Bryant 345MAV III. Vent Termination, IV. Multiventing, Condensate Drain General, II. Application

Page 29

15.Slope vent pipe toward furnace a minimum of 1/4 in. per linear ft with no sags between hangers.

16.Use appropriate methods to seal openings where vent pipe passes through roof or sidewall.

D.Extended Exposed Sidewall Pipes

Sidewall vent pipe termination may be extended beyond area shown in Fig. 34 in outside ambient by insulating pipe as indicated in Table 5.

1.Determine vent pipe diameter, as stated above, using total pipe length and number of elbows.

2.Find appropriate temperature for your application and furnace model using winter design temperature (used in load calculations).

3.Determine required insulation thickness for exposed pipe lengths.

NOTE: Pipe length (ft) specified for maximum pipe lengths located in unconditioned spaces cannot exceed total allowable pipe length as specified in Table 4.

III.VENT TERMINATION

Vent pipe must terminate either through roof or sidewall. See Table 6 for required clearances. See Fig. 33, 34, and 35 for exterior piping arrangements.

Consideration of the following should be made when determining an appropriate location for termination:

1.Comply with all clearance requirements stated in Table 6.

2.Termination should be positioned where vent vapors will not damage plants/shrubs or air conditioning equipment.

3.Termination should be positioned where it will not be damaged by or subjected to foreign objects such as stones, balls, etc.

4.Termination should be positioned where vent vapors are not objectionable.

IV. MULTIVENTING

When 2 or more 345MAV Furnaces are vented near each other, each furnace must be individually vented. NEVER common vent or breach vent 345MAV furnaces.

CONDENSATE DRAIN

I.GENERAL

Condensate trap is shipped installed in the blower shelf and factory connected for UPFLOW applications. Condensate trap must be RELOCATED for use in DOWNFLOW and HORIZONTAL applications.

Condensate trap MUST be used for all applications.

An external trap is not required when connecting the field drain to this condensate trap.

The field drain connection (condensate trap or drain tube coupling) is sized for 1/2-in. CPVC, 1/2-in. PVC, or 5/8-in. ID tube connection.

Drain pipe and fittings must conform to ANSI standards and ASTM D1785 or D2846. CPVC or PVC cement and primer must conform to ASTM D2564 or F493. In Canada, use CSA or ULC certified schedule 40 CPVC or PVC drain pipe, fittings, and cement.

When a condensate pump is required, select a pump which is approved for condensing furnace applications. To avoid conden- sate spillage, select a pump with an overflow switch.

Furnace condensate is mildly acidic, typically in the pH range of

3.2to 4.5. Due to corrosive nature of unneutralized condensate, a condensate pH neutralizing filter may be desired. Check with local authorities to determine if a pH neutralizer is required.

Ð29Ð

TABLE 6ÐVENT PIPE

TERMINATION CLEARANCES

LOCATION

CLEARANCE (FT)

U.S.A.

Canada

 

 

 

 

Above grade level or above antici-

1

pated snow depth

 

 

Dryer vent

3

3

From plumbing vent stack

3

3

From any mechanical fresh air intake

1

6

For furnaces with an input capacity of

 

 

100,000 Btuh or lessÐfrom any non-

 

 

mechanical air supply (windows or

1

1

doors which can be opened) or

 

 

combustion-air opening

 

 

For furnaces with an input capacity

 

 

greater than 100,000 BtuhÐfrom any

 

 

non-mechanical air supply (windows

1

3

or doors which can be opened) or

 

 

combustion-air opening

 

 

From service regulator vent, electric

4*

and gas meters, and relief equipment

 

 

Above grade when adjacent to public

Note 3

Note 3

walkway

 

 

* Horizontal distance.

² 18 in. above roof surface in Canada.

³36 in. to electric meter in Canada only.

NOTES:

1. If installing 2 adjacent 345MAV Furnaces, refer to Multiventing and Vent Terminations section for proper vent configurations.

2. When locating vent terminations, consideration must be given to prevailing winds, location, and other conditions which may cause recirculation of the appliance's own flue products or the flue products of adjacent vents. Recircu- lation can cause poor combustion, inlet condensate problems, and accelerated corrosion of heat exchangers.

3. Vent termination can not terminate less than 2 ft horizontal and 7 ft above public walkway or where condensate vapor or droplets may be a hazard.

II.APPLICATION

The furnace, A/C, and humidifier drains may be combined and drained together. The A/C drain must have an external, field- supplied trap prior to the furnace drain connection. All drain connections (furnace, A/C, or humidifier) must be terminated into an open or vented drain as close to the respective equipment as possible to prevent siphoning of the equipment's drain.

See Fig. 36 for example of possible field drain attachment using 1/2-in. CPVC or PVC tee for vent and A/C or humidifier drain connection.

Outdoor draining of the furnace is permissible if allowed by local codes. Caution should be taken when freezing ambient may freeze drain pipe and prohibit draining.

WARNING: Caution should be taken to prevent drain- ing where slippery conditions may cause personal inju- ries. Excessive condensate draining may cause saturated soil conditions which may result in damage to plants.

III.CONDENSATE DRAIN PROTECTION

Freezing condensate left in condensate trap and drain line may cause cracks, and possible water damage may occur. If freeze protection is required, use condensate freeze protection accessory or equivalent 3 to 6 watt per ft at 120v and 40°F self-regulating, shielded, and waterproof heat tape. See Installation Instructions supplied with accessory or heat tape manufacturer's recommenda- tions.

1.Fold heat tape in half and wrap on itself 3 times.

2.Locate heat tape between sides of condensate trap back. (See Fig. 37.)

