, ±SPEED Selector

Page 38

c.Measure time (in sec) for gas meter test dial to complete 1 revolution.

d.Refer to Table 9 for cu ft of gas per hr.

e.Multiply gas rate (cu ft/hr) X heating value (Btu/cu ft) using natural gas heating value from local gas utility/supplier.

TABLE 9ÐGAS RATE (CU FT/HR)

SECONDS

SIZE OF TEST DIAL

SECONDS

SIZE OF TEST DIAL

FOR 1

1

2

5

FOR 1

1

2

5

REVOLUTION

cu ft

cu ft

cu ft

REVOLUTION

cu ft

cu ft

cu ft

10

360

720

1800

50

72

144

360

11

327

655

1636

51

71

141

355

12

300

600

1500

52

69

138

346

13

277

555

1385

53

68

136

340

14

257

514

1286

54

67

133

333

15

240

480

1200

55

65

131

327

16

225

450

1125

56

64

129

321

17

212

424

1059

57

63

126

316

18

200

400

1000

58

62

124

310

19

189

379

947

59

61

122

305

20

180

360

900

60

60

120

300

21

171

343

857

62

58

116

290

22

164

327

818

64

56

112

281

23

157

313

783

66

54

109

273

24

150

300

750

68

53

106

265

25

144

288

720

70

51

103

257

26

138

277

692

72

50

100

250

27

133

267

667

74

48

97

243

28

129

257

643

76

47

95

237

29

124

248

621

78

46

92

231

30

120

240

600

80

45

90

225

31

116

232

581

82

44

88

220

32

113

225

563

84

43

86

214

33

109

218

545

86

42

84

209

34

106

212

529

88

41

82

205

35

103

206

514

90

40

80

200

36

100

200

500

92

39

78

196

37

97

195

486

94

38

76

192

38

95

189

474

96

38

75

188

39

92

185

462

98

37

74

184

40

90

180

450

100

36

72

180

41

88

176

439

102

35

71

178

42

86

172

429

104

35

69

173

43

84

167

419

106

34

68

170

44

82

164

409

108

33

67

167

45

80

160

400

110

33

65

164

46

78

157

391

112

32

64

161

47

76

153

383

116

31

62

155

48

75

150

375

120

30

60

150

49

73

147

367

 

 

 

 

EXAMPLE:

Btu heating input = Btu/cu ft X cu ft/hr Heating value of gas = 975 Btu/cu ft

Time for 1 revolution of 2-cu ft dial = 70 sec Gas rate = 103 cu ft/hr (from Table 9)

Btu heating input = 103 X 975 = 100,425 Btuh

In this example, the orifice size and manifold pressure adjustment is within ±2 percent of the furnace input rate.

B.Set Temperature Rise

CAUTION: Temperature rise must be within limits specified on unit rating plate. Recommended operation is at midpoint of rise or above. Failure to follow this caution may result in condensing or overheating the heat ex- changers.

Determine and adjust air temperature rise as follows:

1.Place thermometers in return and supply ducts as close to furnace as possible. Be sure thermometers do not see heat exchanger so that radiant heat does not affect readings. This practice is particularly important with straight-run ducts.

Ð38Ð

2.When thermometer readings stabilize, subtract return-air temperature from supply-air temperature to determine air temperature rise.

3.Adjust temperature rise by adjusting blower speed. Increase blower speed to reduce temperature rise. Decrease blower speed to increase temperature rise.

WARNING: Disconnect 115-v electrical power before changing speed tap. Failure to follow this warning could result in personal injury.

4.To change blower motor speed selections for heating mode, remove blower motor lead from control center HEAT terminal. (See Fig. 27.) Select desired blower motor speed lead from 1 of the other terminals and relocate it to HEAT terminal. See Table 10 for lead color identification. Recon- nect original lead on SPARE terminal.

Follow this same procedure for proper COOL speed selec- tion.

TABLE 10±SPEED SELECTOR

 

 

FACTORY-

COLOR

SPEED

SHIPPED

 

 

CONNECTION

Black

High

Cool

Yellow (When Present)

Medium High

Spare

Blue

Medium Low

Heat

Red

Low

Spare

White

Common

Com

C.Blower Off Delay (Heat Mode)

The main blower off time delay period is factory-set at 135 sec and is not field-adjustable.

D.Set Thermostat Heat Anticipator

Thermostat heat anticipator must be set to match amp draw of components in R-W circuit. Accurate amp draw measurements can be obtained at thermostat subbase terminals R and W.

Fig. 42 illustrates an easy method of obtaining these measure- ments. Amp reading should be taken after blower motor has started. See thermostat manufacturer's instructions for adjusting heat anticipator and for varying heating cycle length.

