Bryant 310AAV Electrical Shock and Fire Hazard, Furnace MAY not Operate, Wiring, BOX Relocation

Page 21

!WARNING

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow this warning could result in personal injury, death, or property damage.

The cabinet MUST have an uninterrupted or unbroken ground according to NEC ANSI/NFPA 70-2008 or local codes to minimize personal injury if an electrical fault should occur. This may consist of electrical wire, conduit approved for electrical ground or a listed, grounded power cord (where permitted by local code) when installed in accordance with existing electrical codes. Refer to the power cord manufacturer’s ratings for proper wire gauge. Do not use gas piping as an electrical ground.

!CAUTION

FURNACE MAY NOT OPERATE

Failure to follow this caution may result in intermittent furnace operation.

Furnace control must be grounded for proper operation or else control will lock out. Control must remain grounded through green/yellow wire routed to gas valve and manifold bracket screw.

115-V WIRING

Verify that the voltage, frequency, and phase correspond to that specified on unit rating plate. Also, check to be sure that service provided by utility is sufficient to handle load imposed by this equipment. Refer to rating plate or Table 7 for equipment electrical specifications.

Make all electrical connections in accordance with National Electrical Code (NEC) ANSI/NFPA 70-2008 and any local codes or ordinances that might apply.

!WARNING

FIRE HAZARD

Failure to follow this warning could result in personal injury, death, or property damage.

Do not connect aluminum wire between disconnect switch and furnace. Use only copper wire.

Use a separate, fused branch electrical circuit with a properly sized fuse or circuit breaker for this furnace. See Table 7 for wire size and fuse specifications. A readily accessible means of electrical disconnect must be located within sight of the furnace.

NOTE: Proper polarity must be maintained for 115-v wiring. If polarity is incorrect, control LED status indicator light will flash rapidly and furnace will NOT operate.

J-BOX RELOCATION

NOTE: If factory location of J-Box is acceptable, go to next section (ELECTRICAL CONNECTION TO J-BOX).

NOTE: On 14-in. (356 mm) wide casing models, the J-Box shall not be relocated to other side of furnace casing when the vent pipe is routed within the casing.

1.Remove and save two screws holding J-Box. (See Fig. 23.)

NOTE: The J-Box cover need not be removed from the J-Box in order to move the J-Box. Do NOT remove green ground screw inside J-Box. The ground screw is not threaded into the casing flange and can be lifted out of the clearance hole in casing

while swinging the front edge of the J-Box outboard of the casing.

2.Cut wire tie on loop in furnace wires attached to J-box.

3.Move J-Box to desired location.

4.Fasten J-Box to casing with two screws removed in Step 1.

5.Route J-Box wires within furnace away from sharp edges, rotating parts and hot surfaces.

ELECTRICAL CONNECTION TO J-BOX

Field-Supplied Electrical Box on Furnace J-Box Bracket See Fig. 24.

1.Remove cover from furnace J-Box.

2.Attach electrical box to furnace J-Box bracket with at least two field-supplied screws through holes in electrical box into holes in bracket. Use blunt-nose screws that will not pierce wire insulation.

3.Route furnace power wires through holes in electrical box and J-Box bracket, and make field-wire connections in electrical box. Use best practices (NEC in U.S.) for wire bushings, strain relief, etc.

4.Route and secure field ground wire to green ground screw on J-Box bracket.

5.Connect line voltage leads as shown in Fig. 26.

6.Reinstall cover to J-Box. Do not pinch wires between cover and bracket. Electrical Box on Furnace Casing Side See Fig. 24.

!WARNING

FIRE OR ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury, death, or property damage.

If field-supplied manual disconnect switch is to be mounted on furnace casing side, select a location where a drill or fastener cannot damage electrical or gas components.

1.Select and remove a hole knockout in the casing where the electrical box is to be installed.

NOTE: Check that duct on side of furnace will not interfere with installed electrical box.

2.Remove the desired electrical box hole knockout and posi- tion the hole in the electrical box over the hole in the fur- nace casing.

3.Fasten the electrical box to casing by driving two field supplied screws from inside electrical box into casing steel.

4.Remove and save two screws holding J-Box. (See Fig. 23.)

5.Pull furnace power wires out of 1/2-in. (12 mm) diameter hole in J-Box. Do not loosen wires from strain-relief wire-tie on outside of J-Box.

6.Route furnace power wires through holes in casing and electrical box and into electrical box.

7.Pull field power wires into electrical box.

8.Remove cover from furnace J-Box.

9.Route field ground wire through holes in electrical box and casing, and into furnace J-Box.

10.Reattach furnace J-Box to furnace casing with screws re- moved in Step 4.

11.Secure field ground wire to J-Box green ground screw.

