Bryant 345MAV instruction manual Vent Extension Pipe, 040 060 080 100 120

Page 28

TABLE 5ÐMAXIMUM ALLOWABLE EXPOSED VENT PIPE LENGTH (FT) WITH INSULATION IN

WINTER DESIGN TEMPERATURE AMBIENT*

UNIT

WINTER DESIGN

MAX PIPE

WITHOUT

WITH 3/8-IN. OR

TEMPERATURE

DIAMETER

SIZE

INSULATION

THICKER INSULATION²

(°F)

(IN.)

 

 

 

 

20

1.5

51

70

 

 

 

 

 

 

0

1.5

28

70

 

 

 

 

 

040

-20

1.5

16

70

 

 

 

 

20

2

45

70

 

 

 

 

 

 

 

0

2

22

70

 

 

 

 

 

 

-20

2

10

58

 

 

 

 

 

 

20

2

65

70

060

 

 

 

 

0

2

35

70

 

-20

2

20

70

 

20

2

55

55

 

0

2

48

55

080

-20

2

30

55

20

2.5

70

70

 

 

0

2.5

47

70

 

-20

2.5

28

70

 

20

2.5

40

40

 

0

2.5

40

40

100

-20

2.5

38

40

20

3

70

70

 

 

0

3

50

70

 

-20

3

28

70

 

20

3

70

70

120

0

3

61

70

 

-20

3

37

70

 

 

 

 

 

* Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces. Pipes located in unconditioned space cannot exceed total allowable pipe length as specified in Table 4.

² Insulation thickness based on R value of 3.5 (ft 2·°F·hr.)/(Btu·in.)

WARNING: Inducer housing outlet cap must be in- stalled and fully seated against inducer housing. Clamp must be tightened to prevent any condensate leakage. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.

3.Install pipe support (factory-supplied in loose parts bag) into selected furnace casing vent pipe hole. Pipe support should be positioned at bottom of casing hole.

4. Be certain that mating surfaces of inducer housing connec- tion, elastomeric coupling, and 2-in. diameter vent pipe are clean and dry. Assemble the elastomeric (rubber) vent coupling (with 2 loose clamps) onto inducer housing connection. Insert the 2-in. diameter vent pipe through the elastomeric (rubber) coupling and fully into inducer hous- ing connection until it bottoms on the internal stop. Tighten both clamps to secure the pipe to inducer housing. Tighten the clamp screws to 15 in.-lb. of torque.

WARNING: Vent pipe must be installed and fully seated against inducer housing internal stop. Clamp must

be tightened to prevent any condensate leakage. Failure to follow this warning could result in electrical shock, fire, personal injury, or death.

NOTE: A 2-in. diameter pipe must be used within the furnace casing. Make all pipe diameter transitions outside furnace casing.

VENT EXTENSION PIPE

Some furnaces are supplied with a PVC vent extension pipe (2-in. diameter by 12-in. long). This pipe has a built-in

Ð28Ð

channel to assist vent condensate disposal. When this vent extension pipe is supplied, it must be used to connect the field vent pipe to furnace inducer housing on ALL upflow and downflow applications.

NOTE: See label on vent extension pipe for proper installation. This pipe may be shortened if an elbow is used to connect vent extension tube to field-installed vent pipe.

5.Working from furnace to outside, cut pipe to required length(s).

6.Deburr inside and outside of pipe.

7.Chamfer outside edge of pipe for better distribution of primer and cement.

8.Clean and dry all surfaces to be joined.

9.Check dry fit of pipe and mark insertion depth on pipe.

NOTE: It is recommended that all pipes be cut, prepared, and preassembled before permanently cementing any joint.

10.After pipes have been cut and preassembled, apply gener- ous layer of cement primer to pipe fitting socket and end of pipe to insertion mark. Quickly apply approved cement to end of pipe and fitting socket (over primer). Apply cement in a light, uniform coat on inside of socket to prevent buildup of excess cement. Apply second coat.

11.While cement is still wet, twist pipe into socket with 1/4 turn. Be sure pipe is fully inserted into fitting socket.

12.Wipe excess cement from joint. A continuous bead of cement will be visible around perimeter of a properly made joint.

13.Handle pipe joints carefully until cement sets.

14.Support vent piping a minimum of every 5 ft (3 ft for SDR-21 or -26 PVC) using perforated metal hanging strap.

