Bryant 345MAV Ðelectrical Data, Wiring, Length FT³ CKT BKR Amps Phase, Amps Size

Page 20

TABLE 3ÐELECTRICAL DATA

UNIT

VOLTSÐ

OPERATING

MAX

UNIT

MIN

MAX WIRE

MAX FUSE OR

HERTZÐ

VOLTAGE RANGE

UNIT

WIRE

SIZE

AMPACITY²

LENGTH (FT)³

CKT BKR AMPS**

PHASE

Max*

Min*

AMPS

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

024040

115Ð60Ð1

127

104

6.1

8.4

14

44

15

036040

115Ð60Ð1

127

104

7.3

10.0

14

37

15

024060

115Ð60Ð1

127

104

6.1

8.4

14

44

15

036060

115Ð60Ð1

127

104

7.1

9.8

14

38

15

048060

115Ð60Ð1

127

104

9.5

12.8

14

29

15

036080

115Ð60Ð1

127

104

7.6

10.4

14

36

15

048080

115Ð60Ð1

127

104

10.0

13.4

14

28

15

060080

115Ð60Ð1

127

104

14.1

18.4

12

31

20

048100

115Ð60Ð1

127

104

10.2

13.5

14

27

15

060100

115Ð60Ð1

127

104

14.8

19.3

12

30

20

060120

115Ð60Ð1

127

104

14.6

19.1

12

30

20

 

 

 

 

 

 

 

 

 

* Permissible limits of voltage range at which unit will operate satisfactorily.

² Unit ampacity = 125 percent of largest operating component's full load amps plus 100 percent of all other potential operating components' (EAC, humidifier, etc.) full load amps.

³Length shown is as measured 1 way along wire path between unit and service panel for maximum 2 percent voltage drop. ** Time-delay type is recommended.

CAUTION: Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green wire routed to gas valve and burner box screw.

I.115-V WIRING

Before proceeding with electrical connections, make certain that voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 3 for equipment electrical specifications.

Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70-1999 and any local codes or ordinances that might apply. For Canadian installations, all electrical connections must be made in accordance with Canadian Electrical Code CSA C22.1 or subauthorities having jurisdiction.

ELECTRIC

DISCONNECT

SWITCH

COPPER

WIRE ONLY

ALUMINUM

WIRE

A93033

CAUTION: Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.

WARNING: The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-1999 and Canadian Electrical Code CSA C22.1 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire or conduit approved for electrical ground when installed in accordance with existing electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in electrical shock, fire, or death.

J-BOX RELOCATION

1.Remove 2 screws holding auxiliary J-box. (See Fig. 25.)

2.Rotate J-box 180° and attach box to right side, using holes provided.

FACTORY

 

INSTALLED

ALTERNATE

LOCATION

 

FIELD

 

LOCATION

A93051

Use a separate, fused branch electrical circuit containing a properly sized fuse or circuit breaker for this furnace. See Table 3 for wire size and fuse specifications. A disconnecting means must be located within sight from and readily accessible to furnace.

NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control center status code indicator light will flash rapidly and furnace will NOT operate.

Ð20Ð

Fig. 25ÐRelocating J-Box

CAUTION: If manual disconnect switch is to be mounted on furnace, select a location where a drill or fastener will not contact electrical or gas components.

