Bryant 345MAV Ð6Ð, Condensate Trap Field Drain Attachment, Pressure Switch Tubing

Page 6

PLUG

 

CAP

 

COLLECTOR BOX

 

DRAIN TUBE (BLUE

 

& WHITE STRIPED)

 

COLLECTOR BOX

 

TUBE (PINK)

 

COLLECTOR BOX

 

TUBE (GREEN)

 

INDUCER HOUSING

 

(MOLDED) DRAIN

 

TUBE (BEHIND

 

COLLECTOR BOX

 

DRAIN TUBE)

 

COLLECTOR BOX

 

DRAIN TUBE (BLUE)

CONDENSATE

 

 

TRAP

FIELD-INSTALLED

 

FACTORY-SUPPLIED

 

DRAIN TUBE

 

COUPLING (LEFT

 

DRAIN OPTION)

 

PLUG

CAP

COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)

COLLECTOR BOX

TUBE (PINK)

COLLECTOR BOX

TUBE (GREEN)

COLLECTOR BOX DRAIN TUBE (BLUE)

CONDENSATE TRAP

INDUCER HOUSING DRAIN TUBE (VIOLET)

FIELD-INSTALLED

 

FACTORY-SUPPLIED

 

DRAIN TUBE

 

FIELD-INSTALLED

FIELD-INSTALLED

FACTORY-SUPPLIED

FACTORY-SUPPLIED

12-IN. CPVC STREET

DRAIN TUBE

ELBOWS (2) FOR

COUPLING (RIGHT

LEFT DRAIN OPTION

DRAIN OPTION)

A94163

Fig. 5ÐFactory-Shipped Upflow Tube Configuration

(Shown With Blower Access Panel Removed)

D.Condensate Trap Tubing (Alternate Upflow Orientation)

NOTE: See Fig. 6 or tube routing label on main furnace door to confirm location of these tubes.

1. Collector Box Drain Tube

Connect collector box drain tube (blue label) to condensate trap.

NOTE: On 17-1/2-in. wide furnaces ONLY, cut tube between corrugated sections to prevent kinks from occurring.

2.Inducer Housing Drain Tube

a.Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to conden- sate trap.

b.Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the con- densate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

a.Connect relief port tube (green label) to condensate trap.

b.Use smaller diameter tube (factory-supplied in loose parts bag) to extend this tube if required.

Ð6Ð

A94164

Fig. 6ÐAlternate Upflow Tube Configuration and

Trap Location

c.Determine appropriate length, cut, and connect tube.

E. Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

F. Pressure Switch Tubing

The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any modification.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

G.Upper Collector Box and Inducer Housing (Unused) Drain Connections

UPPER COLLECTOR BOX DRAIN CONNECTION

Attached to the UPPER collector box drain connection is a factory-installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged.

NOTE: See Fig. 5 or 6 or tube routing label on main furnace door to check for proper connections.

UPPER INDUCER HOUSING DRAIN CONNECTION

Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.