3.Use wire ties to secure heat tape in place. Wire ties can be positioned in notches of condensate trap sides. (See Fig. 37.)

Image 29
Contents Ð1Ð Electrostatic Discharge ESD Precautions→ ÐDimensional Drawing DimensionsÐ2Ð Unit SizeElectrostatic Discharge ESD Precautions Safety ConsiderationsMinimum Inches Clearance to Combustible Construction → ÐClearances to CombustiblesApplications General IntroductionII. Upflow Applications Condensate Trap Location Factory-Shipped OrientationCondensate Trap Location Alternate Upflow Orientation Ð5ÐCondensate Trap Field Drain Attachment Pressure Switch TubingÐ6Ð III. Downflow Applications Condensate Trap Freeze ProtectionCondensate Trap Location Condensate Trap TubingÐ8Ð IV. Horizontal Left SUPPLY-AIR Discharge ApplicationsÐ9Ð Horizontal Right SUPPLY-AIR Discharge ApplicationsConstruct a Working Platform ÐAttic Location and Working Platform Front Upflow or Downflow Horizontal II. Furnace Location Relative to Cooling Equipment AIR for Combustion and Ventilation General III. Hazardous LocationsII. Unconfined Space III. Confined SpaceCombustion AIR from Outdoors Through Horizontal Ducts Installation Leveling Legs if DesiredCombustion AIR from Outdoors Through Vertical Ducts Furnace Casing Width II. Installation on a Concrete SlabOpening Dimensions AIR Ducts IV. Installation in Horizontal ApplicationsGeneral Requirements Ductwork acoustical treatmentVI. Filter Arrangement Return Air ConnectionsÐfilter Information VII. Bottom Closure Panel171⁄2-IN. Wide Casings only VIII. GAS PipingNominal Length of Pipe FT Iron Internal Diameter Size Ðmaximum Capacity of Pipe CU FT PER HRElectrical Connections Length FT³ CKT BKR Amps Phase WiringÐelectrical Data Amps SizeÐWiring Diagram III. Accessories II -V WiringVenting Removal of Existing Furnaces from Common Vent SystemsCombustion Air Pipe II. COMBUSTION-AIR and Vent PipingGeneral ÐCombustion-Air Inlet Pipe Assembly 4001 to 5000² Ðmaximum Allowable Vent Pipe Length FT3001 to 5001 to 6000² Ðmaximum Allowable Vent Pipe Length FT6001 to 7000² 7001 to 8000²9001 to 10,000² ÐShort Vent 5 to 8 Ft System040 060 080 100 120 Vent Extension PipeIV. Multiventing III. Vent TerminationCondensate Drain General Ðvent Pipe Termination ClearancesÐRoof Termination Preferred II. Cooling Mode Heating ModeIII. Continuous Blower Mode IV. Heat Pump ModeComponent Test START-UP Procedures GeneralComponent Test Sequence II. Prime Condensate Trap with WaterIV. Adjustments → ÐInducer Housing Drain TubeIII. Purge GAS Lines Set Gas Input RateAltitude BTU/CU FT4001 Only5000 Only 5001775 70018000 Only 8001Altitude Derate Multiplier Factor for U.S.A Ðaltitude Derate Multiplier for U.S.AExample Blower Off Delay Heat Mode Set Temperature RiseÐgas Rate CU FT/HR ±SPEED SelectorChecklist Check Safety Controls Check Primary Limit ControlII. Check Pressure Switch CHECKLISTÐSTART-UP ChecklistðinstallationLoad Calculation Vent Piping
Related manuals
Manual 12 pages 26.52 Kb Manual 12 pages 34 Kb

345MAV specifications

The Bryant 345MAV is a premier choice in the realm of residential heating and cooling systems, encapsulating advanced technologies, high efficiency, and remarkable performance. Designed for homeowners seeking reliability and comfort, this model exemplifies modern HVAC (Heating, Ventilation, and Air Conditioning) innovations.

One standout feature of the Bryant 345MAV is its impressive energy efficiency. With a high SEER (Seasonal Energy Efficiency Ratio) rating, it operates at peak levels while consuming less energy. This not only reduces utility bills but also supports environmental sustainability, making it an ideal selection for eco-conscious consumers. The model employs variable-speed technology, which allows the system to adjust its output based on current heating and cooling needs. As a result, it provides consistent indoor comfort while minimizing temperature fluctuations.

The Bryant 345MAV incorporates advanced refrigerant technologies designed for optimal performance. It uses R-410A refrigerant, which is known for its lower environmental impact compared to traditional refrigerants like R-22. This environmentally friendly aspect aligns with regulations aimed at reducing ozone depletion, thereby promoting a greener approach to heating and cooling.

Reliability is another hallmark of the Bryant 345MAV. Engineered with precision, this model features a durable build designed to withstand varying weather conditions. The system is equipped with a robust compressor that is engineered for longevity and minimal noise during operation. Homeowners will appreciate the quiet performance of the 345MAV, ensuring peace in their living spaces.

Comfort also extends to the user experience with the inclusion of a smart thermostat option. This integration allows homeowners to manage their heating and cooling systems remotely, enhancing convenience and control. Programmable settings can optimize energy use based on individual schedules, facilitating both comfort and savings.

In summary, the Bryant 345MAV is a top-tier solution for residential climate control, blending energy efficiency, innovative technology, and unmatched reliability. With its variable-speed operation, environmentally friendly refrigerant, and smart features, the 345MAV represents a significant advancement in the HVAC field. Homeowners investing in this model can expect a system that not only meets their heating and cooling needs but exceeds them in terms of efficiency and comfort.