Bryant 310AAV instruction manual Internal Area of Chimney, Vent Height

Page 28

310AAV

Table 8—Exterior Masonry Chimney Fan + Nat Installations with Type-B Double Wall Vent Connectors ENFPA & AGA Combined Appliance Maximum Input

Rating in Thousands of Btuh per Hour

 

INTERNAL AREA OF CHIMNEY

VENT HEIGHT

 

SQ. IN. (SQ. MM)

 

FT. (M)

 

 

 

 

12

19

28

38

 

(7741)

(12258)

(18064)

(24516)

 

 

 

 

 

6 (1.8)

74

119

178

257

8 (2.4)

80

130

193

279

10 (3.0)

84

138

207

299

15 (4.5)

NR

152

233

334

20 (6.0)

NR

NR

250

368

30 (9.1)

NR

NR

NR

404

Table 9—Minimum Allowable Input Rating of Space-Heat-

ing Appliance in Thousands of Btuh per Hour

 

INTERNAL AREA OF CHIMNEY

VENT HEIGHT

 

SQ. IN. (SQ. MM)

 

FT. (M)

12

19

28

38

 

(7741)

(12258)

18064)

(24516)

Local 99% Winter Design Temperature: 17 to 26 degrees F

6

0

55

99

141

8

52

74

111

154

10

NR

90

125

169

15

NR

NR

167

212

20

NR

NR

212

258

30

NR

NR

NR

362

Local 99% Winter Design Temperature: 5 to 16 degrees F*

6

NR

78

121

166

8

NR

94

135

182

10

NR

111

149

198

15

NR

NR

193

247

20

NR

NR

NR

293

30

NR

NR

NR

377

Local 99% Winter Design Temperature: --- 10 to 4 degrees F*

6

NR

NR

145

196

8

NR

NR

159

213

10

NR

NR

175

231

15

NR

NR

NR

283

20

NR

NR

NR

333

30

NR

NR

NR

NR

Local 99% Winter Design Temperature: --- 11_F (16_C) or

lower

Not recommended for any vent configuration.

*The 99.6% heating db temperatures found in the 1997 or 2001 ASHRAE Fundamentals Handbook, Climatic Design Information chapter, Table 1A (United States) or the 2005 ASHRAE Fundamentals handbook, Climatic Design Information chapter, and the CD ---ROM included with the 2005 ASHRAE Fundamentals Handbook.

28

Image 28
Contents 310AAV/JAV Furnace Reliability Hazard Safety ConsiderationsCUT Hazard Inlet Width Size 20/060155Introduction SafetyCodes and Standards Electrostatic Discharge ESD Precautions Procedure LocationMultipoise Orientations Fire and Explosion HazardAIR for Combustion Ventilation Personal Injury AND/OR Property Damage HazardFire Hazard Location Relative to Cooling EquipmentCarbon Monoxide Poisoning Hazard Outdoor Combustion Air MethodOther than FAN-ASSISTED Total Installation Upflow InstallationBottom Return Air Inlet Side Return Air InletDownflow Installation Leveling Legs Leveling Legs If DesiredSuspended Furnace Support Platform Furnace SupportRoll-Out Protection Filter Arrangement Carbon Monoxide and Poisoning HazardOpening Dimensions In. mm AIR DuctsGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsFurnace RETURN---AIR Speed Air Delivery CFM with FilterSize Inlet ⎯ Air Delivery CFM with Filter FurnaceHorizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions Return Air Connections GAS Piping Fire or Explosion HazardMaximum Capacity of Pipe Furnace Overheat HazardBurner and Manifold Electrical Connections Electrical Shock HazardWiring Electrical Shock and Fire HazardFurnace MAY not Operate BOX RelocationBX Cable Installation in Furnace J-BOX Power Cord Installation in Furnace J-BOXElectrical Data Furnace Control Venting AccessoriesGeneral Venting Requirements Masonry Chimney Requirements Chimney Inspection Chart Appliance Application Requirements Additional Venting RequirementsBurn Hazard Sidewall VentingInternal Area of Chimney Vent HeightUpflow Application-Vent Elbow Up Diameter Height Orientation Input BTUH/HRDownflow Application-Vent Elbow Up then Left Horizontal Right Application-Vent Elbow Right START-UP, ADJUSTMENT, and Safety Check Start-Up ProceduresAdjustments GeneralFurnace Damage Hazard Never Assume Orifice SIZE. Always Check and VerifySpeed Selection Furnace Overheating HazardWiring Diagram Gas Control Valve Orifice Hole Check Safety Controls ChecklistFilter Size Information In. / mm Gas Rate cu ft./hrSeconds for Size of Test Dial Revolution Specific Gravity of Natural GAS Altitude Range BTU/CU FTSpecific Gravity of Natural GAS Altitude Range Heat Value AT Altitude Specific Gravity of Natural GAS AltitudeService and Maintenance Procedures IntroductionCleaning AND/OR Replacing AIR Filter Care and MaintenanceCarbon Monoxide Poisoning and Fire Hazard Blower Motor and Wheel Electrical Shock Hazard Media cabinet filter proceduresUnit Damage Hazard Cleaning Heat Exchanger Igniter Position-Side ViewSequence of Operation HeatingWiring Diagrams TroubleshootingCooling Mode Continuous Blower ModeTroubleshooting Guide Chimneyin KitAdapter VentBlocked usedswitch Accessory List Description Part NumberParts Replacement Information Guide
Related manuals
Manual 45 pages 34.04 Kb

310AAV specifications

The Bryant 310AAV and 310JAV are high-efficiency air conditioning and heating systems designed for residential and light commercial applications. These models embody Bryant's commitment to delivering reliable comfort solutions while prioritizing energy efficiency and performance.

One of the standout features of the Bryant 310AAV and 310JAV is their impressive Seasonal Energy Efficiency Ratio (SEER) ratings. The higher the SEER, the more efficient the unit is in using electricity to cool your space. The Bryant 310AAV boasts a SEER rating of up to 16, while the 310JAV offers a slightly lower rating. This efficiency translates into cost savings on monthly energy bills while ensuring indoor comfort throughout the year.

Both models utilize advanced technologies, including two-stage heating and cooling capabilities. This means that the systems can adjust their operation based on the heating or cooling needs of a space, providing optimal temperature control while reducing energy waste. The two-stage operation also contributes to quieter operation levels, making these units suitable for residential settings where noise is a concern.

The 310AAV and 310JAV are equipped with variable-speed compressors, which further enhance their efficiency and comfort levels. The variable-speed technology allows the system to operate at different speeds, ensuring consistent temperature management and reducing the frequency of on-and-off cycling. This leads to steadier indoor temperatures and improved humidity control.

In addition to their performance features, Bryant places a strong emphasis on durability and dependability. The units are constructed with high-quality materials that are designed to withstand various environmental conditions. Features such as a weather-resistant cabinet and an efficient coil design help protect the units from wear and tear, ensuring long-lasting performance.

The implementation of environmentally friendly refrigerant options is another characteristic that demonstrates Bryant's commitment to sustainability. Both the 310AAV and 310JAV utilize R-410A refrigerant, which has a lower environmental impact compared to older refrigerants, aligning with modern standards for eco-friendly HVAC systems.

Overall, the Bryant 310AAV and 310JAV represent a blend of efficiency, advanced technology, and durability. With their attractive SEER ratings, two-stage operation, variable-speed capabilities, and commitment to sustainability, these models stand out as excellent choices for homeowners and businesses looking to enhance their heating and cooling solutions while keeping energy consumption in check. Whether for residential comfort or light commercial use, these Bryant units promise reliability and performance for years to come.