Image 6
Contents Electrostatic Discharge ESD Precautions Ð1ÐÐ2Ð Dimensions→ ÐDimensional Drawing Unit SizeMinimum Inches Clearance to Combustible Construction Safety ConsiderationsElectrostatic Discharge ESD Precautions → ÐClearances to CombustiblesII. Upflow Applications IntroductionApplications General Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow OrientationPressure Switch Tubing Ð6ÐCondensate Trap Field Drain Attachment Condensate Trap Location Condensate Trap Freeze ProtectionIII. Downflow Applications Condensate Trap TubingIV. Horizontal Left SUPPLY-AIR Discharge Applications Ð8ÐHorizontal Right SUPPLY-AIR Discharge Applications Construct a Working PlatformÐ9Ð ÐAttic Location and Working Platform Front Upflow or Downflow Horizontal II. Furnace Location Relative to Cooling Equipment II. Unconfined Space III. Hazardous LocationsAIR for Combustion and Ventilation General III. Confined SpaceInstallation Leveling Legs if Desired Combustion AIR from Outdoors Through Vertical DuctsCombustion AIR from Outdoors Through Horizontal Ducts II. Installation on a Concrete Slab Opening DimensionsFurnace Casing Width General Requirements IV. Installation in Horizontal ApplicationsAIR Ducts Ductwork acoustical treatmentÐfilter Information Return Air ConnectionsVI. Filter Arrangement VII. Bottom Closure PanelVIII. GAS Piping 171⁄2-IN. Wide Casings onlyÐmaximum Capacity of Pipe CU FT PER HR Electrical ConnectionsNominal Length of Pipe FT Iron Internal Diameter Size Ðelectrical Data WiringLength FT³ CKT BKR Amps Phase Amps SizeÐWiring Diagram Venting II -V WiringIII. Accessories Removal of Existing Furnaces from Common Vent SystemsII. COMBUSTION-AIR and Vent Piping GeneralCombustion Air Pipe ÐCombustion-Air Inlet Pipe Assembly Ðmaximum Allowable Vent Pipe Length FT 3001 to4001 to 5000² 6001 to 7000² Ðmaximum Allowable Vent Pipe Length FT5001 to 6000² 7001 to 8000²ÐShort Vent 5 to 8 Ft System 9001 to 10,000²Vent Extension Pipe 040 060 080 100 120Condensate Drain General III. Vent TerminationIV. Multiventing Ðvent Pipe Termination ClearancesÐRoof Termination Preferred III. Continuous Blower Mode Heating ModeII. Cooling Mode IV. Heat Pump ModeComponent Test Sequence START-UP Procedures GeneralComponent Test II. Prime Condensate Trap with WaterIII. Purge GAS Lines → ÐInducer Housing Drain TubeIV. Adjustments Set Gas Input RateBTU/CU FT Altitude5000 Only4001 Only 50018000 7001775 Only 8001Ðaltitude Derate Multiplier for U.S.A ExampleAltitude Derate Multiplier Factor for U.S.A Ðgas Rate CU FT/HR Set Temperature RiseBlower Off Delay Heat Mode ±SPEED SelectorCheck Safety Controls Check Primary Limit Control II. Check Pressure SwitchChecklist Load Calculation ChecklistðinstallationCHECKLISTÐSTART-UP Vent Piping
Related manuals
Manual 12 pages 26.52 Kb Manual 12 pages 34 Kb

345MAV specifications

The Bryant 345MAV is a premier choice in the realm of residential heating and cooling systems, encapsulating advanced technologies, high efficiency, and remarkable performance. Designed for homeowners seeking reliability and comfort, this model exemplifies modern HVAC (Heating, Ventilation, and Air Conditioning) innovations.

One standout feature of the Bryant 345MAV is its impressive energy efficiency. With a high SEER (Seasonal Energy Efficiency Ratio) rating, it operates at peak levels while consuming less energy. This not only reduces utility bills but also supports environmental sustainability, making it an ideal selection for eco-conscious consumers. The model employs variable-speed technology, which allows the system to adjust its output based on current heating and cooling needs. As a result, it provides consistent indoor comfort while minimizing temperature fluctuations.

The Bryant 345MAV incorporates advanced refrigerant technologies designed for optimal performance. It uses R-410A refrigerant, which is known for its lower environmental impact compared to traditional refrigerants like R-22. This environmentally friendly aspect aligns with regulations aimed at reducing ozone depletion, thereby promoting a greener approach to heating and cooling.

Reliability is another hallmark of the Bryant 345MAV. Engineered with precision, this model features a durable build designed to withstand varying weather conditions. The system is equipped with a robust compressor that is engineered for longevity and minimal noise during operation. Homeowners will appreciate the quiet performance of the 345MAV, ensuring peace in their living spaces.

Comfort also extends to the user experience with the inclusion of a smart thermostat option. This integration allows homeowners to manage their heating and cooling systems remotely, enhancing convenience and control. Programmable settings can optimize energy use based on individual schedules, facilitating both comfort and savings.

In summary, the Bryant 345MAV is a top-tier solution for residential climate control, blending energy efficiency, innovative technology, and unmatched reliability. With its variable-speed operation, environmentally friendly refrigerant, and smart features, the 345MAV represents a significant advancement in the HVAC field. Homeowners investing in this model can expect a system that not only meets their heating and cooling needs but exceeds them in terms of efficiency and comfort.