Image 20
Contents Electrostatic Discharge ESD Precautions Ð1ÐDimensions → ÐDimensional DrawingÐ2Ð Unit SizeSafety Considerations Electrostatic Discharge ESD PrecautionsMinimum Inches Clearance to Combustible Construction → ÐClearances to CombustiblesIntroduction Applications GeneralII. Upflow Applications Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow OrientationCondensate Trap Field Drain Attachment Pressure Switch TubingÐ6Ð Condensate Trap Freeze Protection III. Downflow ApplicationsCondensate Trap Location Condensate Trap TubingIV. Horizontal Left SUPPLY-AIR Discharge Applications Ð8ÐÐ9Ð Horizontal Right SUPPLY-AIR Discharge ApplicationsConstruct a Working Platform ÐAttic Location and Working Platform Front Upflow or Downflow Horizontal II. Furnace Location Relative to Cooling Equipment III. Hazardous Locations AIR for Combustion and Ventilation GeneralII. Unconfined Space III. Confined SpaceCombustion AIR from Outdoors Through Horizontal Ducts Installation Leveling Legs if DesiredCombustion AIR from Outdoors Through Vertical Ducts Furnace Casing Width II. Installation on a Concrete SlabOpening Dimensions IV. Installation in Horizontal Applications AIR DuctsGeneral Requirements Ductwork acoustical treatmentReturn Air Connections VI. Filter ArrangementÐfilter Information VII. Bottom Closure PanelVIII. GAS Piping 171⁄2-IN. Wide Casings onlyNominal Length of Pipe FT Iron Internal Diameter Size Ðmaximum Capacity of Pipe CU FT PER HRElectrical Connections Wiring Length FT³ CKT BKR Amps PhaseÐelectrical Data Amps SizeÐWiring Diagram II -V Wiring III. AccessoriesVenting Removal of Existing Furnaces from Common Vent SystemsCombustion Air Pipe II. COMBUSTION-AIR and Vent PipingGeneral ÐCombustion-Air Inlet Pipe Assembly 4001 to 5000² Ðmaximum Allowable Vent Pipe Length FT3001 to Ðmaximum Allowable Vent Pipe Length FT 5001 to 6000²6001 to 7000² 7001 to 8000²ÐShort Vent 5 to 8 Ft System 9001 to 10,000²Vent Extension Pipe 040 060 080 100 120III. Vent Termination IV. MultiventingCondensate Drain General Ðvent Pipe Termination ClearancesÐRoof Termination Preferred Heating Mode II. Cooling ModeIII. Continuous Blower Mode IV. Heat Pump ModeSTART-UP Procedures General Component TestComponent Test Sequence II. Prime Condensate Trap with Water→ ÐInducer Housing Drain Tube IV. AdjustmentsIII. Purge GAS Lines Set Gas Input RateBTU/CU FT AltitudeOnly 40015000 Only 50017001 7758000 Only 8001Altitude Derate Multiplier Factor for U.S.A Ðaltitude Derate Multiplier for U.S.AExample Set Temperature Rise Blower Off Delay Heat ModeÐgas Rate CU FT/HR ±SPEED SelectorChecklist Check Safety Controls Check Primary Limit ControlII. Check Pressure Switch Checklistðinstallation CHECKLISTÐSTART-UPLoad Calculation Vent Piping
Related manuals
Manual 12 pages 26.52 Kb Manual 12 pages 34 Kb

345MAV specifications

The Bryant 345MAV is a premier choice in the realm of residential heating and cooling systems, encapsulating advanced technologies, high efficiency, and remarkable performance. Designed for homeowners seeking reliability and comfort, this model exemplifies modern HVAC (Heating, Ventilation, and Air Conditioning) innovations.

One standout feature of the Bryant 345MAV is its impressive energy efficiency. With a high SEER (Seasonal Energy Efficiency Ratio) rating, it operates at peak levels while consuming less energy. This not only reduces utility bills but also supports environmental sustainability, making it an ideal selection for eco-conscious consumers. The model employs variable-speed technology, which allows the system to adjust its output based on current heating and cooling needs. As a result, it provides consistent indoor comfort while minimizing temperature fluctuations.

The Bryant 345MAV incorporates advanced refrigerant technologies designed for optimal performance. It uses R-410A refrigerant, which is known for its lower environmental impact compared to traditional refrigerants like R-22. This environmentally friendly aspect aligns with regulations aimed at reducing ozone depletion, thereby promoting a greener approach to heating and cooling.

Reliability is another hallmark of the Bryant 345MAV. Engineered with precision, this model features a durable build designed to withstand varying weather conditions. The system is equipped with a robust compressor that is engineered for longevity and minimal noise during operation. Homeowners will appreciate the quiet performance of the 345MAV, ensuring peace in their living spaces.

Comfort also extends to the user experience with the inclusion of a smart thermostat option. This integration allows homeowners to manage their heating and cooling systems remotely, enhancing convenience and control. Programmable settings can optimize energy use based on individual schedules, facilitating both comfort and savings.

In summary, the Bryant 345MAV is a top-tier solution for residential climate control, blending energy efficiency, innovative technology, and unmatched reliability. With its variable-speed operation, environmentally friendly refrigerant, and smart features, the 345MAV represents a significant advancement in the HVAC field. Homeowners investing in this model can expect a system that not only meets their heating and cooling needs but exceeds them in terms of efficiency and comfort.