4.Wrap field drain pipe with remaining heat tape, approxi- mately 1 wrap per ft.

5.When using field-supplied heat tape, follow heat tape manufacturer's instructions for all other installation guide- lines.

SEQUENCE OF OPERATION

CAUTION: Furnace control must be grounded for proper operation, or control will lock out. Control is grounded through green wire routed to gas valve and burner box screw.

Using schematic diagram, follow sequence of operation through different modes. (See Fig. 26.) This furnace has a new control system. Read and follow wiring diagram carefully.

NOTE: If 115-v power supply to furnace or blower access panel switch is interrupted during a call for heat, blower operates for 90 sec when power is restored before heating cycle is resumed.

I.HEATING MODE

When wall thermostat "calls for heat," R-W circuit closes. Furnace control performs a self-check, verifies pressure switch contacts are open, and starts inducer motor.

1.Prepurge periodÐAs inducer motor comes up to speed, pressure switch contacts close to begin a 15-sec prepurge period.

2.Ignitor warm upÐAt end of prepurge period, ignitor is energized for a 17-sec ignitor warm-up period.

3.Ignition sequenceÐWhen ignitor warm-up period is com- pleted, gas valve opens, permitting gas flow to burners where it is ignited. After 5 sec, ignitor is de-energized and a 2-sec flame-sensing period begins.

HUM terminal on control center is energized with gas valve. See Accessories Ð Humidifier section.

4.Flame sensingÐWhen burner flame is sensed, control begins blower on delay period and continues holding gas valve open.

If burner flame is not sensed, control center de-energizes gas valve and ignition sequence is repeated.

NOTE: Ignition sequence repeats 3 additional times before a lockout occurs. Lockout automatically resets after 3 hr or can be manually reset by turning off 115v (not at thermostat) for 3 sec minimum, then turning it on again.

5.Blower on delayÐSixty sec after burner flame is proven, blower motor is energized on heating speed. Simulta- neously, electronic air cleaner terminal EAC-1 is energized.

6.Blower off delayÐWhen thermostat is satisfied, circuit between R-W is opened, de-energizing gas valve (stopping gas flow to burners) and humidifier. Blower motor and electronic air cleaner remain energized for 135 sec.

7.Post purgeÐInducer motor remains energized 15 sec after burners are extinguished.

II.COOLING MODE

When thermostat "calls for cooling," R-G and R-Y circuits close. R-Y circuit starts outdoor condensing unit, and combined R-Y and R-G circuit starts furnace blower motor on cooling speed. Elec- tronic air cleaner EAC-1 terminal is energized with 115v whenever blower is operating.

When thermostat is satisfied, R-G and R-Y circuits are opened, furnace blower continues operating on cooling speed for an additional 90 sec.

III.CONTINUOUS BLOWER MODE

When R-G circuit is made, blower motor operates on heating speed.

NOTE: Electronic air cleaner EAC-1 terminal is energized with 115v whenever blower is operating.

If a "call for heat" (R-W) occurs while thermostat is in continuous blower mode, blower stops to allow furnace heat exchangers to heat up more quickly, then restarts at end of blower on delay period of 60 sec.

Blower reverts to continuous operation after heating cycle is completed.

If a "call for cooling" (R-Y) occurs while thermostat is in continuous blower mode, blower changes from continuous blower speed (heating speed) to cooling speed.

When thermostat cooling call is satisfied, R-Y opens and blower operates an additional 90 sec at cooling speed before reverting back to continuous operation (heating speed).

IV. HEAT PUMP MODE

When installed with a heat pump, furnace control automatically changes blower on delay timing sequence to avoid no blower operation time during demand defrost cycles. When R-W and R-Y or R-W, R-Y, and R-G thermostat inputs are received at the same time at furnace control center, control starts blower in heating speed. Then a gas heat mode begins. Blower remains operating at heating speed for 15 sec or until end of prepurge period, then blower shuts off until end of ignitor warm up and trial for ignition

CONDENSATE TRAP

WIRE TIE(S)

HEAT TAPE (3 WRAPS MINIMUM)

Fig. 37ÐCondensate Trap Heat Tape

A93036

Ð31Ð

periods (a total of 24 sec). Blower restarts at heating speed.

When R-W thermostat call disappears, control completes inducer post-purge period (15 sec) and changes to cooling speed after a 2-sec delay.

If R-W, R-Y, and R-G thermostat signals should disappear simultaneously, blower remains on for heating blower off delay period of 135, and the inducer goes through 15 sec post-purge period. If R-W and R-Y thermostat signals should disappear, leaving R-G thermostat signal, blower remains on in heating speed and inducer remains on for 15 sec to complete post-purge period.

Control initiates a 90-sec blower only on period before starting another heat pump cycle if there is a power interruption. Anytime control senses false flame, control locks out of heating mode. This reaction occurs because control ignores W input due to false flame signal and, as a result, sees only Y input and goes into cooling mode blower off delay. All other control functions remain in standard format.

NOTE: EAC-1 terminal is energized whenever blower operates. HUM terminal is only energized when gas valve is energized.

