Bryant 310AAV instruction manual Sequence of Operation, Heating

Page 47

1-7/8

(47.6 mm)

A05026

Fig. 47 ---Igniter Position-Top View

A01050

Fig. 48 ---Cleaning Heat Exchanger Cell

(4)Insert brush end of cable in burner inlet opening of cell, and proceed to clean 2 lower passes of cell in same manner as upper pass.

(5)Repeat foregoing procedures until each cell in furnace has been cleaned.

(6)Using vacuum cleaner, remove residue from each cell.

(7)Using vacuum cleaner with soft brush attachment, clean burner assembly.

(8)Clean flame sensor with fine steel wool.

(9)Install NOx baffles (if removed).

(10)Reinstall burner assembly. Center burners in cell openings.

10.Remove old sealant from cell panel and collector box flange.

11.Spray releasing agent on the heat exchanger cell panel where collector box assembly contacts cell panel.

NOTE: A releasing agent such as cooking spray or equivalent (must not contain corn or canola oil, aromatic or halogenated hydrocarbons or inadequate seal may occur) and RTV sealant (G.E. 162, 6702, or Dow-Corning 738) are needed before starting installation. DO NOT substitute any other type of RTV sealant. G.E. 162 (P771-9003) is available through RCD in 3-oz tubes.

12.Apply new sealant to flange of collector box and attach to cell panel using existing screws, making sure all screws are secure.

13.Reconnect wires to the following components. (Use con- nection diagram on wiring label, if wires were not marked for reconnection locations.):

a.Draft safeguard switch.

b.Inducer motor.

c.Pressure switch(es).

d.Limit over-temperature switch.

e.Gas valve.

f.Hot surface igniter.

g.Flame-sensing electrode.

h.Flame rollout switches.

i.Install NOx baffles (if removed).

14.Reinstall internal vent pipe, if applicable.

15.Reinstall vent connector on furnace vent elbow. Securely fasten vent connector to vent elbow with 2 field-supplied, corrosion-resistant, sheet metal screws located 180_ apart.

16.Replace blower access door only, if it was removed.

17.Set thermostat above room temperature and check furnace for proper operation.

18.Verify blower airflow and speed changes between heating and cooling.

!WARNING

FIRE OR EXPLOSION HAZARD

Failure to follow this warning could result in personal injury, death and/or property damage.

Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections.

19.Check for gas leaks.

20.Replace outer access door.

Step 3 Sequence of Operation

NOTE: Furnace control must be grounded for proper operation or control will lock out. Control is grounded through green/yellow wire routed to gas valve and manifold bracket screw.

Using the schematic diagram in Fig. 41, follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully.

NOTE: If a power interruption occurs during a call for heat (W), the control will start a 90-sec blower-only ON period two seconds after power is restored, if the thermostat is still calling for gas heating. The amber LED light will flash code 12 during the 90-sec period, after which the LED will be ON continuous, as long as no faults are detected. After the 90-sec period, the furnace will respond to the thermostat normally.

The blower door must be installed for power to be conducted through the blower door interlock switch ILK to the furnace control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot-surface igniter HSI, and gas valve GV.

1.Heating

(See Fig. 26 for thermostat connections.) The wall thermo- stat “calls for heat,” closing the R-to-W circuit. The fur- nace control performs a self-check, verifies the pressure switch contacts PRS are open, and starts the inducer motor IDM.

a.Inducer Prepurge Period- As the inducer motor IDM comes up to speed, the pressure switch contacts PRS close, 24 VAC power is supplied for a field in- stalled humidifier at the HUM terminal and the control begins a 15-sec prepurge period.

b.Igniter Warm-Up- At the end of the prepurge period, the Hot-Surface igniter HSI is energized for a 17-second igniter warm-up period.

c.Trial-for-Ignition Sequence- When the igniter warm-up period is completed, the main gas valve re- lay contacts GVR close to energize the gas valve GV, the gas valve opens, The gas valve GV permits gas flow to the burners where it is ignited by the HSI. Five seconds after the GVR closes, a 2-second flame prov- ing period begins. The HSI igniter will remain ener- gized until the flame is sensed or until the 2-second flame proving period begins.

