Bryant 310AAV instruction manual Carbon Monoxide Poisoning Hazard, Outdoor Combustion Air Method

Page 8

310AAV

!WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal injury or death.

The operation of exhaust fans, kitchen ventilation fans, clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make-up air MUST be provided for the ventilation devices, in addition to that required by the furnace. Refer to Carbon Monoxide Poisoning Hazard warning in venting section of these instructions to determine if an adequate amount of make-up air is available.

The requirements for combustion and ventilation air depend upon whether or not the furnace is located in a space having a volume of at least 50 cu/ft. per 1,000 Btuh input rating for all gas appliances installed in the space.

SSpaces having less than 50 cu/ft. per 1,000 Btuh re- quire the OUTDOOR COMBUSTION AIR METHOD.

SSpaces having at least 50 cu/ft. per 1,000 Btuh may use the INDOOR COMBUSTION AIR, STANDARD or

KNOWN AIR INFILTRATION METHOD.

Outdoor Combustion Air Method

1.Provide the space with sufficient air for proper combus- tion, ventilation, and dilution of flue gases using perman- ent horizontal or vertical duct(s) or opening(s) directly communicating with the outdoors or spaces that freely communicate with the outdoors.

2.Fig. 7 illustrates how to provide TWO OUTDOOR OPENINGS, one inlet and one outlet combustion and ventilation air opening, to the outdoors.

e. One opening MUST commence within 12 in. (300 mm) of the ceiling and the second opening MUST commence within 12 in. (300 mm) of the floor.

f.Size openings and ducts per Fig. 7 and Table 2.

g.TWO HORIZONTAL DUCTS require 1 sq./in. of free area per 2,000 Btuh (1,100 mm2/kW) of combined input for all gas appliances in the space per Fig. 7 and Table 2.

h.TWO OPENINGS OR VERTICAL DUCTS require 1 sq./in. of free area per 4,000 Btuh (550 mm2/kW) for combined input of all gas appliances in the space per Fig. 7 and Table 2.

3.ONE OUTDOOR OPENING requires:

a.1 square inch of free area per 3,000 Btuh (734 mm2/kW) for combined input of all gas appliances in the space per Table 2 and

b.Not less than the sum of the areas of all vent connect- ors in the space.

The opening shall commence within 12 in. (300 mm) of the ceiling. Appliances in the space shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.

Indoor Combustion Air NFPA & AGA

Standard and Known-Air-Infiltration Rate Methods

Indoor air is permitted for combustion, ventilation, and dilution, if the Standard or Known-Air-Infiltration Method is used.

!WARNING

CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in death and/or personal injury.

Many homes require air to be supplied from outdoors for furnace combustion, ventilation, and dilution of flue gases. The furnace combustion air supply must be provided in accordance with this instruction manual.

Table 2—Minimum Free Area Required for Each Combustion Air Opening of Duct to Outdoors

 

TWO HORIZONTAL DUCTS

 

 

SINGLE DUCT OR OPENING

 

TWO OPENINGS OR VERTICAL

 

 

 

 

 

DUCTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FURNACE

 

(1 SQ. IN./2,000 BTUH)

 

 

(1 SQ. IN./3,000 BTUH)

 

(1 SQ. IN./4,000 BTUH)

INPUT

 

(1,100 SQ. MM/KW)

 

 

 

 

(734 SQ. MM/KW)

 

 

(550 SQ. MM/KW)

(BTUH)

 

 

 

 

 

 

 

 

 

Free Area of Open-

 

Round Duct

 

Free Area of Open-

Round Duct

Free Area of Open-

 

Round Duct

 

ing and Duct

 

Dia.

 

 

ing and Duct

Dia.

 

ing and Duct

 

Dia.