Image 31
Contents Ð1Ð Electrostatic Discharge ESD PrecautionsUnit Size Dimensions→ ÐDimensional Drawing Ð2Ð→ ÐClearances to Combustibles Safety ConsiderationsElectrostatic Discharge ESD Precautions Minimum Inches Clearance to Combustible ConstructionCondensate Trap Location Factory-Shipped Orientation IntroductionApplications General II. Upflow ApplicationsCondensate Trap Location Alternate Upflow Orientation Ð5ÐÐ6Ð Pressure Switch TubingCondensate Trap Field Drain Attachment Condensate Trap Tubing Condensate Trap Freeze ProtectionIII. Downflow Applications Condensate Trap LocationÐ8Ð IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsConstruct a Working Platform Horizontal Right SUPPLY-AIR Discharge ApplicationsÐ9Ð ÐAttic Location and Working Platform Front Upflow or Downflow Horizontal II. Furnace Location Relative to Cooling Equipment III. Confined Space III. Hazardous LocationsAIR for Combustion and Ventilation General II. Unconfined SpaceCombustion AIR from Outdoors Through Vertical Ducts Installation Leveling Legs if DesiredCombustion AIR from Outdoors Through Horizontal Ducts Opening Dimensions II. Installation on a Concrete SlabFurnace Casing Width Ductwork acoustical treatment IV. Installation in Horizontal ApplicationsAIR Ducts General RequirementsVII. Bottom Closure Panel Return Air ConnectionsVI. Filter Arrangement Ðfilter Information171⁄2-IN. Wide Casings only VIII. GAS PipingElectrical Connections Ðmaximum Capacity of Pipe CU FT PER HRNominal Length of Pipe FT Iron Internal Diameter Size Amps Size WiringLength FT³ CKT BKR Amps Phase Ðelectrical DataÐWiring Diagram Removal of Existing Furnaces from Common Vent Systems II -V WiringIII. Accessories VentingGeneral II. COMBUSTION-AIR and Vent PipingCombustion Air Pipe ÐCombustion-Air Inlet Pipe Assembly 3001 to Ðmaximum Allowable Vent Pipe Length FT4001 to 5000² 7001 to 8000² Ðmaximum Allowable Vent Pipe Length FT5001 to 6000² 6001 to 7000²9001 to 10,000² ÐShort Vent 5 to 8 Ft System040 060 080 100 120 Vent Extension PipeÐvent Pipe Termination Clearances III. Vent TerminationIV. Multiventing Condensate Drain GeneralÐRoof Termination Preferred IV. Heat Pump Mode Heating ModeII. Cooling Mode III. Continuous Blower ModeII. Prime Condensate Trap with Water START-UP Procedures GeneralComponent Test Component Test SequenceSet Gas Input Rate → ÐInducer Housing Drain TubeIV. Adjustments III. Purge GAS LinesAltitude BTU/CU FTOnly 5001 Only4001 5000Only 8001 7001775 8000Example Ðaltitude Derate Multiplier for U.S.AAltitude Derate Multiplier Factor for U.S.A ±SPEED Selector Set Temperature RiseBlower Off Delay Heat Mode Ðgas Rate CU FT/HRII. Check Pressure Switch Check Safety Controls Check Primary Limit ControlChecklist Vent Piping ChecklistðinstallationCHECKLISTÐSTART-UP Load Calculation
Related manuals
Manual 12 pages 26.52 Kb Manual 12 pages 34 Kb

345MAV specifications

The Bryant 345MAV is a premier choice in the realm of residential heating and cooling systems, encapsulating advanced technologies, high efficiency, and remarkable performance. Designed for homeowners seeking reliability and comfort, this model exemplifies modern HVAC (Heating, Ventilation, and Air Conditioning) innovations.

One standout feature of the Bryant 345MAV is its impressive energy efficiency. With a high SEER (Seasonal Energy Efficiency Ratio) rating, it operates at peak levels while consuming less energy. This not only reduces utility bills but also supports environmental sustainability, making it an ideal selection for eco-conscious consumers. The model employs variable-speed technology, which allows the system to adjust its output based on current heating and cooling needs. As a result, it provides consistent indoor comfort while minimizing temperature fluctuations.

The Bryant 345MAV incorporates advanced refrigerant technologies designed for optimal performance. It uses R-410A refrigerant, which is known for its lower environmental impact compared to traditional refrigerants like R-22. This environmentally friendly aspect aligns with regulations aimed at reducing ozone depletion, thereby promoting a greener approach to heating and cooling.

Reliability is another hallmark of the Bryant 345MAV. Engineered with precision, this model features a durable build designed to withstand varying weather conditions. The system is equipped with a robust compressor that is engineered for longevity and minimal noise during operation. Homeowners will appreciate the quiet performance of the 345MAV, ensuring peace in their living spaces.

Comfort also extends to the user experience with the inclusion of a smart thermostat option. This integration allows homeowners to manage their heating and cooling systems remotely, enhancing convenience and control. Programmable settings can optimize energy use based on individual schedules, facilitating both comfort and savings.

In summary, the Bryant 345MAV is a top-tier solution for residential climate control, blending energy efficiency, innovative technology, and unmatched reliability. With its variable-speed operation, environmentally friendly refrigerant, and smart features, the 345MAV represents a significant advancement in the HVAC field. Homeowners investing in this model can expect a system that not only meets their heating and cooling needs but exceeds them in terms of efficiency and comfort.