Bryant 345MAV instruction manual IV. Horizontal Left SUPPLY-AIR Discharge Applications, Ð8Ð

Page 8

b.Remove and discard UPPER (molded) inducer housing drain tube which was previously connected to conden- sate trap.

c.Install cap and clamp on UPPER inducer housing drain connection where molded drain tube was removed.

d.Use inducer housing drain tube (violet label and factory- supplied in loose parts bag) to connect LOWER inducer housing drain connection to the condensate trap.

e.Connect inducer housing drain connection to condensate trap.

(1.)

Condensate Trap Located on Left Side of Casing

 

(a.)

Determine appropriate length and cut.

 

(b.)

Connect tube to condensate trap.

 

(c.)

Clamp tube to prevent any condensate leakage.

(2.)

Condensate Trap Located on Right Side of Casing

 

(a.)

Route inducer housing drain tube (violet label)

 

 

between gas valve and inlet housing behind

 

 

collector box drain tube.

 

(b.)

Determine appropriate length and cut.

 

(c.)

Connect tube to condensate trap.

 

(d.)

Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

Refer to Pressure Switch Tubing section for connection procedure.

C.Condensate Trap Field Drain Attachment

Refer to Condensate Drain section for recommendations and procedures.

D.Pressure Switch Tubing

One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW or HORIZONTAL RIGHT applications. NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.

Relocate tubes as described below.

1.Disconnect collector box pressure tube (pink label) attached to pressure switch.

2.Use smaller diameter tube (factory-supplied in loose parts bag) to extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection.

3.Connect collector box pressure tube (green label) to pres- sure switch connection labeled "collector box."

4.Use remaining smaller diameter tube (factory-supplied in loose parts bag) to extend collector box pressure tube (pink label) which was previously connected to pressure switch.

5.Route this extended tube (pink label) to condensate trap relief port connection.

6.Determine appropriate length, cut, and connect tube.

7.Clamp tube to relief port connection.

E. Condensate Trap Freeze Protection

Refer to Condensate Drain Protection section for recommenda- tions and procedures.

IV. HORIZONTAL LEFT (SUPPLY-AIR DISCHARGE) APPLICATIONS

A horizontal left furnace application is where furnace blower is located to the right of combustion and controls section of furnace, and conditioned air is discharged to the left.

Ð8Ð

CAUTION: Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.

NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.

NOTE: The auxiliary junction box (J-Box) MUST be relocated to opposite side of furnace casing. (See Fig. 9.) See Electrical Connection section for J-Box relocation.

A.Condensate Trap Location

The condensate trap must be removed from the factory-installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 9.

To relocate condensate trap from the blower shelf to desired location, perform the following:

1.Remove 3 tubes connected to condensate trap.

2.Remove trap from blower shelf by gently pushing tabs inward and rotating trap.

3.Remove casing hole filler cap from casing hole. (See Fig. 2 or 9.)

4.Install casing hole filler cap into blower shelf hole where trap was removed.

5.Install condensate trap into casing hole by inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.

B.Condensate Trap Tubing

NOTE: See Fig. 9 or tube routing label on main furnace door to check for proper connections.

1.Collector Box Drain Tube

a.Install drain tube coupling (factory-supplied in loose parts bag) into collector box drain tube (blue label) which was previously connected to condensate trap.

b.Connect large diameter drain tube and clamp (factory- supplied in loose parts bag) to drain tube coupling, extending collector box drain tube.

c.Route extended tube (blue label) to condensate trap and cut to appropriate length.

d.Clamp tube to prevent any condensate leakage.

2.Inducer Housing Drain Tube

a.Remove and discard LOWER (molded) inducer housing drain tube which was previously connected to conden- sate trap.

b.Use inducer housing drain extension tube (violet label and factory-supplied in loose parts bag) to connect LOWER inducer housing drain connection to the con- densate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

3.Relief Port Tube

a.Use smaller diameter tube (factory-supplied in loose parts bag) to extend collector box tube (green label) which was previously connected to the condensate trap.

b.Route extended collector box pressure tube to relief port connection on the condensate trap.

c.Determine appropriate length, cut, and connect tube.

d.Clamp tube to prevent any condensate leakage.