 

Sq. In. (Sq. mm)

 

In. (mm)

 

 

Sq. In. (Sq. mm)

In. (mm)

Sq. In. (Sq. mm)

 

In. (mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

44,000

22

(14194)

 

6

(152)

 

 

14.7

(9484)

5 (127)

 

11

(7096)

 

4 (102)

66,000

33

(21290)

 

7

(178)

 

 

22.0

(14193)

6 (152)

 

16.5

(10645)

 

5 (127)

88,000

44

(28387)

 

8

(203)

 

 

29.3

(18903)

7 (178)

 

22

(14193)

 

6 (152)

110,000

55

(35484)

 

9

(229)

 

 

36.7

(23677)

7 (178)

 

27.5

(17742)

 

6 (152)

132,000

66

(42580)

 

10

(254)

 

 

44 .0 (28387)

8 (203)

 

33

(21290)

 

7 (178)

154,000

77

(49677)

 

10

(254)

 

 

51.3

(33096)

9 (229)

 

38.5

(24839)

 

8 (203)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXAMPLES: Determining Free Area

 

 

 

 

 

FURNACE

 

WATER HEATER

 

 

TOTAL INPUT

 

 

 

 

 

 

 

110,000

+

30,000

 

 

=

(140,000 divided by 4,000)

= 35.0 Sq. In. for each two Vertical Ducts or Openings

66,000

+

40,000

 

 

=

(106,000 divided by 3,000)

= 35.3

Sq. In. for a Single Duct or Opening

 

88,000

+

30,000

 

 

=

(118,000 divided by 2,000)

= 59.0

Sq. In. for each of two Horizontal Ducts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

Image 8
Contents 310AAV/JAV CUT Hazard Safety ConsiderationsFurnace Reliability Hazard Inlet Width Size 20/060155Codes and Standards SafetyIntroduction Electrostatic Discharge ESD Precautions Procedure LocationMultipoise Orientations Fire and Explosion HazardAIR for Combustion Ventilation Personal Injury AND/OR Property Damage HazardFire Hazard Location Relative to Cooling EquipmentCarbon Monoxide Poisoning Hazard Outdoor Combustion Air MethodOther than FAN-ASSISTED Total Installation Upflow InstallationBottom Return Air Inlet Side Return Air InletDownflow Installation Leveling Legs Leveling Legs If DesiredSuspended Furnace Support Platform Furnace SupportRoll-Out Protection Filter Arrangement Carbon Monoxide and Poisoning HazardOpening Dimensions In. mm AIR DuctsGeneral Requirements Ductwork Acoustical Treatment Supply Air ConnectionsSize Inlet Air Delivery CFM with FilterFurnace RETURN---AIR Speed ⎯ Air Delivery CFM with Filter FurnaceHorizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions Return Air Connections GAS Piping Fire or Explosion HazardMaximum Capacity of Pipe Furnace Overheat HazardBurner and Manifold Electrical Connections Electrical Shock HazardWiring Electrical Shock and Fire HazardFurnace MAY not Operate BOX RelocationElectrical Data Power Cord Installation in Furnace J-BOXBX Cable Installation in Furnace J-BOX Furnace Control General Venting Requirements AccessoriesVenting Masonry Chimney Requirements Chimney Inspection Chart Appliance Application Requirements Additional Venting RequirementsBurn Hazard Sidewall VentingInternal Area of Chimney Vent HeightUpflow Application-Vent Elbow Up Diameter Height Orientation Input BTUH/HRDownflow Application-Vent Elbow Up then Left Horizontal Right Application-Vent Elbow Right START-UP, ADJUSTMENT, and Safety Check Start-Up ProceduresAdjustments GeneralFurnace Damage Hazard Never Assume Orifice SIZE. Always Check and VerifySpeed Selection Furnace Overheating HazardWiring Diagram Gas Control Valve Orifice Hole Check Safety Controls ChecklistSeconds for Size of Test Dial Revolution Gas Rate cu ft./hrFilter Size Information In. / mm Specific Gravity of Natural GAS Altitude Range BTU/CU FTSpecific Gravity of Natural GAS Altitude Range Heat Value AT Altitude Specific Gravity of Natural GAS AltitudeService and Maintenance Procedures IntroductionCarbon Monoxide Poisoning and Fire Hazard Care and MaintenanceCleaning AND/OR Replacing AIR Filter Unit Damage Hazard Media cabinet filter proceduresBlower Motor and Wheel Electrical Shock Hazard Cleaning Heat Exchanger Igniter Position-Side ViewSequence of Operation HeatingWiring Diagrams TroubleshootingCooling Mode Continuous Blower ModeTroubleshooting Guide Chimneyin KitAdapter VentBlocked usedswitch Accessory List Description Part NumberParts Replacement Information Guide
Related manuals
Manual 45 pages 34.04 Kb