310AAV

47

Image 47
Contents 310AAV/JAV CUT Hazard Safety ConsiderationsFurnace Reliability Hazard 20/060155 Inlet Width SizeCodes and Standards SafetyIntroduction Location Electrostatic Discharge ESD Precautions ProcedureFire and Explosion Hazard Multipoise OrientationsLocation Relative to Cooling Equipment AIR for Combustion VentilationPersonal Injury AND/OR Property Damage Hazard Fire HazardOutdoor Combustion Air Method Carbon Monoxide Poisoning HazardOther than FAN-ASSISTED Total Side Return Air Inlet InstallationUpflow Installation Bottom Return Air InletLeveling Legs Leveling Legs If Desired Downflow InstallationFilter Arrangement Carbon Monoxide and Poisoning Hazard Suspended Furnace SupportPlatform Furnace Support Roll-Out ProtectionDuctwork Acoustical Treatment Supply Air Connections Opening Dimensions In. mmAIR Ducts General RequirementsSize Inlet Air Delivery CFM with FilterFurnace RETURN---AIR Speed Furnace ⎯ Air Delivery CFM with FilterHorizontal Unit Suspension Typical Attic Installation Downflow Return Air Configurations and Restrictions Furnace Overheat Hazard Return Air ConnectionsGAS Piping Fire or Explosion Hazard Maximum Capacity of PipeElectrical Connections Electrical Shock Hazard Burner and ManifoldBOX Relocation WiringElectrical Shock and Fire Hazard Furnace MAY not OperateElectrical Data Power Cord Installation in Furnace J-BOXBX Cable Installation in Furnace J-BOX Furnace Control General Venting Requirements AccessoriesVenting Masonry Chimney Requirements Chimney Inspection Chart Sidewall Venting Appliance Application RequirementsAdditional Venting Requirements Burn HazardVent Height Internal Area of ChimneyDiameter Height Orientation Input BTUH/HR Upflow Application-Vent Elbow UpDownflow Application-Vent Elbow Up then Left Horizontal Right Application-Vent Elbow Right General START-UP, ADJUSTMENT, and Safety CheckStart-Up Procedures AdjustmentsNever Assume Orifice SIZE. Always Check and Verify Furnace Damage HazardFurnace Overheating Hazard Speed SelectionWiring Diagram Gas Control Valve Orifice Hole Checklist Check Safety ControlsSeconds for Size of Test Dial Revolution Gas Rate cu ft./hrFilter Size Information In. / mm BTU/CU FT Specific Gravity of Natural GAS Altitude RangeSpecific Gravity of Natural GAS Altitude Range Heat Value AT Altitude Altitude Specific Gravity of Natural GASIntroduction Service and Maintenance ProceduresCarbon Monoxide Poisoning and Fire Hazard Care and MaintenanceCleaning AND/OR Replacing AIR Filter Unit Damage Hazard Media cabinet filter proceduresBlower Motor and Wheel Electrical Shock Hazard Igniter Position-Side View Cleaning Heat ExchangerHeating Sequence of OperationContinuous Blower Mode Wiring DiagramsTroubleshooting Cooling ModeTroubleshooting Guide Chimneyin KitAdapter VentBlocked usedswitch Description Part Number Accessory ListParts Replacement Information Guide
Related manuals
Manual 45 pages 34.04 Kb

310AAV specifications

The Bryant 310AAV and 310JAV are high-efficiency air conditioning and heating systems designed for residential and light commercial applications. These models embody Bryant's commitment to delivering reliable comfort solutions while prioritizing energy efficiency and performance.

One of the standout features of the Bryant 310AAV and 310JAV is their impressive Seasonal Energy Efficiency Ratio (SEER) ratings. The higher the SEER, the more efficient the unit is in using electricity to cool your space. The Bryant 310AAV boasts a SEER rating of up to 16, while the 310JAV offers a slightly lower rating. This efficiency translates into cost savings on monthly energy bills while ensuring indoor comfort throughout the year.

Both models utilize advanced technologies, including two-stage heating and cooling capabilities. This means that the systems can adjust their operation based on the heating or cooling needs of a space, providing optimal temperature control while reducing energy waste. The two-stage operation also contributes to quieter operation levels, making these units suitable for residential settings where noise is a concern.

The 310AAV and 310JAV are equipped with variable-speed compressors, which further enhance their efficiency and comfort levels. The variable-speed technology allows the system to operate at different speeds, ensuring consistent temperature management and reducing the frequency of on-and-off cycling. This leads to steadier indoor temperatures and improved humidity control.

In addition to their performance features, Bryant places a strong emphasis on durability and dependability. The units are constructed with high-quality materials that are designed to withstand various environmental conditions. Features such as a weather-resistant cabinet and an efficient coil design help protect the units from wear and tear, ensuring long-lasting performance.

The implementation of environmentally friendly refrigerant options is another characteristic that demonstrates Bryant's commitment to sustainability. Both the 310AAV and 310JAV utilize R-410A refrigerant, which has a lower environmental impact compared to older refrigerants, aligning with modern standards for eco-friendly HVAC systems.

Overall, the Bryant 310AAV and 310JAV represent a blend of efficiency, advanced technology, and durability. With their attractive SEER ratings, two-stage operation, variable-speed capabilities, and commitment to sustainability, these models stand out as excellent choices for homeowners and businesses looking to enhance their heating and cooling solutions while keeping energy consumption in check. Whether for residential comfort or light commercial use, these Bryant units promise reliability and performance for years to come.