Image 28
Contents Electrostatic Discharge ESD Precautions Ð1ÐDimensions → ÐDimensional DrawingÐ2Ð Unit SizeSafety Considerations Electrostatic Discharge ESD PrecautionsMinimum Inches Clearance to Combustible Construction → ÐClearances to CombustiblesIntroduction Applications GeneralII. Upflow Applications Condensate Trap Location Factory-Shipped OrientationÐ5Ð Condensate Trap Location Alternate Upflow OrientationÐ6Ð Pressure Switch TubingCondensate Trap Field Drain Attachment Condensate Trap Freeze Protection III. Downflow ApplicationsCondensate Trap Location Condensate Trap TubingIV. Horizontal Left SUPPLY-AIR Discharge Applications Ð8ÐConstruct a Working Platform Horizontal Right SUPPLY-AIR Discharge ApplicationsÐ9Ð ÐAttic Location and Working Platform Front Upflow or Downflow Horizontal II. Furnace Location Relative to Cooling Equipment III. Hazardous Locations AIR for Combustion and Ventilation GeneralII. Unconfined Space III. Confined SpaceCombustion AIR from Outdoors Through Vertical Ducts Installation Leveling Legs if DesiredCombustion AIR from Outdoors Through Horizontal Ducts Opening Dimensions II. Installation on a Concrete SlabFurnace Casing Width IV. Installation in Horizontal Applications AIR DuctsGeneral Requirements Ductwork acoustical treatmentReturn Air Connections VI. Filter ArrangementÐfilter Information VII. Bottom Closure PanelVIII. GAS Piping 171⁄2-IN. Wide Casings onlyElectrical Connections Ðmaximum Capacity of Pipe CU FT PER HRNominal Length of Pipe FT Iron Internal Diameter Size Wiring Length FT³ CKT BKR Amps PhaseÐelectrical Data Amps SizeÐWiring Diagram II -V Wiring III. AccessoriesVenting Removal of Existing Furnaces from Common Vent SystemsGeneral II. COMBUSTION-AIR and Vent PipingCombustion Air Pipe ÐCombustion-Air Inlet Pipe Assembly 3001 to Ðmaximum Allowable Vent Pipe Length FT4001 to 5000² Ðmaximum Allowable Vent Pipe Length FT 5001 to 6000²6001 to 7000² 7001 to 8000²ÐShort Vent 5 to 8 Ft System 9001 to 10,000²Vent Extension Pipe 040 060 080 100 120III. Vent Termination IV. MultiventingCondensate Drain General Ðvent Pipe Termination ClearancesÐRoof Termination Preferred Heating Mode II. Cooling ModeIII. Continuous Blower Mode IV. Heat Pump ModeSTART-UP Procedures General Component TestComponent Test Sequence II. Prime Condensate Trap with Water→ ÐInducer Housing Drain Tube IV. AdjustmentsIII. Purge GAS Lines Set Gas Input RateBTU/CU FT AltitudeOnly 40015000 Only 50017001 7758000 Only 8001Example Ðaltitude Derate Multiplier for U.S.AAltitude Derate Multiplier Factor for U.S.A Set Temperature Rise Blower Off Delay Heat ModeÐgas Rate CU FT/HR ±SPEED SelectorII. Check Pressure Switch Check Safety Controls Check Primary Limit ControlChecklist Checklistðinstallation CHECKLISTÐSTART-UPLoad Calculation Vent Piping
Related manuals
Manual 12 pages 26.52 Kb Manual 12 pages 34 Kb

345MAV specifications

The Bryant 345MAV is a premier choice in the realm of residential heating and cooling systems, encapsulating advanced technologies, high efficiency, and remarkable performance. Designed for homeowners seeking reliability and comfort, this model exemplifies modern HVAC (Heating, Ventilation, and Air Conditioning) innovations.

One standout feature of the Bryant 345MAV is its impressive energy efficiency. With a high SEER (Seasonal Energy Efficiency Ratio) rating, it operates at peak levels while consuming less energy. This not only reduces utility bills but also supports environmental sustainability, making it an ideal selection for eco-conscious consumers. The model employs variable-speed technology, which allows the system to adjust its output based on current heating and cooling needs. As a result, it provides consistent indoor comfort while minimizing temperature fluctuations.

The Bryant 345MAV incorporates advanced refrigerant technologies designed for optimal performance. It uses R-410A refrigerant, which is known for its lower environmental impact compared to traditional refrigerants like R-22. This environmentally friendly aspect aligns with regulations aimed at reducing ozone depletion, thereby promoting a greener approach to heating and cooling.

Reliability is another hallmark of the Bryant 345MAV. Engineered with precision, this model features a durable build designed to withstand varying weather conditions. The system is equipped with a robust compressor that is engineered for longevity and minimal noise during operation. Homeowners will appreciate the quiet performance of the 345MAV, ensuring peace in their living spaces.

Comfort also extends to the user experience with the inclusion of a smart thermostat option. This integration allows homeowners to manage their heating and cooling systems remotely, enhancing convenience and control. Programmable settings can optimize energy use based on individual schedules, facilitating both comfort and savings.

In summary, the Bryant 345MAV is a top-tier solution for residential climate control, blending energy efficiency, innovative technology, and unmatched reliability. With its variable-speed operation, environmentally friendly refrigerant, and smart features, the 345MAV represents a significant advancement in the HVAC field. Homeowners investing in this model can expect a system that not only meets their heating and cooling needs but exceeds them in terms of efficiency and comfort.