Image 8
Contents Electrostatic Discharge ESD Precautions Ð1ÐDimensions → ÐDimensional DrawingÐ2Ð Unit SizeSafety Considerations Electrostatic Discharge ESD PrecautionsMinimum Inches Clearance to Combustible Construction → ÐClearances to CombustiblesIntroduction Applications GeneralII. Upflow Applications Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow OrientationCondensate Trap Field Drain Attachment Pressure Switch TubingÐ6Ð Condensate Trap Freeze Protection III. Downflow ApplicationsCondensate Trap Location Condensate Trap TubingIV. Horizontal Left SUPPLY-AIR Discharge Applications Ð8ÐÐ9Ð Horizontal Right SUPPLY-AIR Discharge ApplicationsConstruct a Working Platform ÐAttic Location and Working Platform Front Upflow or Downflow Horizontal II. Furnace Location Relative to Cooling Equipment III. Hazardous Locations AIR for Combustion and Ventilation GeneralII. Unconfined Space III. Confined SpaceCombustion AIR from Outdoors Through Horizontal Ducts Installation Leveling Legs if DesiredCombustion AIR from Outdoors Through Vertical Ducts Furnace Casing Width II. Installation on a Concrete SlabOpening Dimensions IV. Installation in Horizontal Applications AIR DuctsGeneral Requirements Ductwork acoustical treatmentReturn Air Connections VI. Filter ArrangementÐfilter Information VII. Bottom Closure PanelVIII. GAS Piping 171⁄2-IN. Wide Casings onlyNominal Length of Pipe FT Iron Internal Diameter Size Ðmaximum Capacity of Pipe CU FT PER HRElectrical Connections Wiring Length FT³ CKT BKR Amps PhaseÐelectrical Data Amps SizeÐWiring Diagram II -V Wiring III. AccessoriesVenting Removal of Existing Furnaces from Common Vent SystemsCombustion Air Pipe II. COMBUSTION-AIR and Vent PipingGeneral ÐCombustion-Air Inlet Pipe Assembly 4001 to 5000² Ðmaximum Allowable Vent Pipe Length FT3001 to Ðmaximum Allowable Vent Pipe Length FT 5001 to 6000²6001 to 7000² 7001 to 8000²ÐShort Vent 5 to 8 Ft System 9001 to 10,000²Vent Extension Pipe 040 060 080 100 120III. Vent Termination IV. MultiventingCondensate Drain General Ðvent Pipe Termination ClearancesÐRoof Termination Preferred Heating Mode II. Cooling ModeIII. Continuous Blower Mode IV. Heat Pump ModeSTART-UP Procedures General Component TestComponent Test Sequence II. Prime Condensate Trap with Water→ ÐInducer Housing Drain Tube IV. AdjustmentsIII. Purge GAS Lines Set Gas Input RateBTU/CU FT AltitudeOnly 40015000 Only 50017001 7758000 Only 8001Altitude Derate Multiplier Factor for U.S.A Ðaltitude Derate Multiplier for U.S.AExample Set Temperature Rise Blower Off Delay Heat ModeÐgas Rate CU FT/HR ±SPEED SelectorChecklist Check Safety Controls Check Primary Limit ControlII. Check Pressure Switch Checklistðinstallation CHECKLISTÐSTART-UPLoad Calculation Vent Piping
Related manuals
Manual 12 pages 26.52 Kb Manual 12 pages 34 Kb

345MAV specifications

The Bryant 345MAV is a premier choice in the realm of residential heating and cooling systems, encapsulating advanced technologies, high efficiency, and remarkable performance. Designed for homeowners seeking reliability and comfort, this model exemplifies modern HVAC (Heating, Ventilation, and Air Conditioning) innovations.

One standout feature of the Bryant 345MAV is its impressive energy efficiency. With a high SEER (Seasonal Energy Efficiency Ratio) rating, it operates at peak levels while consuming less energy. This not only reduces utility bills but also supports environmental sustainability, making it an ideal selection for eco-conscious consumers. The model employs variable-speed technology, which allows the system to adjust its output based on current heating and cooling needs. As a result, it provides consistent indoor comfort while minimizing temperature fluctuations.

The Bryant 345MAV incorporates advanced refrigerant technologies designed for optimal performance. It uses R-410A refrigerant, which is known for its lower environmental impact compared to traditional refrigerants like R-22. This environmentally friendly aspect aligns with regulations aimed at reducing ozone depletion, thereby promoting a greener approach to heating and cooling.

Reliability is another hallmark of the Bryant 345MAV. Engineered with precision, this model features a durable build designed to withstand varying weather conditions. The system is equipped with a robust compressor that is engineered for longevity and minimal noise during operation. Homeowners will appreciate the quiet performance of the 345MAV, ensuring peace in their living spaces.

Comfort also extends to the user experience with the inclusion of a smart thermostat option. This integration allows homeowners to manage their heating and cooling systems remotely, enhancing convenience and control. Programmable settings can optimize energy use based on individual schedules, facilitating both comfort and savings.

In summary, the Bryant 345MAV is a top-tier solution for residential climate control, blending energy efficiency, innovative technology, and unmatched reliability. With its variable-speed operation, environmentally friendly refrigerant, and smart features, the 345MAV represents a significant advancement in the HVAC field. Homeowners investing in this model can expect a system that not only meets their heating and cooling needs but exceeds them in terms of efficiency and comfort.