310AAV

21

Image 21
Contents 310AAV/JAV Safety Considerations Furnace Reliability HazardCUT Hazard 20/060155 Inlet Width SizeSafety IntroductionCodes and Standards Location Electrostatic Discharge ESD Precautions ProcedureFire and Explosion Hazard Multipoise OrientationsPersonal Injury AND/OR Property Damage Hazard AIR for Combustion VentilationFire Hazard Location Relative to Cooling EquipmentOutdoor Combustion Air Method Carbon Monoxide Poisoning HazardOther than FAN-ASSISTED Total Upflow Installation InstallationBottom Return Air Inlet Side Return Air InletLeveling Legs Leveling Legs If Desired Downflow InstallationPlatform Furnace Support Suspended Furnace SupportRoll-Out Protection Filter Arrangement Carbon Monoxide and Poisoning HazardAIR Ducts Opening Dimensions In. mmGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsAir Delivery CFM with Filter Furnace RETURN---AIR SpeedSize Inlet Furnace ⎯ Air Delivery CFM with FilterHorizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions GAS Piping Fire or Explosion Hazard Return Air ConnectionsMaximum Capacity of Pipe Furnace Overheat HazardElectrical Connections Electrical Shock Hazard Burner and ManifoldElectrical Shock and Fire Hazard WiringFurnace MAY not Operate BOX RelocationPower Cord Installation in Furnace J-BOX BX Cable Installation in Furnace J-BOXElectrical Data Furnace Control Accessories VentingGeneral Venting Requirements Masonry Chimney Requirements Chimney Inspection Chart Additional Venting Requirements Appliance Application RequirementsBurn Hazard Sidewall VentingVent Height Internal Area of ChimneyDiameter Height Orientation Input BTUH/HR Upflow Application-Vent Elbow UpDownflow Application-Vent Elbow Up then Left Horizontal Right Application-Vent Elbow Right Start-Up Procedures START-UP, ADJUSTMENT, and Safety CheckAdjustments GeneralNever Assume Orifice SIZE. Always Check and Verify Furnace Damage HazardFurnace Overheating Hazard Speed SelectionWiring Diagram Gas Control Valve Orifice Hole Checklist Check Safety ControlsGas Rate cu ft./hr Filter Size Information In. / mmSeconds for Size of Test Dial Revolution BTU/CU FT Specific Gravity of Natural GAS Altitude RangeSpecific Gravity of Natural GAS Altitude Range Heat Value AT Altitude Altitude Specific Gravity of Natural GASIntroduction Service and Maintenance ProceduresCare and Maintenance Cleaning AND/OR Replacing AIR FilterCarbon Monoxide Poisoning and Fire Hazard Media cabinet filter procedures Blower Motor and Wheel Electrical Shock HazardUnit Damage Hazard Igniter Position-Side View Cleaning Heat ExchangerHeating Sequence of OperationTroubleshooting Wiring DiagramsCooling Mode Continuous Blower ModeTroubleshooting Guide Chimneyin KitAdapter VentBlocked usedswitch Description Part Number Accessory ListParts Replacement Information Guide
Related manuals
Manual 45 pages 34.04 Kb

310AAV specifications

The Bryant 310AAV and 310JAV are high-efficiency air conditioning and heating systems designed for residential and light commercial applications. These models embody Bryant's commitment to delivering reliable comfort solutions while prioritizing energy efficiency and performance.

One of the standout features of the Bryant 310AAV and 310JAV is their impressive Seasonal Energy Efficiency Ratio (SEER) ratings. The higher the SEER, the more efficient the unit is in using electricity to cool your space. The Bryant 310AAV boasts a SEER rating of up to 16, while the 310JAV offers a slightly lower rating. This efficiency translates into cost savings on monthly energy bills while ensuring indoor comfort throughout the year.

Both models utilize advanced technologies, including two-stage heating and cooling capabilities. This means that the systems can adjust their operation based on the heating or cooling needs of a space, providing optimal temperature control while reducing energy waste. The two-stage operation also contributes to quieter operation levels, making these units suitable for residential settings where noise is a concern.

The 310AAV and 310JAV are equipped with variable-speed compressors, which further enhance their efficiency and comfort levels. The variable-speed technology allows the system to operate at different speeds, ensuring consistent temperature management and reducing the frequency of on-and-off cycling. This leads to steadier indoor temperatures and improved humidity control.

In addition to their performance features, Bryant places a strong emphasis on durability and dependability. The units are constructed with high-quality materials that are designed to withstand various environmental conditions. Features such as a weather-resistant cabinet and an efficient coil design help protect the units from wear and tear, ensuring long-lasting performance.

The implementation of environmentally friendly refrigerant options is another characteristic that demonstrates Bryant's commitment to sustainability. Both the 310AAV and 310JAV utilize R-410A refrigerant, which has a lower environmental impact compared to older refrigerants, aligning with modern standards for eco-friendly HVAC systems.

Overall, the Bryant 310AAV and 310JAV represent a blend of efficiency, advanced technology, and durability. With their attractive SEER ratings, two-stage operation, variable-speed capabilities, and commitment to sustainability, these models stand out as excellent choices for homeowners and businesses looking to enhance their heating and cooling solutions while keeping energy consumption in check. Whether for residential comfort or light commercial use, these Bryant units promise reliability and performance for years to come.