THERMOSTAT SUBBASE

TERMINALS WITH

THERMOSTAT REMOVED

HOOK-AROUND

VOLT/AMMETER

R Y W G

 

10 TURNS

 

FROM UNIT 24-VOLT

 

TERMINAL BLOCK

EXAMPLE:

5.0 AMPS ON AMMETER = 0.5 AMPS FOR THERMOSTAT SETTING

 

10 TURNS AROUND JAWS

 

A80201

 

Fig. 42ÐAmp Draw Check with Ammeter

Image 38
Contents Electrostatic Discharge ESD Precautions Ð1ÐÐ2Ð Dimensions→ ÐDimensional Drawing Unit SizeMinimum Inches Clearance to Combustible Construction Safety ConsiderationsElectrostatic Discharge ESD Precautions → ÐClearances to CombustiblesII. Upflow Applications IntroductionApplications General Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow OrientationCondensate Trap Field Drain Attachment Pressure Switch TubingÐ6Ð Condensate Trap Location Condensate Trap Freeze ProtectionIII. Downflow Applications Condensate Trap TubingIV. Horizontal Left SUPPLY-AIR Discharge Applications Ð8ÐÐ9Ð Horizontal Right SUPPLY-AIR Discharge ApplicationsConstruct a Working Platform ÐAttic Location and Working Platform Front Upflow or Downflow Horizontal II. Furnace Location Relative to Cooling Equipment II. Unconfined Space III. Hazardous LocationsAIR for Combustion and Ventilation General III. Confined SpaceCombustion AIR from Outdoors Through Horizontal Ducts Installation Leveling Legs if DesiredCombustion AIR from Outdoors Through Vertical Ducts Furnace Casing Width II. Installation on a Concrete SlabOpening Dimensions General Requirements IV. Installation in Horizontal ApplicationsAIR Ducts Ductwork acoustical treatmentÐfilter Information Return Air ConnectionsVI. Filter Arrangement VII. Bottom Closure PanelVIII. GAS Piping 171⁄2-IN. Wide Casings onlyNominal Length of Pipe FT Iron Internal Diameter Size Ðmaximum Capacity of Pipe CU FT PER HRElectrical Connections Ðelectrical Data WiringLength FT³ CKT BKR Amps Phase Amps SizeÐWiring Diagram Venting II -V WiringIII. Accessories Removal of Existing Furnaces from Common Vent SystemsCombustion Air Pipe II. COMBUSTION-AIR and Vent PipingGeneral ÐCombustion-Air Inlet Pipe Assembly 4001 to 5000² Ðmaximum Allowable Vent Pipe Length FT3001 to 6001 to 7000² Ðmaximum Allowable Vent Pipe Length FT5001 to 6000² 7001 to 8000²ÐShort Vent 5 to 8 Ft System 9001 to 10,000²Vent Extension Pipe 040 060 080 100 120Condensate Drain General III. Vent TerminationIV. Multiventing Ðvent Pipe Termination ClearancesÐRoof Termination Preferred III. Continuous Blower Mode Heating ModeII. Cooling Mode IV. Heat Pump ModeComponent Test Sequence START-UP Procedures GeneralComponent Test II. Prime Condensate Trap with WaterIII. Purge GAS Lines → ÐInducer Housing Drain TubeIV. Adjustments Set Gas Input RateBTU/CU FT Altitude5000 Only4001 Only 50018000 7001775 Only 8001Altitude Derate Multiplier Factor for U.S.A Ðaltitude Derate Multiplier for U.S.AExample Ðgas Rate CU FT/HR Set Temperature RiseBlower Off Delay Heat Mode ±SPEED SelectorChecklist Check Safety Controls Check Primary Limit ControlII. Check Pressure Switch Load Calculation ChecklistðinstallationCHECKLISTÐSTART-UP Vent Piping
Related manuals
Manual 12 pages 26.52 Kb Manual 12 pages 34 Kb

345MAV specifications

The Bryant 345MAV is a premier choice in the realm of residential heating and cooling systems, encapsulating advanced technologies, high efficiency, and remarkable performance. Designed for homeowners seeking reliability and comfort, this model exemplifies modern HVAC (Heating, Ventilation, and Air Conditioning) innovations.

One standout feature of the Bryant 345MAV is its impressive energy efficiency. With a high SEER (Seasonal Energy Efficiency Ratio) rating, it operates at peak levels while consuming less energy. This not only reduces utility bills but also supports environmental sustainability, making it an ideal selection for eco-conscious consumers. The model employs variable-speed technology, which allows the system to adjust its output based on current heating and cooling needs. As a result, it provides consistent indoor comfort while minimizing temperature fluctuations.

The Bryant 345MAV incorporates advanced refrigerant technologies designed for optimal performance. It uses R-410A refrigerant, which is known for its lower environmental impact compared to traditional refrigerants like R-22. This environmentally friendly aspect aligns with regulations aimed at reducing ozone depletion, thereby promoting a greener approach to heating and cooling.

Reliability is another hallmark of the Bryant 345MAV. Engineered with precision, this model features a durable build designed to withstand varying weather conditions. The system is equipped with a robust compressor that is engineered for longevity and minimal noise during operation. Homeowners will appreciate the quiet performance of the 345MAV, ensuring peace in their living spaces.

Comfort also extends to the user experience with the inclusion of a smart thermostat option. This integration allows homeowners to manage their heating and cooling systems remotely, enhancing convenience and control. Programmable settings can optimize energy use based on individual schedules, facilitating both comfort and savings.

In summary, the Bryant 345MAV is a top-tier solution for residential climate control, blending energy efficiency, innovative technology, and unmatched reliability. With its variable-speed operation, environmentally friendly refrigerant, and smart features, the 345MAV represents a significant advancement in the HVAC field. Homeowners investing in this model can expect a system that not only meets their heating and cooling needs but exceeds them in terms of efficiency and comfort.